Troubleshooting Chart (cont.)
For Models Using Honeywell Gas Control
LED Status | Control Status | Probable Cause | ||
|
|
|
|
|
Service
Procedure
Five flashes and a three second pause.
Seven flashes and a three second pause.
Eight flashes and a three second pause.
Thermowell fault
Gas control fault detected.
Pilot flame remains on while gas control is in the “OFF” position.
1.Damage to thermowell
wires.
2. Thermowell sensor resistance out of range.
1.Gas control needs to be reset.
2.Gas control is wet or physically damaged.
Pilot valve stuck in the open position.
See Service Procedure
Lite pilot per the instructions located on the lighting instructions label or the lighting instructions located in the installation and operation manual.
Replace gas control. See Service Procedure
Page 5