State Industries SBL95 199NE Outdoor Air Through Two Vertical Ducts, Air From Other Indoor Spaces

Page 17

Outdoor Air Through Two Vertical Ducts

The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confined spaces only.

Do not refer to these illustrations for the purpose of vent installation. See Venting Installation on page 15 for complete venting installation instructions.

Figure 17.

The confined space shall be provided with two permanent vertical ducts, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The vertical ducts shall communicate directly with the outdoors. See Figure 17.

Each duct opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr (550 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure.

When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches.

Air From Other Indoor Spaces

Figure 18.

The confined space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. See Figure 18.

Each opening shall communicate directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an Unconfined Space.

Each opening shall have a minimum free area of 1 square inch per 1,000 Btu/hr (2200 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure. Each opening shall not be less than 100 square inches (645 cm2).

17

Image 17
Contents SBL95 199NE SBL85 275NEA SBL85 390NEA Ultra Low NOx Series Commercial gas water heatersTable Of Contents Approvals Safe Installation, Use and ServiceFire and Explosion Hazard General Safety InformationFire or Explosion Hazard Hydrogen Gas Flammable PrecautionsGrounding Instructions Introduction Qualified Installer or Service AgencyAbbreviations Used QualificationsHydrocannon self-cleaning system Features and ComponentsBlower/Burner Assembly High Limit Switch ControlsRough In Dimensions Installation considerationsRough-In-Dimensions Recovery Capacities, based on 82% efficiencyClearances Locating the Water HeaterInsulation Blanket NSF Leg KitHard Water Circulation PumpsBreathing Hazard Carbon Monoxide Gas High Altitude InstallationsInstallation Requirements Dishwashing Machines Temperature-Pressure Relief ValveClosed Water Systems Thermal ExpansionCombustible Material Storage Water Damage HazardContaminated Air Valve Discharge Pipe RequirementsUnconfined Space Air RequirementsConfined Space VentingFresh Air Openings for Confined Spaces Multiple Heater Manifold Outdoor Air Through One OpeningOutdoor Air Through Two Openings Outdoor Air Through Two Horizontal DuctsAir From Other Indoor Spaces Outdoor Air Through Two Vertical DuctsMultiple Gas Fired Tank-Type Heaters Technical Data VentingType B GAS Vent Model SBL85 275NEA Valve Discharge Pipe Water heater installationWater Line Connections Installation Diagrams Top Inlet/Outlet Usage Heater Wiring Gas Piping Gas Line Leak TestingPurging Gas Meter Size Natural Gases OnlyInitial Start Up Start upPrior to Start Up Multiple Appliance Installations Water Temperature AdjustmentChecking Venting Checking the InputLighting & Operating Label Sequence of OperationYES Sequence of Operation Flow ChartTemperature-Pressure Relief Valve Test MaintenanceVenting System Intake Air ScreenDeliming Solvents Draining and FlushingTo Drain the Water Heater Storage Tank To Flush the Water Heater Storage TankChemical Hazard Tank Cleanout ProcedureDeliming Using Flo-Jug Method Electrical Servicing System DiagnosticsIgnition Control System For Your Information High Water Temperature Shut OFF SystemStart Up Conditions Operational ConditionsComplaint Cause Remedy User TroubleshootingQualified Service Agency Water Piping DiagramsTemperature & Pressure Temperature & Pressure Relief Valve Circulating Pump Multi Flue 2 Units Multi Flue 2 Units with Vertical Storage Tank Multi Flue 2 Units with Vertical Storage Tank Return from Multi Flue 2 Units TWO Temperature Multi Flue 2 Units with Booster TWO Temperature MULTI-FLUE 3 Units MULTI-FLUE 3 Units with Vertical Storage Tank MULTI-FLUE 3 Units with Horizontal Storage Tank Multi Flue Flue 4 Units MULTI-FLUE 4 Units with Vertical Storage Tank MULTI-FLUE 4 Units with Horizontal Storage Tank Model Dimension a Page ALL Other Parts Limited Warranty