6.3 GUARD INPUT
Enables or inhibits command signal input on both Analog and raise/Lower models.
6.4 ANALOG OUTPUT
Function: | Current feedback signal tracks the output of |
| the Remote Set Regulator. Signal is typically |
| used to telemeter pressure output value back |
| to the command site. |
Range: | 4 - 20 mA common ground type output |
Load Resistance: | 380 Ohms Max. |
6.5 ACCURACY - ANALOG MODELS
Electrical Input to Pressure Output: ±5% of span
Pressure output to Feedback: | ±5% of span |
6.6 ACCURACY - RAISE/LOWER MODELS
Feedback Volts to Pressure Output: | ±5% of span |
Pulse Input to Pressure Output: | ±20% of span |
6.7 DC POWER |
|
12 Volt Model: | 11 - 14 Vdc @ 0.35 A Max. |
24 Volt Model: | 22 - 28 Vdc @ 0.25 A Max. |
Fuse: | 1 A, 250 Vdc, 3AG |
6.8 STEPPER DRIVE MECHANISM | |
Stepper Motor: | Gearing from motor shaft to pressure |
| regulator assembly results in approximately |
| 22,000 incremental steps for 100% output |
| range travel. |
Output Rate of Change: | Full scale sweep adjustable from 1.8 to 69.4 |
| minutes. |
Environmental Effects: | ±1.0% Max. full scale per 50°F (28°C) |
Supply Voltage Effect: | ±0.15% Max. full scale per 1 volt change |
Specifications |