State Industries SBL85 275NE(A), SBL85 390NE(A), SBL95 199NE Installation Requirements

Page 12

Installation Requirements

Gas Supply Systems

Low pressure building gas supply systems are defined as those systems that cannot under any circumstances exceed 14” W.C. (3.49 kPa) (1/2 PSI Gauge). These systems do not require pressure regulation. Measurements should be taken to insure that gas pressures are stable and fall within the requirements stated on the water heater rating plate. Readings should be taken with all gas burning equipment off (static pressure) and with all gas burning equipment running at maximum rate (dynamic pressure). The gas supply pressure must be stable within 1.5” W.C. (0.37 kPa) from static to dynamic pressure to provide good performance. Pressure drops that exceed 1.5” W.C. (0.37 kPa) may cause rough starting, noisy combustion or nuisance outages. Increases or spikes in static pressure during off cycles may cause failure to ignite or in severe cases damage to appliance gas valves. If your low pressure system does NOT meet these requirements, the installer is responsible for the corrections.

High Pressure building supply systems use pressures that exceed 14” W.C. (3.49 kPa) (1/2 PSI Gauge). These systems must use field supplied regulators to lower the gas pressure to less than 14” W.C. (3.49 kPa) (1/2 PSI Gauge). Appliances require gas regulators that are properly sized for the water heater input and deliver the rating plate specified pressures. Gas supply systems where pressure exceeds 5 PSI (34.5 kPa) often require multiple regulators to achieve desired pressures. Systems in excess of 5 PSI building pressure should be designed by gas delivery professionals for best performance. Water heaters connected to gas supply systems that exceed 14” W.C. (3.49 kPa) (1/2 PSI Gauge) at any time must be equipped with a gas supply regulator.

Gas Pressure Requirements

All models require a minimum gas supply pressure of 3.5” W.C. (0.87 kPa) The minimum supply pressure is measured while gas is flowing (dynamic pressure). The supply pressure (dynamic) should never fall below 3.5” W.C. (0.87 kPa) The supply pressure should be measured with all gas fired appliances connected to the common main firing at full capacity. If the supply pressure drops more than 1.5” W.C. (0.37 kPa) as gas begins to flow to the water heater then the supply gas system including the gas line and/or the gas regulator may be restricted or undersized. See Supply Gas Regulator section and Gas Piping section of this manual.

The gas valve on all models has a maximum gas supply pressure limit of 14" W.C. (3.48 kPa). The maximum supply pressure is measured while gas is not flowing (static pressure).

Supply Gas Regulator

The maximum allowable gas supply pressure for this water heater is 14 inches W.C. (3.48 kPa). Install a positive lock-up gas pressure regulator in the gas supply line if inlet gas pressure can exceed 14 inches W.C. (3.48 kPa) at any time. Regulators must be sized/used according to manufacturer's specifications.

If a positive lock-up regulator is required follow these instructions:

1.Positive lock-up gas pressure regulators must be rated at or above the input Btu/hr rating of the water heater they supply.

2.Positive lock-up gas pressure regulator(s) should be installed no closer than 3 feet (1 meter) and no farther than 8 feet (2.4 meters) of equivalent length from the water heater’s inlet gas connection.

3.After installing the positive lock-up gas pressure regulator(s) an initial nominal supply pressure setting of 7.0” W.C. (1.74 kPa) while the water heater is operating is recommended and will generally provide good water heater operation. Some addition adjustment maybe required later to maintain a steady gas supply pressure.

4.When installing multiple water heaters in the same gas supply system it is recommended that individual positive lock-up gas pressure regulators be installed at each unit.

Power Supply

The water heaters covered in this manual require a 120 VAC, 1Ø (single phase), 60Hz, 15 amp power supply and must also be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/ NFPA 70 or the Canadian Electrical Code, CSA C22.1.

Water Temperature Control and Mixing Valves

Water temperature over 125°F (52°C) can cause severe burns instantly resulting in severe injury or death.

Children, the elderly and the physically or mentally disabled are at highest risk for scald injury.

Feel water before bathing or showering.

Temperature limiting devices such as mixing valves must be installed when required by codes and to ensure safe temperatures at fixtures.

Water heated to a temperature which will satisfy clothes washing, dish washing, and other sanitizing needs can scald and cause permanent injury upon contact. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the water heater’s temperature setting by up to 20°F (11°C).

Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infirm and the physically/mentally disabled. Table 5 shows the approximate time-to-burn relationship for normal adult skin. If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water temperature at the point of use, then special precautions must be taken.

In addition to using the lowest possible temperature setting that satisfies the demand of the application a Mixing Valve should be installed at the water heater (see Figure 10) or at the hot water taps to further reduce system water temperature.

Mixing valves are available at plumbing supply stores. Consult a Qualified Installer or Service Agency. Follow mixing valve manufacturer’s instructions for installation of the valves.

Table 5.

Water Temperature

Time for 1st Degree Burn

Time for Permanent Burns

°F (°C)

(Less Severe Burns)

2nd & 3rd Degree

(Most Severe Burns)

 

 

110 (43)

(normal shower temp.)

 

 

 

 

116 (47)

(pain threshold)

 

 

 

 

116 (47)

35 minutes

45 minutes

 

 

 

122 (50)

1 minute

5 minutes

 

 

 

131 (55)

5 seconds

25 seconds

 

 

 

140 (60)

2 seconds

5 seconds

 

 

 

149 (65)

1 second

2 seconds

 

 

 

154 (68)

instantaneous

1 second

 

 

 

(U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15, 1978)

12

Image 12
Contents Commercial gas water heaters SBL95 199NE SBL85 275NEA SBL85 390NEA Ultra Low NOx SeriesTable Of Contents Safe Installation, Use and Service ApprovalsGeneral Safety Information Fire or Explosion HazardFire and Explosion Hazard Precautions Grounding InstructionsHydrogen Gas Flammable Qualified Installer or Service Agency IntroductionAbbreviations Used QualificationsFeatures and Components Hydrocannon self-cleaning systemBlower/Burner Assembly High Limit Switch ControlsInstallation considerations Rough In DimensionsRough-In-Dimensions Recovery Capacities, based on 82% efficiencyLocating the Water Heater ClearancesNSF Leg Kit Insulation BlanketHard Water Circulation PumpsHigh Altitude Installations Breathing Hazard Carbon Monoxide GasInstallation Requirements Temperature-Pressure Relief Valve Dishwashing MachinesClosed Water Systems Thermal ExpansionWater Damage Hazard Combustible Material StorageContaminated Air Valve Discharge Pipe RequirementsAir Requirements Unconfined SpaceConfined Space VentingMultiple Heater Manifold Outdoor Air Through One Opening Fresh Air Openings for Confined SpacesOutdoor Air Through Two Openings Outdoor Air Through Two Horizontal DuctsOutdoor Air Through Two Vertical Ducts Air From Other Indoor SpacesTechnical Data Venting Type B GAS VentMultiple Gas Fired Tank-Type Heaters Model SBL85 275NEA Water heater installation Water Line ConnectionsValve Discharge Pipe Installation Diagrams Top Inlet/Outlet Usage Heater Wiring Gas Line Leak Testing Gas PipingPurging Gas Meter Size Natural Gases OnlyStart up Prior to Start UpInitial Start Up Water Temperature Adjustment Multiple Appliance InstallationsChecking Venting Checking the InputSequence of Operation Lighting & Operating LabelSequence of Operation Flow Chart YESMaintenance Temperature-Pressure Relief Valve TestVenting System Intake Air ScreenDraining and Flushing Deliming SolventsTo Drain the Water Heater Storage Tank To Flush the Water Heater Storage TankTank Cleanout Procedure Deliming Using Flo-Jug MethodChemical Hazard System Diagnostics Ignition Control SystemElectrical Servicing High Water Temperature Shut OFF System For Your InformationStart Up Conditions Operational ConditionsTroubleshooting Qualified Service AgencyComplaint Cause Remedy User Diagrams Water PipingTemperature & Pressure Temperature & Pressure Relief Valve Circulating Pump Multi Flue 2 Units Multi Flue 2 Units with Vertical Storage Tank Multi Flue 2 Units with Vertical Storage Tank Return from Multi Flue 2 Units TWO Temperature Multi Flue 2 Units with Booster TWO Temperature MULTI-FLUE 3 Units MULTI-FLUE 3 Units with Vertical Storage Tank MULTI-FLUE 3 Units with Horizontal Storage Tank Multi Flue Flue 4 Units MULTI-FLUE 4 Units with Vertical Storage Tank MULTI-FLUE 4 Units with Horizontal Storage Tank Model Dimension a Page Limited Warranty ALL Other Parts