Bradford-White Corp C(S, D)W275T*(BN, CX service manual Honeywell Thermowell Testing

Page 16

SERVICE PROCEDURE AG-III

Honeywell Thermowell Testing and

Replacemet

HONEYWELL THERMOWELL TESTING

Step 1. If gas control has gone into lockout due to excessive tank temperature (four flashes and a three second pause) reset the gas control to the “OFF” position. Then follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.

Step 2. Observe the water heater operation. If the gas control continues to lockout due to excessive tank temperature proceed to Step 3, thermowell testing, to determine the cause.

Step 3. To perform thermowell testing turn the gas control to the “OFF” position and disconnect the thermowell harness from the gas control.

Disconnect

thermowell wire

harness

Figure 28

 

Figure 29

CAUTION

DO NOT Use standard multimeter probes to test. Doing so will damage connector. Use special pin type electronic probes or small diameter wire pins inserted into connector

Figure 30

Step 4. Using a multimeter set to measure Ohms determine the resistance of the thermowell sensor (See caution on this page).

Step 5. Hold one probe in the center pin and measure the outside positions pins (see figure 29 & 30).

Step 6. Refer to Table 1 on page 17 to determine the correct resistance value for the water heater tank temperature.

Step 7. If the resistance values are correct the gas control needs to be replaced. If they are incorrect the thermowell needs to be replaced.

Page 16

16

Image 16
Contents Service Manual Table of Contents Troubleshooting Chart LED Status Control Status Probable Cause LED Status Control Status Probable Cause Service Procedure Open Circuit Thermocouple Testing Service Procedure AG-IThermocouple Replacement Open Circuit Thermopile Testing Closed Circuit Thermopile TestingAn Open Circuit test A Closed Circuit testThermopile Replacement Step Turn off gas supply to water heater. Rotate knob Pilot Assembly Inspection Cleaning and Replacement IGNITER/ELECTRODE Testing Replacement Gas Control Testing and Replacement Service Procedure AG-IIILine Pressure Magnet Assembly Testing White Rodgers Control Thermocouple TestingMagnet Assembly Testing Robertshaw Control ECO Energy Cut Off Testing GAS Control ReplacementInstallation of gas control Honeywell Thermowell Testing Determine Water Heater Tank Temperature Honeywell GAS Control & Thermowell Removal Honeywell GAS Control Removal from ThermowellHoneywell GAS Control Assembly to Thermalwell Service Procedure AG-IV Cast Iron Burner AdjustmentBurner Cleaning Steel & Cast Iron Burner Cleaning Service Procedure AG-V Diptube Inspection and ReplacementAnode Inspection and Replacement Turn gas control knob to OFF positionPage Page