LG Electronics LP121HEM-Y8 manual Condensate Disposal Pump Kit Installation, Part No AYSB2101

Page 25

Condensate Disposal Pump Kit Installation

Part No: AYSB2101

Description

The internal condensate pump serves as a means for disposing of condensate generated during heat pump operation by transferring it to the indoor coil. The warm coil surface and the warm room air help in evaporation of the condensate while adding humidity to the room.

As with any equipment of this type, the addition of this kit will decrease the effective heating capacity of the unit. This kit is not intended for use in seacoast or corrosive environments.

NOTE:

Under extreme high humidity conditions, the internal condensate pump may not be able to dispose of all the condensate produced, and condensate would then drip from the outside of the wall sleeve. If this condensation is unacceptable, then a drain system (including factory approved drain kit for the wall sleeve) should be installed.

Receiving

Upon receipt of the product, inspect the shipping carton for signs of visible damage. Report any damage or shortage to the carrier and note it on the delivery receipt. Unit must be stored in its original shipping carton in a dry, secure place prior to its installation and use.

Installation

The installation and servicing of the equipment referred to in this booklet should be performed by qualified, experienced technicians.

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

Important Note:

The unit OFF switch does not disconnect all electrical power to this unit.

1.Remove front plastic cover by rotating bottom outward and then lifting up and out from chassis.

2.Unplug and remove the PTAC chassis from the wallsleeve. Movethe chassis where the front and back of the chassis can be easily accessed.

3.Remove the wire junction box cover by removing four screws and lifting up as shown in figure 31.

Figure 31

4.Remove and set aside the air discharge screen by unscrewing the 5 screws on the top.

5.Remove the one screws holding the control board cover as shown figure 32.

Remove the cover by lifting it up so its free from its hinges, and put aside.

Figure 32

6.Unplug the electric heater connecter located inside the wire junction box.

Copyright ©2008 LG Electronics. Inc. All right reserved.

- 25 -

Only for training and service purposes

LGE Internal Use Only

 

Image 25
Contents SVC Manual LGE Internal Use Only SpecificationSleeve and the Rear Grille Features and BenefitsOutdoor Air Temperature Switchover Door Switch/Occupancy SensorTemperature limits Quick Heater RecoveryOperation Electric Heating Model Control LocationsVentilation Cooling only ModelAdditional Controls Temperature LimitingRemoving the Front Grille Additional ControlsREMOTE/LOCAL Control Molex Housing SpecEnergy Saver Front Desk ControlMechanical Parts Disassembly InstructionsFront Grille Control BOX Electric Heater Electric Heater Model only AIR Handling PartsAxial FAN Cross Flow FANShroud Electrical PartsOutdoor Motor Compressor6 P.C.B Power CordCondenser Refrigeration CycleEvaporator Capillary TubeLGE Internal Use Only Pulling Vacuum HOW to Install the Unit InstallationDimension of air conditioner Dimension of sleeve assembly optionalWall Case Installation Data Wall Sleeve InstallationGeneral As shipped, the LG wall sleeve is ready for installation Installation of Wall Case in Wall OpeningPreparation of the Front Grille Preparation of the Wall Case for All Types of ConstructionLGE Internal Use Only Sub-Base Connected Unit Installation Electrical Requirements Electrical SafetyElectrical Data for 230/208V Model 208, 230, and 208/230 Volt UnitsInstallation Field Installed AccessoriesControl Panel Key Lock DescriptionPart No AYSB2101 Condensate Disposal Pump Kit InstallationHazardous Voltage Place the top cover assembly back into the unit Spraying Architectural Grille Architecture Grille Aluminum Single PackCondensate Drain kit Drain InstallationPart No AYDR101 Outdoor Drain Kit Installation Outdoor Drain Kit InstallationChecklist Indoor Drain Kit InstallationLeveling Legs Part No AYLL101Leveling Leg Assembly Installation on Wall Sleeve Leveling Leg AssemblyJunction Box Kit Installation and Wiring Procedure Hard Wire KitPart No AYAGALA01 Use Copper Conductors OnlyVolt Units 208/230 Volt UnitsPart No AYRE110 Remote Escutcheon KitPart No AYSB1101 230/208V 20A AYSB2101 230/208V 30A SubbaseTo each installation instruction for that accessory After wiring is complete, mount covers a and F toSkirting Hole Location Right Cover Assembly Subbase with provided screws. FigureOutside Dimensions Troubleshooting GuidePiping System 066mm 406mm 505mmTroubleshooting Guide Fails to Start Complaint Cause Remedy 208/230V 187V 253V Room AIR Conditioner Voltage LimitsComplaint Cause Remedy Th2 Thermistor for Evaporator pipe temperature Piping DiagramsTh3 Thermistor for outdoor Air temperature Th4 Thermistor for Condenser pipe Air temperatureCN-NN Schematic Diagram435300B Exploded ViewJanuary