Baxi Potterton 30 HE Appliance Operation, Central Heating Mode Fig, Domestic Hot Water Mode Fig

Page 8

 

 

 

 

 

 

1

 

 

Central Heating Circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

28

 

 

 

 

 

 

2

 

 

 

 

 

 

3

4

7

 

 

26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

6

 

 

25

 

 

 

 

8

 

 

24

 

 

 

 

 

 

 

 

 

 

 

 

 

23

 

 

 

 

9

 

 

 

 

 

 

 

 

 

22

 

 

27

 

 

11

 

21

 

17

 

10

 

 

 

 

 

 

20

18

 

 

 

 

 

 

16

15

14

 

13

12

 

 

19

 

 

 

 

 

 

Fig. 2

 

 

 

 

 

 

Key

 

 

 

 

 

 

1

Primary Heat Exchanger

 

 

15

Domestic Hot Water Outlet

2

Burner

 

 

16

Heating Flow

 

3

Ignition Electrode

 

 

17

Pressure Gauge

 

4

Flame Sensing Electrode

 

 

18

Hydraulic Differential Pressure Sensor Microswitch

5

Gas Valve

 

 

19

Automatic By-Pass

 

6

Pump

 

 

20

Hydraulic Differential Pressure Sensor

7

Automatic Air Vent

 

 

21

Diverter Valve Assembly

 

8

Plate Heat Exchanger

 

 

22

Domestic Hot Water Flow Priority Assembly

9

Flow Sensor with Filter

 

 

23

Domestic Hot Water Flow Priority Microswitch

10

Pressure Relief Valve

 

 

24

Safety Thermostat

 

11

Boiler Drain Point

 

 

25

Central Heating Temperature Sensor

12

Heating Return

 

 

26

Expansion Vessel

 

13 Cold Water Inlet On/Off Valve and Filter

27

Domestic Hot Water Temperature Sensor

14

Gas Inlet

 

 

28

Secondary Heat Exchanger

 

 

 

 

 

 

1

 

 

Domestic Hot Water Circuit

 

 

 

 

 

 

 

 

 

 

 

 

28

 

 

 

 

 

 

2

 

 

 

 

 

 

3

4

7

 

 

26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

6

 

25

 

24

 

 

 

8

 

 

 

 

 

23

 

 

 

9

 

 

 

 

 

 

22

 

 

 

 

11

21

 

17

27

 

 

 

 

10

 

20

 

 

 

 

16

18

15

14

13

12

 

19

 

 

 

 

Fig. 3

3.0 Appliance Operation

NOTE: All delay timers mentioned in 3.1 and 3.2 are

overridden by domestic hot water demand.

3.1Central Heating Mode (Fig. 2)

1.With a demand for heating, the pump circulates water through the primary circuit. At a pre-determined flow rate the central heating flow switch operates, initiating the ignition sequence.

2.The main burner ignites at low rate, then the gas valve controls the gas rate to maintain the heating temperature measured by the temperature sensor.

3.When the flow temperature exceeds the setting temperature, a 3 minute delay occurs before the burner relights automatically (anti-cycling). The pump continues to run during this period.

4.When the demand is satisfied the burner is extinguished and the pump continues to run for a period of 3 minutes (Pump Overrun).

3.2Domestic Hot Water Mode (Fig. 3)

1.Priority is given to the domestic hot water supply. A demand at a tap or shower will override any central heating requirement.

2.The flow of water will operate the DHW flow switch which requests the 3 way valve to change position. This will allow the pump to circulate the primary water through the DHW plate heat exchanger.

3.The burner will light automatically and the temperature of the domestic hot water is controlled by the temperature sensor.

4.When the domestic hot water demand ceases the burner will extinguish and the diverter valve will remain in the domestic hot water mode, unless there is a demand for central heating.

IMPORTANT: When the selector switch is in the ‘0’ (Off) position the electrical supply to the boiler is isolated. The boiler will not operate and the integral timer (if fitted) will require resetting once the selector switch is set to either Position (i) or Position (ii).

3.3Frost Protection Mode

1.The frost protection mode is integral to the appliance and functions only with the selector switch (see Section 2.1) in the domestic hot water and central heating position. If the system temperature falls below 5° C then the boiler will fire on its minimum setting until a flow temperature of 30° C is reached. Further protection can be incorporated by using a system frost thermostat.

3.4Pump Protection

1.With the selector switch (see Section 2.1) in either the central heating or central heating and domestic hot water position the pump will automatically operate for 1 minute in every 24 hours to prevent sticking.

8© Baxi Heating UK Ltd 2007

Image 8
Contents Installation & Service Instructions Contents Installer Notification Guidelines Scheme Members onlyCodes of Practice, most recent version should be used Important Installation, Commissioning, Service & RepairLegislation Safe Manual Handling GeneralPreparation TechniqueIntroduction DescriptionOptional Extras Case Front Panel Control Box Data Badge1211 30 31 32 General LayoutLayout Central Heating Mode Fig Domestic Hot Water Mode FigFrost Protection Mode Appliance OperationTechnical Data Performa 30 HEDimensions and Fixings System Details InformationCentral Heating Circuit BypassSystem Filling and Pressurising Pressure Relief Valve FigHard Water Areas Domestic Hot Water Circuit FigShowers Clearances Figs Site RequirementsLocation Electrical Supply Ventilation of CompartmentsGas Supply External termination via internal Condensate DrainPlume Displacement Kit FlueBuilt-in element such as a window frame. See BS 5440 Pt Or DoorFlue Options Horizontal FluesHorizontal Flue Systems This bend is equivalent to 1 metreVertical Flues Twin Pipe Twin & Vertical Flue SystemsMetre for each 91.5 elbow Metre for each 45 elbow 1m extension 45bend 25m 91.5bend5111079 Flue AccessoriesKey Accessory Size For Twin Flue Systems fit the adaptors as follows Flue Duct AdaptorAir duct adaptor Flue Dimensions For Roof TerminalsFlue Trim Terminal Guard FigPlume Displacement Plume Displacement Kit bElbow/Plume Outlet Assembly Ring Bracket Metres 60Ø Exhaust Flue Pipe 60Ø SupportDetermining Permissible Lengths 30mm General Fitting NotesMin metres Flue Trim Spigot ScrewPlume Outlet Elbow Installation Initial PreparationFlushing Preparing The BoilerFitting The Boiler Condensate Drain see sectionPressure Relief Valve Discharge Pipe Wall Plate Remove the sealing caps from the boiler connectionsFitting The Flue Wall Thickness Flue Elbow AdaptorWasteY Flue Inner Flue Support Bracket Flue Elbow Vertical FlueMaking The Electrical Connections Preliminary Electrical ChecksCommissioning the Boiler Commissioning the BoilerChecking the Burner Pressure Pressure Test Point Sealing ScrewCase Front Panel Facia Panel CompletionCompletion Servicing the Boiler 13 .1 Annual ServicingAnnual Servicing Fan Figs Pressure Switch FigChanging Components Burner Fig 14.0 Changing ComponentsHeat Exchanger Fig Injectors Fig Electrodes FigInsulation Fig Reassemble in reverse orderCentral Heating Temperature Sensor Fig Safety Thermostat FigDHW Temperature Sensor Fig Gas Valve FigAutomatic Air Vent Fig Pump Head Only FigPump Complete Fig Condensate Trap Fig Pressure Gauge FigsExpansion Vessel Fig Selector Switch Fig 14.19 P.C.B. FigPlate Heat Exchanger Fig Diverter Valve Assembly Flow Regulator FigsSecondary Heat Exchanger Fig Flue Overheat Thermostat FigIllustrated Wiring Diagram Control PCBFault Finding Microswitch terminals Diverter valve spindle Assembly faultyDomestic Hot Water Follow operational sequence Turn selector to neon illuminatedCheck wiring PCB A4 connector Replace selector Terminals 4 Replace pump PCB A4 connector terminals 3 Replace PCBPCB A2 connector, is Across terminals 5 Replace microswitchPCB A1 connector has 230V AC Turn selector switchTo ‘Reset’ position Gas at burnerON/OFF/RESET selector when turned to ‘Reset’ position Short Parts List Short Parts List131 154GAS Boiler Commissioning Checklist Service Interval Record Potterton
Related manuals
Manual 12 pages 48.65 Kb

30 HE specifications

The Baxi Potterton 30 HE is a popular choice among homeowners seeking an efficient and reliable boiler solution. Recognized for its compact design and advanced technologies, this boiler is ideal for various residential heating needs.

One of the standout features of the Baxi Potterton 30 HE is its high efficiency rating, which ensures lower energy consumption and reduced utility bills. With an impressive efficiency of up to 90%, this boiler operates at a much higher capacity compared to older models, making it both environmentally friendly and cost-effective. The 30 HE is particularly well-suited for medium to larger homes with a higher demand for hot water.

The Baxi Potterton 30 HE incorporates a range of innovative technologies aimed at enhancing performance and reliability. The automatic modulation function adjusts the boiler's output according to demand, ensuring that it only works as hard as necessary. This not only prolongs the lifespan of the unit but also maximizes comfort levels in the home.

Another feature of the 30 HE is its low noise operation. This boiler has been specifically designed to minimize sound, allowing it to operate quietly in the background without disturbing daily activities. This makes it an ideal choice for homes where noise can be a concern, particularly in open-plan living spaces.

The compact dimensions of the Baxi Potterton 30 HE make it easy to install in various locations, whether it be in a kitchen, utility room, or even a loft space. Its lightweight construction further simplifies the installation process, saving both time and labor costs.

In terms of user-friendliness, the boiler is equipped with an intuitive control panel that allows homeowners to easily adjust settings and monitor performance. This user-centric design ensures that even those who may not be technically inclined can manage their heating requirements with ease.

Safety features are also a priority in the design of the Baxi Potterton 30 HE. It includes built-in safety mechanisms such as frost protection and a burner pressure monitoring system, which work to prevent overheating and ensure optimal operation.

Overall, the Baxi Potterton 30 HE is an efficient, reliable, and user-friendly boiler that meets the heating demands of modern homes. Its blend of advanced technologies, compact size, and focus on safety make it a standout choice for homeowners seeking a high-performance heating solution.