INSTALLATION DIAGRAMS-TOP INLET/OUTLET USAGE

GENERAL

The type, size and location of the relief valves must be in

accordance with local codes. The locations of the relief valves shown in the installation diagrams are typical. The heater has a factory installed high temperature limit switch and temperature and pressure relief valve.

Cold water lines to heater should be installed as shown in order to minimize gravity circulation of hot water to building cold water lines.

A listed temperature and pressure relief valve of adequate capacity is installed on the heater. The locations shown in the installation diagrams on the following pages are typical.

The discharge opening of the temperature and pressure relief valve, located in front of the heater must be piped to an open drain and should not be subject to freezing temperatures.

Install in accordance with all local codes.

Use of the top inlet water connection requires installation of an inlet dip tube (refer to figure 9). The tube is supplied in the heater. Follow caution labels if applying heat to this fitting. Do not allow pipe dope to contact the plastic tube during installation.

CODE RESTRICTIONS

Use of the top inlet water connection is not permitted on installations in the state of North Carolina, due to the material of the tube (Polypropylene). Where such code restrictions exist, use only lower inlet tank connection. This may also require a heat trap - check local codes. The “Top Outlet” connection may still be used on these applications. Plug or cap all unused openings in the tank before filling with water.

DANGER

TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 25. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT

WATER SUPPLIED TO FIXTURES.

TUBE INLET INSTALLATION

FIGURE 9

12

Image 12
Contents Models SBN71120NE Thru SBN85390NE/A Series ROUGH-IN-DIMENSIONS Front View TOP View Back View ROUGH-IN-DIMENSIONSGasand Electrical Characteristics Table of Contents ForewordGeneral Safety Information Features High Altitude InstallationsSELF-CLEANING Hydro Cannon High Limit SwitchExhaust Inducer Blower Assy Circulating PumpDishwashing Machine Requirement UncratingLeveling ClearancesModel Right Back Ceiling SideHard Water AIR RequirementsVenting UnconfinedspaceTechnical Data Venting Type B GAS VentTechnical Data Venting Multiple Heater Manifold Water Line ConnectionsWater Potable Heating and Space Relief ValveInstallation DIAGRAMS-TOP INLET/OUTLET Usage Tube Inlet InstallationGeneral Code RestrictionsVertical Storage Tank and Forced Circulation Horizontal Storage Tank and Forced CirculationPage Installation DIAGRAMS-SIDE INLET/OUTLET Usage Circulating Return Line ConnectionHeater with Mixing Valve and Recirculated Sanitizing Loop TWO PRE-HEATERS with Booster Heater Horizontal Storage Tank Model Dimension a Manifold KitsTWO Unit Manifold KIT Three Unit Manifold KIT Four Unit Manifold KITHeater Wiring Single Unit Wiring Diagram SBN-120 Through 400AGAS Pipingand Dirt LEG Installation GAS PipingGAS Pressure Regulator PurgingOperation Manifold GAS Pressure in Inches Water Column ALL ModelsFilling Sequence of Operation For Your Safety Read Before Operating Lighting and Operation InstructionsOperating Instructions Preventive Maintenance Water Temperature ControlCheck the Ignitor Assembly Ignitor AssemblyMain Burner GAS ValvesChecking the Input Remote Storage Tank Temperature Control Venting SystemHOT Water Odor Anode ROD InspectionTank Cleanout Procedure Deliming Using FLO-JUG MethodDeliming Solvents Service System DiagnosticsIgnition Module System Electrical ServicingReplacement PARTS, Service Handbooks and Training Aids Sequence of Operation Flow ChartYES Operational Checklist Complaint Cause User ServicemanLindahl Parkway Ashland City, TN Phone 800-821-2017 Fax