3.2 WALL SLEEVE INSTALLATION

3.2.1 Wall Case Installation Data

For new construction, early planning with the architect is necessary. Unit location, electrical connection locations, and wall openings of the proper dimensions are essential to avoid the necessity of rework, fillers, framing, moving electrical outlets, and other expensive modifications.

General

Generally, units are installed 3" to 5" above the floor (flush to finished floor installation is possible) as near to the center of the room as possible; underneath a window or a glass panel is typical. Normal installation of the wall case allows installation flexibility; from flush with the finished interior wall to a minimum of 1/4" of the wall case extending beyond the finished exterior of the building.

Special consideration must be given to installations where the wall case does not extend a minimum of 1/4" beyond the finished exterior wall.

Regardless of the installation, there are several things to consider when selecting a location for installing the unit. For instance, drapery location could interfere with air discharge, and placement of furniture may have an impact on the performance of the unit. The following information is intended to minimize installation problems and assure you of trouble-free installation.

Refer to page 17 for required wall opening dimensions. Minimum recommended interior and exterior case projection for standard wall thicknesses are shown in the drawings in this manual. The case may be installed flush with the finished indoor wall.

Mounting an outdoor grille or louver section to the building face may cause a space between the outdoor coil and the louver section. Air splitters, aligned with the ends of the outdoor coil, must be installed between the outdoor coil inlet and outlet air streams. Gaps between the outdoor coil and the louver section may allow condenser air recirculation and affect the operation of the unit.

The wall case should be level from side to side and from level to 1/4 bubble tilt to the outdoors. The condensate disposal system in the unit is designed to dissipate the condensate water generated during cooling operation in accordance with ARI standards and actually uses this water for maximum unit efficiency. A level unit will also insure proper performance of the Internal Condensate Removal (ICR) system optional on heat pump units.

For existing construction it is important that carpentry, masonry and electrical work be performed by competent, qualified personnel. Since installations in existing construction may involve removal of building material from the structure, locating the wall case must be done correctly.

Copyright ©2008 LG Electronics. Inc. All right reserved.

- 18 -

Only for training and service purposes

LGE Internal Use Only

 

Image 18
Contents SVC Manual Specification LGE Internal Use OnlyFeatures and Benefits Sleeve and the Rear GrilleTemperature limits Door Switch/Occupancy SensorOutdoor Air Temperature Switchover Quick Heater RecoveryVentilation Control LocationsOperation Electric Heating Model Cooling only ModelRemoving the Front Grille Temperature LimitingAdditional Controls Additional ControlsEnergy Saver Molex Housing SpecREMOTE/LOCAL Control Front Desk ControlDisassembly Instructions Mechanical PartsFront Grille Control BOX AIR Handling Parts Electric Heater Electric Heater Model onlyCross Flow FAN Axial FANOutdoor Motor Electrical PartsShroud CompressorPower Cord 6 P.C.BEvaporator Refrigeration CycleCondenser Capillary TubeLGE Internal Use Only Pulling Vacuum Dimension of air conditioner InstallationHOW to Install the Unit Dimension of sleeve assembly optionalWall Sleeve Installation Wall Case Installation DataGeneral Preparation of the Front Grille Installation of Wall Case in Wall OpeningAs shipped, the LG wall sleeve is ready for installation Preparation of the Wall Case for All Types of ConstructionLGE Internal Use Only Sub-Base Connected Unit Installation Electrical Data for 230/208V Model Electrical SafetyElectrical Requirements 208, 230, and 208/230 Volt UnitsControl Panel Key Lock Field Installed AccessoriesInstallation DescriptionCondensate Disposal Pump Kit Installation Part No AYSB2101Hazardous Voltage Place the top cover assembly back into the unit Spraying Architecture Grille Aluminum Single Pack Architectural GrilleDrain Installation Condensate Drain kitPart No AYDR101 Outdoor Drain Kit Installation Outdoor Drain Kit InstallationLeveling Legs Indoor Drain Kit InstallationChecklist Part No AYLL101Leveling Leg Assembly Leveling Leg Assembly Installation on Wall SleevePart No AYAGALA01 Hard Wire KitJunction Box Kit Installation and Wiring Procedure Use Copper Conductors Only208/230 Volt Units Volt UnitsRemote Escutcheon Kit Part No AYRE110Subbase Part No AYSB1101 230/208V 20A AYSB2101 230/208V 30ASkirting Hole Location Right Cover Assembly After wiring is complete, mount covers a and F toTo each installation instruction for that accessory Subbase with provided screws. FigurePiping System Troubleshooting GuideOutside Dimensions 066mm 406mm 505mmTroubleshooting Guide Fails to Start Complaint Cause Remedy Room AIR Conditioner Voltage Limits 208/230V 187V 253VComplaint Cause Remedy Th3 Thermistor for outdoor Air temperature Piping DiagramsTh2 Thermistor for Evaporator pipe temperature Th4 Thermistor for Condenser pipe Air temperatureSchematic Diagram CN-NNExploded View 435300BJanuary