Bradford-White Corp BNTV, BNTH, Modulating Boiler warranty Combustion Air and Vent Through Side Wall

Page 16
Figure 12. Combustion Air and Vent Through Side Wall.

Page 16

 

BRADFORD WHITE CORP.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U.S. Installations (see note 1)

Canadian Installations (see note 2)

A=

Clearance above grade, veranda, porch,

12 inches (30 cm)

12 inches (30 cm)

 

deck, or balcony

See note 6

See note 6

B=

Clearance to window or door that may be

Direct vent only: 12 inches (30cm);

36 inches (91 cm)

 

opened

Other than Direct vent: 4 ft (1.2m) below or to

 

 

 

side of opening; 1 ft (30cm) above opening

 

C=

Clearance to permanently closed window

See note 4

See note 5

D=

Vertical clearance to ventilated soffit located

 

 

 

above the terminal within a horizontal

See note 4

See note 5

 

distance of 2 feet (61cm) from the center

 

 

 

line of the terminal

 

 

E=

Clearance to unventilated soffit

See note 4

See note 5

F=

Clearance to outside corner

See note 4

See note 5

G=

Clearance to inside corner

3 feet minimum

3 feet (91cm) minimum

H=

Clearance to each side of center line

 

3 feet (91 cm) within a height 15 feet

 

extended above meter/regulator assembly

See note 4

above the meter/regulator assembly

I=

Clearance to service regulator vent outlet

See note 4

3 feet (91 cm)

J=

Clearance to nonmechanical air supply

Direct vent only: 12" (30cm) 80-285; 36" (91cm)

 

 

inlet to building or the combustion air inlet

399-850. Other than Direct vent: 4 ft (1.2m) below

36 inches (91 cm)

 

to any other appliance

or to side of opening; 1 ft (30cm) above opening

 

K=

Clearance to a mechanical air supply inlet

3 feet (91 cm) above if within 10 feet (3 m)

6 feet (1.83 m)

 

 

horizontally

 

L=

Clearance above paved sidewalk or paved

Vent termination not allowed in this location

Vent termination not allowed in this

 

driveway located on public property

for category IV appliances.

location for category IV appliances.

M=

Clearance under veranda, porch, deck,

See note 4

12 inches (30 cm) (see note 3)

 

or balcony

 

 

Notes:

1.In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.

2.In accordance with the current CAN/CGA-B149 Installation Codes.

3.Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

4.For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of the gas supplier.

5.For clearances not specified in CAN/CGA-B149, clearance is in accordance with local installation codes and the requirements of the gas supplier.

6.IMPORTANT: terminal must be placed such that it remains a minimum 12" above expected snow line. Local codes may have more specific requirements, and must be consulted.

*When vent terminal is less than 10 feet (3m) horizontally from a forced air inlet, the terminal must be at least 3 feet (0.9m) above the air inlet.

Figure 12. Combustion Air and Vent Through Side Wall.

Image 16
Contents Installation and Operation Instructions DocumentInstallation and Operation Instructions for BRUTE ELITETABLE OF CONTENTS Brute Elite Control Setup and OperationSECTION General InformationSECTION Maintenance Trouble ShootingReplacement Parts SECTION Modes of OperationSECTION General Information 1.1 Introduction1.2 Model Identification Model NomenclatureFigure 1. Location of Components, Sizes Figure 2. Location of Components, SizesFigure 3. Location of Components, Size Figure 4. Location of Components, SizeFigure 5. Location of Components, Size Figure 6. Location of Components, SizeFigure 7. Location of Components, Sizes 750 and 1.4 Warranty 1.6 Dimensions1.3 Appliance Overview 1.5 UnpackingFigure 9. Dimensional Drawing, Sizes Dimensions are nominal and are shown in inches, cmSECTION Locating the Appliance Brute Elite is for indoor installations only2.1 Locating the Appliance SECTION Venting and Combustion Air 3.1 Combustion Air3.1.1 Combustion Air From Room 3.1.2 Ducted Combustion AirFigure 10. Combustion Air and Vent Through Roof 3.2 VentingTable 5. Required Exhaust Vent Material 3.3 Locating Vent & Combustion Air Terminals 3.2.1 Venting Requirements Unique to CanadaA. exhaust vent terminal not included E. CPVC exhaust pipe section 80-500 not incl3.3.5 Installations in the Commonwealth of Massachusetts 3.3.2 Side Wall Combustion Air Terminal5. For concentric vent, follow instructions included with vent kit 3.3.3 Vertical Vent TerminalFigure 12. Combustion Air and Vent Through Side Wall 3.4 Common Vent Test 2. Approved Carbon Monoxide Detectors3. Signage 4. Inspection4.1 Gas Supply and Piping SECTION Gas Supply and Piping3. Refer to Tables 6A, 6B, 6C and 6D to size piping SECTION Pump Requirements 5.1 Brute Elite Boiler Flow and Head Requirements see Table5.2 Brute Elite Water Heater Flow and Head Requirements see Table Table 6A6A.1 BNTH System Piping Hot Supply Connections SECTION 6A Water Connections - BNTH Boiler6A.2 BNTH Cold Water Make-Up 6A.4 BNTH Suggested Piping Schematics 6A.3 Freeze Protection6A.5 Recognized Chemicals 1. Sentinel Performance Solutions Group 2. Hercules Chemical CompanyFigure 15. Hydronic Piping - Single Boiler zoning with circulators Brute Elite Figure 17. Hydronic Piping - Multiple Boilers zoning with circulators Brute Elite PagePage Brute Elite PagePage SECTION 6B 6B.1 BNTV Water Quality6B.2 Piping Requirements Water Connections - BNTV Water Heater6B.5 BNTV Suggested Piping Schematics 6B.3 Cold Water Make-Up6B.4 Freeze Protection 6B.6 BNTV Suggested PumpsFigure 25. DHW Piping, Two Heaters, One Vertical Tank Figure 26. DHW Piping, Two Heaters, Two Vertical TanksCaution Pump sizing must be based opon water hardness at job site7.1 Main Power SECTION Electrical Connections7.10 Lead Lag/ Cascading Wiring Connections 7.2 Pump Connections7.3 24Vac Transformer with Integral Circuit Breaker 7.4 Hydronic Call for HeatFigure 28. Lead-Lag / Cascading Wiring Connections 7.11 Wiring Diagrams see Figures 29 and Figure 29. Ladder DiagramFigure 30. Wiring Diagram all sizes 8.1 Display Navigation SECTION Brute Elite Control Setup and Operation8.2 Ignition Control- Sequence of Events 8.3 Modulation Control 8.5 Anti-Short Cycle ASC8.5 High Limit 8.7 Outlet Water Temperature8.12.5 Lead Lag Base Load Setting 8.13 Boiler Pump Interrupt8.12.1 Lead Lag Setpoint 8.12.2 Lead Lag Master/Slave Selection9.2 Hydronic Heating with Outdoor Reset 9.4 Hydronic Heating Using External Modulation ControlSECTION Modes of Operation 9.1 Hydronic Heating Demand9.5 Hydronic Heating Using Local Lead- Lag/Cascading Feature 9.7 Warm Weather Shutdown9.8 Domestic Hot Water Demand BNTV only Let’s consider the following example9.9 Domestic Hot Water Heating Using External Modulation Control 10.2 Operating the Burner and Set Up SECTION Operating Instructions10.1 Filling the Boiler System 10.2.1 Burner Operation10.2.2 Boiler Setup and Adjustment 10.3 Shutting Down Brute Elite10.4 To Restart Brute Elite 3. WAIT FIVE 5 MINUTESFigure 33A. Brute Elite Gas Valves 285, 399 and 80-285Figure 33B. Brute Elite Gas Valves 600, 750 and SECTION Maintenance 11.1 System Maintenance11.2 Appliance Maintenance and Component Description yearly, unless otherwise noted11.2.5 Flame Sensor 11.2.4 Ignitor AssemblyIgniters and sensors get hot and can cause burns or injury 11.2.7 Blower 11.2.6 Transformer with Integral Circuit Breaker11.2.8 Heat Exchanger Coils SECTION Trouble Shooting 12.3 Error Codes - See Table11.2.9 Gas Pressure Switches optional 12.1 Sequence of OperationPROBLEM SOLUTIONcontinued next page CODE#Table 18. Error Codes see SectionSECTION Replacement Parts 13.2 Parts List13.1 General Information Jacket Components - See FigureGas Train Components - See Figure Heat Exchanger Components - See Figure Contact Customer Service at 800 900-9275 Electrical Components - See FigureFigure 35. Jacket Components Figure 36A. Internal Components, Sizes Figure 36B. Internal Components, SizesFigure 36C. Internal Components, Sizes Figure 37A. Gas Train Components, Sizes Figure 37B. Gas Train Components, Sizes Figure 38. Heat Exchanger Components Figure 39. Electrical Components Brute Elite Tech. Service 800 Service Parts 800Warranty Service 800 Ambler, PA