State Industries SBL85 390NE(A) Multiple Heater Manifold Outdoor Air Through One Opening

Page 16

Multiple Heater Manifold

 

Outdoor Air Through One Opening

Figure 13 and tables on pages 18 and 19 should be used for horizontally manifolding two or more heaters.

Figure 13.

Fresh Air Openings for Confined Spaces

The following instructions shall be used to calculate the size, number and placement of openings providing fresh air for combustion, ventilation and dilution in confined spaces. The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confined spaces only. DO NOT refer to these illustrations for the purpose of vent installation. See Venting Installation on page 15 for complete venting installation instructions.

Outdoor Air Through Two Openings

Figure 14.

The confined space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The openings shall communicate directly with the outdoors. See Figure 14.

Each opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr (550 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure. Each opening shall not be less than 100 square inches (645 cm2).

Figure 15.

Alternatively a single permanent opening, commencing within 12 inches (300 mm) of the top of the enclosure, shall be provided. See Figure 14. The water heater shall have clearances of at least 1 inch (25 mm) from the sides and back and 6 inches (l50

mm)from the front of the appliance. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors and shall have a minimum free area of the following:

1.1 square inch per 3000 Btu/hr (733 mm2 per kW) of the total input rating of all appliances located in the enclosure, and

2.Not less than the sum of the areas of all vent connectors in the space.

Outdoor Air Through Two Horizontal Ducts

Figure 16.

The confined space shall be provided with two permanent horizontal ducts, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The horizontal ducts shall communicate directly with the outdoors. See Figure 16.

Each duct opening shall have a minimum free area of 1 square inch per 2,000 Btu/hr (1100 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure.

When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches (7.6 cm).

16

Image 16
Contents Commercial gas water heaters SBL95 199NE SBL85 275NEA SBL85 390NEA Ultra Low NOx SeriesTable Of Contents Safe Installation, Use and Service ApprovalsFire or Explosion Hazard General Safety InformationFire and Explosion Hazard Grounding Instructions PrecautionsHydrogen Gas Flammable Qualified Installer or Service Agency IntroductionAbbreviations Used QualificationsFeatures and Components Hydrocannon self-cleaning systemBlower/Burner Assembly High Limit Switch ControlsInstallation considerations Rough In DimensionsRough-In-Dimensions Recovery Capacities, based on 82% efficiencyLocating the Water Heater ClearancesNSF Leg Kit Insulation BlanketHard Water Circulation PumpsHigh Altitude Installations Breathing Hazard Carbon Monoxide GasInstallation Requirements Temperature-Pressure Relief Valve Dishwashing MachinesClosed Water Systems Thermal ExpansionWater Damage Hazard Combustible Material StorageContaminated Air Valve Discharge Pipe RequirementsAir Requirements Unconfined SpaceConfined Space VentingMultiple Heater Manifold Outdoor Air Through One Opening Fresh Air Openings for Confined SpacesOutdoor Air Through Two Openings Outdoor Air Through Two Horizontal DuctsOutdoor Air Through Two Vertical Ducts Air From Other Indoor SpacesType B GAS Vent Technical Data VentingMultiple Gas Fired Tank-Type Heaters Model SBL85 275NEA Water Line Connections Water heater installationValve Discharge Pipe Installation Diagrams Top Inlet/Outlet Usage Heater Wiring Gas Line Leak Testing Gas PipingPurging Gas Meter Size Natural Gases OnlyPrior to Start Up Start upInitial Start Up Water Temperature Adjustment Multiple Appliance InstallationsChecking Venting Checking the InputSequence of Operation Lighting & Operating LabelSequence of Operation Flow Chart YESMaintenance Temperature-Pressure Relief Valve TestVenting System Intake Air ScreenDraining and Flushing Deliming SolventsTo Drain the Water Heater Storage Tank To Flush the Water Heater Storage TankDeliming Using Flo-Jug Method Tank Cleanout ProcedureChemical Hazard Ignition Control System System DiagnosticsElectrical Servicing High Water Temperature Shut OFF System For Your InformationStart Up Conditions Operational ConditionsQualified Service Agency TroubleshootingComplaint Cause Remedy User Diagrams Water PipingTemperature & Pressure Temperature & Pressure Relief Valve Circulating Pump Multi Flue 2 Units Multi Flue 2 Units with Vertical Storage Tank Multi Flue 2 Units with Vertical Storage Tank Return from Multi Flue 2 Units TWO Temperature Multi Flue 2 Units with Booster TWO Temperature MULTI-FLUE 3 Units MULTI-FLUE 3 Units with Vertical Storage Tank MULTI-FLUE 3 Units with Horizontal Storage Tank Multi Flue Flue 4 Units MULTI-FLUE 4 Units with Vertical Storage Tank MULTI-FLUE 4 Units with Horizontal Storage Tank Model Dimension a Page Limited Warranty ALL Other Parts