4.Setting DPC Power Jumpers. If the DPC is a Model 3335 or 3310, jumpers W1A and W1B on the System Interconnect Board must be removed to isolate the chassis connection from the 24V RET connection (see Figure 8). If it is a Model 3330, jumpers W1A, W1B and W1C on the System Interconnect Board must be removed. Series 3308 Gas Flow Computers, if used with these systems, provide an isolated instrument ground without setting jumpers.

Multiple Clusters of DPC Cabinets Powered by Local Supplies

A cluster consists of two or more DPC cabinets that may be grouped together as shown in Figure

9.Several such clusters performing related functions in the same facility make up a multiple cluster system. The following procedures apply:

1.Grounding for DPC Cabinet Cluster using Local Supply. The instrument ground (24VRET terminal) of each DPC in a cabinet must connect to a terminal block within that cabinet that is electrically isolated from the cabinet frame. This terminal block must provide termination for all instrument grounds within that cabinet and include termination for a multistranded, insulated, #4 gauge wire (or greater) that will connect to the same termination point to other cabinets of that cluster, and to the 24VRET terminal of the local power supply.

2.Routing of Cluster Grounds. The instrument grounds (isolated terminal) from each cabinet cluster must connect to each other and then to a single wire that connects to the zero reference point of the facility. This wire should be #4 gauge minimum (multistranded and insulated) and be contained in a metal conduit (pipe). A heavier stranded #4/0 gauge could be used to connect each cluster to the zero reference point while the #4 wire instrument grounds could be locally terminated to the #4/0 wire. The conduit containing this wire must also be connected by bonding strap to the cabinet and facility frame as described in the NEC.

3.AC Power Source. The 24 Vdc power supply of each cluster requires a 120 Vac power source. The ac power terminals of this supply are identified in Figure 8. The 120 Vac wiring for this supply must be contained in cable trays along with the power grid grounding wire. Figure 9 illustrates the cable tray layout and grounding points of a typical facility. The frame of each cabinet and each DPC chassis a cluster must be connected with bonding strap at points specified in the NEC.

4.Setting DPC Power Jumpers. If the DPC is a Model 3335 or 3310, jumpers W1A and W1B on the System Interconnect Board must be removed to isolate the chassis connection from the 24V RET connection (see Figure 8). If it is a Model 3330, jumpers W1A, W1B and W1C on the System Interconnect Board must be removed. Series 3308 Gas Flow Computers and Correctors, if used with these systems, provide an isolated instrument ground without setting jumpers.

References:

1.Grounding for the Control of EMI; Hugh W. Denny; Don White Consultants, Inc. (c) 1983, 1st Ed.

2.IEEE Std. 518-1982

3.ANSI/IEEE Std. 142-1982

14 / Supplement S1400

Image 72
Contents Remote Set Regulator Model 9110-00A IMPORTANT! Read Instructions Before Starting Warranty Mail Bristol IncPhone Bristol Inc. Repair Authorization Form off-line completion Training Telephone Support Technical Questions 860 860 945-2213 FAXVisit our Site on the World Wide Web Training Courses Model 9110-00A Remote SET Regulator Supplemental Instructions Product Description Theory of OperationAnalog Regulator Model Remote Set Regulator Block Diagram of Analog Type Regulator Guard Input Current OutputBlock Diagram of Raise/Lower Type Regulator Data Plate Raise/Lower Regulator ModelModel Number Breakdown = Pneumatic Output = Mounting Arrangement Page General MountingTwo-Inch Pipe Mounting In-Line MountingPressure Connections General PipingRegulator Assembly Moisture in LinesInternal Access Line SizeVenting Body and CoverSafety Note Electrical Conduit PortPage Using Option Switches Cradle Switches with Open DesignationSlide Switches with on Designation Switch Functions Regulator Assembly Switch SW1 & SW2 Functions & SettingsAnalog Input Models RAISE/LOWER Input ModelsContinuous Signal Incremental SignalSwitch SW1 1-5, Pulse Increments Input FilterGuard Input Output Rate of ChangeStatic or Dynamic Guard Input Guard LogicSwitch SW2 2-5, Output Rate Of Change Analog Failure Modes Fail Hold & Fail ZeroFAIL-ZERO Mode Page Field Wiring Terminal Identification For Analog Input Models Terminal Identification For Raise/Lower ModelsAnalog Voltage Input with Guard Analog Current Input 4-20 mA with Guard RAISE/LOWER Inputs with GuardRaise/Lower & Guard Inputs from Relay Contacts DC Power Current Output to FSK Bi-State TransmitterOperating Notes Initial ChecksField Wiring CI-9110 Service Troubleshooting Hints Setting Output Limits Test SetupProcedure General PrinciplesCalibration Test Setup Calibration PrecautionAnalog Test Setup Preliminary Calibration CheckDetailed Calibration for Analog Model Feedback Zero & SpanCurrent Output Span & Load Pressure Output CheckRaise/Lower Test Setup Detailed Calibration for RAISE/LOWER ModelPCB Reference Drawings CPU Board & Termination Board Reference TableAssembly, Analog Type CPU Board with Current Output Assembly, Raise/Lower Type CPU Board with Current Output Analog Input Model RAISE/LOWER Input ModelAnalog Output Accuracy Analog ModelsAccuracy RAISE/LOWER Models Stepper Drive MechanismPressure Regulator Assembly Instrument EnclosureEnvironmental Range Factory Calibrated withHumidity 10 to 95% over -20to +130 F -29to +55 Range Model 9110 Main Parts Parts Referenced in FigureRemote Set Regulator Actuator Unit Remote Set Regulator Actuator Unit Mounting Parts Remote Set Regulator Assembly Basic Parts Remote SET Regulator Basic PartsGuidelines for System Grounding Basic Ground Rod Installation Noise and Signal Errors General RecommendationsGrounding of Equipment Housing Transients and Interference Grounding of Transmitter Types of Earth Grounds AC Power Grounding System Dry Soil Sandy SoilRocky Soil Several DPCs Mounted in Metal Cabinet with Power Supply Following installation procedures applyGrounding for DPCs and Power Supplies Single Metal Cabinet Multiple DPC Cabinets Powered by Single Power Supply Elements of a Facility Ground System Multiple Clusters of DPC Cabinets Powered by Local Supplies ReferencesPage Remote Set Regulator Model 9110-00A