LG Electronics LP121HEM-Y8 manual REMOTE/LOCAL Control, Energy Saver, Front Desk Control

Page 7

REMOTE/LOCAL CONTROL

When remote/local switch #1 is on, it allow the unit to operate by the control of Remote Wall Thermostat. The unit control by knobs are not available.

ENERGY SAVER

The energy saver switch #2 is on. This switch is set at continuous fan to provide continuous fan operation in cool or heat modes. When the switch is off the continuous fan allows continuous circulation of room air and make the more balanced temperature of the room. When the switch is on the fan is on or off with the compressor or with the heater.

FRONT DESK CONTROL

When the pair wire is connected to the connector LOand LI, the unit can be turned ON or OFF with a switch located at the Front Desk Control panel. When the front desk switch is ON, the fan operate according to the condition of setting without working compressor and heater. When the front desk switch is OFF, the unit can operate according to the setting of controls.

Wire # AWG

Maximum Length

#22

600ft(180m)

#20

900ft(270m)

#18

1500ft(450m)

#16

2000ft(610m)

LO LI GL GH O W Y R C

Front Desk Switch

REMOTE WALL THERMOSTAT

When the wires are connected, the unit will be controlled by a remote wall thermostat.

The thermostat connections supply the 24 Volt AC. When you install the digital / electronic thermostat, you must set it to the 24 Volt AC. See the installation Instruction in this manual for the Remote Wall Thermostat.

24Volt-N

24Volt-L

Compressor

Heater

Reversing Valve

High Fan

Low Fan

LO LI GL GH O W Y R C

(Molex Housing Spec 396-09V)

Note:The following figures show wiring schematics for heat pump and straight cool units with electric heat, respectively.

Wiring Schematic for

Remote Heat Pump

Wiring Schematic for

Straight Cool Unit.

Copyright ©2008 LG Electronics. Inc. All right reserved.

- 7 -

Only for training and service purposes

LGE Internal Use Only

 

Image 7
Contents SVC Manual LGE Internal Use Only SpecificationSleeve and the Rear Grille Features and BenefitsQuick Heater Recovery Door Switch/Occupancy SensorOutdoor Air Temperature Switchover Temperature limitsCooling only Model Control LocationsOperation Electric Heating Model VentilationAdditional Controls Temperature LimitingAdditional Controls Removing the Front GrilleFront Desk Control Molex Housing SpecREMOTE/LOCAL Control Energy SaverMechanical Parts Disassembly InstructionsFront Grille Control BOX Electric Heater Electric Heater Model only AIR Handling PartsAxial FAN Cross Flow FANCompressor Electrical PartsShroud Outdoor Motor6 P.C.B Power CordCapillary Tube Refrigeration CycleCondenser EvaporatorLGE Internal Use Only Pulling Vacuum Dimension of sleeve assembly optional InstallationHOW to Install the Unit Dimension of air conditionerWall Case Installation Data Wall Sleeve InstallationGeneral Preparation of the Wall Case for All Types of Construction Installation of Wall Case in Wall OpeningAs shipped, the LG wall sleeve is ready for installation Preparation of the Front GrilleLGE Internal Use Only Sub-Base Connected Unit Installation 208, 230, and 208/230 Volt Units Electrical SafetyElectrical Requirements Electrical Data for 230/208V ModelDescription Field Installed AccessoriesInstallation Control Panel Key LockPart No AYSB2101 Condensate Disposal Pump Kit InstallationHazardous Voltage Place the top cover assembly back into the unit Spraying Architectural Grille Architecture Grille Aluminum Single PackCondensate Drain kit Drain InstallationPart No AYDR101 Outdoor Drain Kit Installation Outdoor Drain Kit InstallationPart No AYLL101 Indoor Drain Kit InstallationChecklist Leveling LegsLeveling Leg Assembly Installation on Wall Sleeve Leveling Leg AssemblyUse Copper Conductors Only Hard Wire KitJunction Box Kit Installation and Wiring Procedure Part No AYAGALA01Volt Units 208/230 Volt UnitsPart No AYRE110 Remote Escutcheon KitPart No AYSB1101 230/208V 20A AYSB2101 230/208V 30A SubbaseSubbase with provided screws. Figure After wiring is complete, mount covers a and F toTo each installation instruction for that accessory Skirting Hole Location Right Cover Assembly066mm 406mm 505mm Troubleshooting GuideOutside Dimensions Piping SystemTroubleshooting Guide Fails to Start Complaint Cause Remedy 208/230V 187V 253V Room AIR Conditioner Voltage LimitsComplaint Cause Remedy Th4 Thermistor for Condenser pipe Air temperature Piping DiagramsTh2 Thermistor for Evaporator pipe temperature Th3 Thermistor for outdoor Air temperatureCN-NN Schematic Diagram435300B Exploded ViewJanuary