State Industries SBN85390NE/A warranty Exhaust Inducer Blower Assy, Circulating Pump, Uncrating

Page 6

IGNITION CONTROL BOARD

FIGURE4

EXHAUST INDUCER (BLOWER ASSY.)

All SBN 120-400 models are equipped with an exhaust inducer. The inducer assists in drawing in fresh air to the unit for combustion and then assists in dispensing the combustion by- products into the venting leading outside.

The exhaust inducer is equipped with a gravity controlled damper to reduce the amount of heat loss through the flue, improving efficiency.

EXHAUST INDUCER

FIGURE5

CIRCULATING PUMP

A circulating pump is used when a system requires a circulating loop or there is a storage tank used in conjunction with the heater. Refer to the piping diagrams in this manual for electrical hookup information and install in accordance with the latest version of the National Electric Code ANSI/NFPA No. 70.

Only all bronze circulators are used with commercial water heaters.

Although circulators are oiled and operated by the manufacturer some circulators must be oiled again before operating. Please refer to manufacturer’s instructions.

DISHWASHING MACHINE REQUIREMENT

These appliances meet the National Sanitation Foundation Standard for sanitary installations when used with the following leg kit, Part No. 6570-7.

All dishwashing machines meeting the National Sanitation Foundation requirements are designed to operate with water flow pressures between 15 and 25 psi. Flow pressures above 25 psi, or below 15 psi, will result in improperly sanitized dishes. Where pressures are high, a water pressure reducing or flow regulating control valve should be used in 1800F line to the dishwashing machine, and should be adjusted to deliver water between these limits.

The National Sanitation Foundation also recommends circulation of 1800F (82.2°C) water. Where this is done, the circulation should be very gentle so that it does not cause any unnecessary turbulence inside the water heater. The circulation should be just enough to provide 1800F(82.2°C) water at the point of take-off to the dishwashing machine. Adjust flow by means of the plug cock in the circulating line.

INSTALLATION INSTRUCTIONS

REQUIRED ABILITY

INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING, GAS SUPPLYAND ELECTRICAL WORKARE REQUIRED.

WARNING

FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN SERIOUS PERSONAL INJURY OR DEATH.

UNCRATING

The heater is shipped with the inducer already installed. The wiring conduit runs from the thermostat to the inducer. Before turning unit on, check to make sure the wiring conduit is securely plugged into the inducer.

LOCATING THE HEATER

When installing the heater, consideration must be given to proper location. Location selected should be as close to the stack or chimney as practicable, with adequate air supply and as centralized with the piping system as possible.

WARNING

THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH AS GAS WATER HEATERS IN ROOMS, GARAGES OR OTHER AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED, OPERATED OR REPAIRED. FLAMMABLE VAPORS ARE HEAVY AND TRAVEL ALONG THE FLOOR AND MAY BE IGNITED BY THE HEATER’S PILOT OR MAIN BURNER FLAMES CAUSING FIRE OR EXPLOSION. SOME LOCAL CODES PERMIT OPERATION OF GAS APPLIANCES IN SUCH AREAS IF THEY ARE INSTALLED 18” OR MORE ABOVE THE FLOOR. THIS MAY REDUCE THE RISK IF LOCATION IN SUCH AN AREA CANNOT BE AVOIDED.

DO NOT INSTALL THIS WATER HEATER DIRECTLY ON A CARPETED FLOOR. A FIRE HAZARD MAY RESULT. Instead the water heater must be placed on a metal or wood panel extending beyond the full width and depth by at least 3 inches (76.2 mm) in

6

Image 6
Contents Models SBN71120NE Thru SBN85390NE/A Series ROUGH-IN-DIMENSIONS Front View TOP View Back View ROUGH-IN-DIMENSIONSGasand Electrical Characteristics Table of Contents ForewordGeneral Safety Information SELF-CLEANING Hydro Cannon FeaturesHigh Altitude Installations High Limit SwitchDishwashing Machine Requirement Exhaust Inducer Blower AssyCirculating Pump UncratingModel Right LevelingClearances Back Ceiling SideVenting Hard WaterAIR Requirements UnconfinedspaceTechnical Data Venting Type B GAS VentTechnical Data Venting Water Potable Heating and Space Multiple Heater ManifoldWater Line Connections Relief ValveGeneral Installation DIAGRAMS-TOP INLET/OUTLET UsageTube Inlet Installation Code RestrictionsVertical Storage Tank and Forced Circulation Horizontal Storage Tank and Forced CirculationPage Installation DIAGRAMS-SIDE INLET/OUTLET Usage Circulating Return Line ConnectionHeater with Mixing Valve and Recirculated Sanitizing Loop TWO PRE-HEATERS with Booster Heater Horizontal Storage Tank TWO Unit Manifold KIT Model Dimension aManifold Kits Three Unit Manifold KIT Four Unit Manifold KITHeater Wiring Single Unit Wiring Diagram SBN-120 Through 400AGAS Pressure Regulator GAS Pipingand Dirt LEG InstallationGAS Piping PurgingOperation Manifold GAS Pressure in Inches Water Column ALL ModelsFilling Sequence of Operation For Your Safety Read Before Operating Lighting and Operation InstructionsOperating Instructions Check the Ignitor Assembly Preventive MaintenanceWater Temperature Control Ignitor AssemblyMain Burner GAS ValvesChecking the Input HOT Water Odor Remote Storage Tank Temperature ControlVenting System Anode ROD InspectionTank Cleanout Procedure Deliming Using FLO-JUG MethodDeliming Solvents Ignition Module System ServiceSystem Diagnostics Electrical ServicingReplacement PARTS, Service Handbooks and Training Aids Sequence of Operation Flow ChartYES Operational Checklist Complaint Cause User ServicemanLindahl Parkway Ashland City, TN Phone 800-821-2017 Fax