SPECIFICATIONS

6.1 ANALOG INPUT MODEL

Function:

Uses Analog Input to set a pressure output signal.

Ranges:

4 - 20 mA dc or 1 - 5 Vdc

Input Impedance:

For 1 - 5 V > 330 K Ohms

 

For 4 - 20 mA > 250 Ohms, ±0.1%

Analog Fault Detector:

Stepper Motor is cut off when AI < 0.8 V, ±0.1V

6.2 RAISE/LOWER INPUT MODEL

Function:

Uses Raise and Lower Inputs to set a pres-

 

sure output signal. Input may be configured

 

to accept a continuous ON/OFF dc signal or

 

incrementing dc pulse signal.

Input Characteristics:

Opto-isolated and bi-polar. Limited to 47 V by

 

metal oxide varistor (MOV).

Types of Inputs Accepted:

May be configured for continuous dc input

 

signal (On or Off) or dc pulse incrementing

 

signal.

Continuous DC Input:

Maximum dc input level is a function of the

 

supply voltage as follows:

 

12V Model: 11 - 14 Vdc

 

24V Model: 22 - 28 Vdc

DC Pulse Incrementing Input:

Pulse rates adjustable from 0.110%/pulse to

 

1.830%/pulse. Pulse must be held in TRUE

 

state for time period necessary for Regulator

 

to reach the new output value. An input that

 

changes state before completion of an

 

operation will have its remaining pulse in-

 

crement discarded. The next complete pulse

 

starts a new increment.

Input Impedance:

For 12V Model: 1800 Ohms

 

For 24V Model: 4300 Ohms

CI-9110

6-1

Specifications

Image 51
Contents Remote Set Regulator Model 9110-00A IMPORTANT! Read Instructions Before Starting Warranty Mail Bristol IncPhone Bristol Inc. Repair Authorization Form off-line completion Training 860 860 945-2213 FAX Telephone Support Technical QuestionsVisit our Site on the World Wide Web Training Courses Model 9110-00A Remote SET Regulator Supplemental Instructions Product Description Theory of OperationAnalog Regulator Model Remote Set Regulator Block Diagram of Analog Type Regulator Current Output Guard InputBlock Diagram of Raise/Lower Type Regulator Data Plate Raise/Lower Regulator ModelModel Number Breakdown = Pneumatic Output = Mounting Arrangement Page In-Line Mounting GeneralMounting Two-Inch Pipe MountingGeneral Piping Pressure ConnectionsMoisture in Lines Regulator AssemblyBody and Cover Internal AccessLine Size VentingElectrical Conduit Port Safety NotePage Using Option Switches Cradle Switches with Open DesignationSlide Switches with on Designation RAISE/LOWER Input Models Switch FunctionsRegulator Assembly Switch SW1 & SW2 Functions & Settings Analog Input ModelsIncremental Signal Continuous SignalInput Filter Switch SW1 1-5, Pulse IncrementsGuard Logic Guard InputOutput Rate of Change Static or Dynamic Guard InputAnalog Failure Modes Fail Hold & Fail Zero Switch SW2 2-5, Output Rate Of ChangeFAIL-ZERO Mode Page Field Wiring Terminal Identification For Raise/Lower Models Terminal Identification For Analog Input ModelsAnalog Voltage Input with Guard RAISE/LOWER Inputs with Guard Analog Current Input 4-20 mA with GuardRaise/Lower & Guard Inputs from Relay Contacts Current Output to FSK Bi-State Transmitter DC PowerInitial Checks Operating NotesField Wiring CI-9110 Service Troubleshooting Hints General Principles Setting Output LimitsTest Setup ProcedureCalibration Precaution Calibration Test SetupPreliminary Calibration Check Analog Test SetupPressure Output Check Detailed Calibration for Analog ModelFeedback Zero & Span Current Output Span & LoadDetailed Calibration for RAISE/LOWER Model Raise/Lower Test SetupCPU Board & Termination Board Reference Table PCB Reference DrawingsAssembly, Analog Type CPU Board with Current Output Assembly, Raise/Lower Type CPU Board with Current Output RAISE/LOWER Input Model Analog Input ModelStepper Drive Mechanism Analog OutputAccuracy Analog Models Accuracy RAISE/LOWER ModelsRange Factory Calibrated with Pressure Regulator AssemblyInstrument Enclosure EnvironmentalHumidity 10 to 95% over -20to +130 F -29to +55 Range Parts Referenced in Figure Model 9110 Main PartsRemote Set Regulator Actuator Unit Remote Set Regulator Actuator Unit Mounting Parts Remote SET Regulator Basic Parts Remote Set Regulator Assembly Basic PartsGuidelines for System Grounding Basic Ground Rod Installation General Recommendations Noise and Signal ErrorsGrounding of Equipment Housing Transients and Interference Grounding of Transmitter Types of Earth Grounds AC Power Grounding System Dry Soil Sandy SoilRocky Soil Following installation procedures apply Several DPCs Mounted in Metal Cabinet with Power SupplyGrounding for DPCs and Power Supplies Single Metal Cabinet Multiple DPC Cabinets Powered by Single Power Supply Elements of a Facility Ground System References Multiple Clusters of DPC Cabinets Powered by Local SuppliesPage Remote Set Regulator Model 9110-00A