Freestanding Corn/Pellet Installation
Caution: Follow the pipe manufacturer’s installation instructions and directions for passing through combustible walls and ceilings. Check local codes in your area.
Must have
minimum 3”
adapter before tee
for longer run. For shorter run (such as Masonry Connection below), tee alone is acceptable.
Illustration 1
Our Part
is acceptable for
(We recommend 4”
for 2500+ ft. installations.)
Basement Installation should be performed by
professional installer. Use 3” metal pipe and coupler for Outside Combustion Air. Minimum 3’ clearance from ground to the Pellet Vent Exhaust Pipe.
1.If 3” flue pipe exceeds 15’ in length, increase to 4” flue pipe for remaining flue connections.
2.Total flue length should not exceed 35’.
3.Horizontal run not to exceed 4’.
4.Floor protector required: Min. size 36” x 36”.
5.If the total run of outside air connection exceeds 6’, if more than 2 elbows are used, or if a basement install, use 3” metal pipe (and coupler) instead.
6.Outside Air is mandatory for proper safe operation.
FLOOR AND WALL PROTECTION
Floor Protection
If your floor is constructed of a
Wall Protection
From the rear of this stove only three inches (3”) of clearance is required to paneling, wallpaper or drywall. The same clearance (3”) is required to a corner wall. Six inches (6”) would be required to a sidewall. Alcove clearances: Six inches (6”) is required to an alcove sidewall; three inches (3”) is required to an alcove backwall, and seventeen inches (17”) is required to an alcove ceiling. The corn vent pipe would require the standard three inches (3”) clearance, or as recommended by the manufacturer. Normally additional wall protection is not required with this type unit.
12