Brute Elite | Page 11 |
|
|
SECTION 2.
Locating the Appliance
2.1Locating the Appliance
Brute Elite is for indoor installations only.
The appliance should be located to provide clearances on all sides for maintenance and inspection. It should not be located in an area where leakage of any connections will result in damage to the area adjacent to the appliance or to lower floors of the structure.
When such a location is not available, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance.
The appliance is design certified by CSA- International for installation on combustible flooring; in basements; in closets, utility rooms or alcoves. Brute
Elite Boilers must never be installed on carpeting. The location for the appliance should be chosen with regard to the vent pipe lengths and external plumbing and on a level surface. The unit shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during operation and service (circulator replacement, control replacement, etc.). When vented vertically, the Brute Elite must be located as close as practical to the vertical section of the vent. If the vent terminal and/or combustion air terminal terminate through a wall, and there is potential for snow accumulation in the local area, both terminals should be installed at an appropriate level above grade or the maximum expected snow line.
The dimensions and requirements that are shown in Table 1 should be met when choosing the locations for the appliance.
2.2Locating Appliance for Correct Vent Distance from Outside Wall or Roof Termination
The forced draft combustion air blower in the appliance has sufficient power to vent properly when the guidelines in Table 2 are followed.
NOTE: When located on the same wall, the Brute Elite combustion air intake terminal must be installed a minimum of 12" below the exhaust terminal.Models 399- 850 also require a minimum horizontal distance from intake to exhaust terminal of 36".
For concentric vent terminal kit (optional), follow installation instructions included with the kit.
APPLIANCE |
| SUGGESTED SERVICE ACCESS CLEARANCE | ||||
SURFACE |
|
|
| INCHES | CM |
|
Left Side |
|
|
| 1 | 2.5 |
|
Right Side |
|
| 12 | 31 |
| |
Top |
|
|
| 24 | 61 |
|
Back |
|
|
| 6 | 15 |
|
Closet, Front |
| 6 | 15 |
| ||
Alcove, Front |
| 24 | 61 |
| ||
Front |
|
| 24 | 61 |
| |
Vent |
|
|
| – | – |
|
| Certified by CSA for zero clearance to |
| ||||
| combustible materials on all sides. |
| ||||
|
|
|
|
| ||
|
| Table 1. Clearances. |
|
| ||
|
|
|
|
| ||
|
| INTAKE / EXHAUST |
|
| ||
STANDARD | MAX EQUIV. | OPTIONAL MAX EQUIV. | ||||
SIZE | VENT | FT. | M | VENT | FT. | M |
80 | 2" | 40 | 6.1 | 3" | 100 | 30.5 |
105 | 2" | 40 | 6.1 | 3" | 100 | 30.5 |
|
|
|
|
|
|
|
150 | 3" | 100 | 30.5 | n/a | — | — |
199/210 | 3" | 100 | 30.5 | n/a | — | — |
285 | 4" | 100 | 30 | n/a | — | — |
|
|
|
|
|
|
|
399 | 4" | 100 | 30 | n/a | — | — |
500 | 4" | 100 | 30 | n/a | — | — |
600 | 4" | 100 | 30 | n/a | — | — |
|
|
|
|
|
|
|
750 | 4" | 40 | 6.1 | 6" | 100 | 30 |
850 | 4" | 40 | 6.1 | 6" | 100 | 30 |
Installations in the U.S. require exhaust vent pipe that is a combination of PVC & CPVC complying with ANSI/ASTM D1785 F441 or stainless steel complying with UL1738. Installations in Canada require exhaust vent pipe that is certified to ULC S636.
Intake (air) pipe must be PVC or CPVC that complies with ANSI/ASTM D1785 F441, ABS that complies with ANSI/ASTM D1527 or galvanized material.
Installer must comply fully with manufacturer's installation instructions, including use of minimum exhaust length CPVC, to maintain ANSI Z21.13 safety certification.
Closet and alcove installations do not allow the use of PVC under any circumstances
To calculate max equivalent length, measure the linear feet of the pipe, and add 5 feet (1.5m) for each elbow used.
Table 2. Vent / Air Pipe Sizes.