11.2.9Gas Pressure Switches (optional)
The high and low gas pressure switches are 24V
manual reset switches that act to cut power to the gas valves if the gas pressure is too low or too high for proper operation. The gas pressure switches used are integrally vent limited, and do not require venting to atmosphere. To remove a switch, remove the screw on the plastic housing and pull the clear cover off. Disconnect the two wires from the screw terminals. Twist the switch off the pipe nipple. Reassemble in reverse order. For natural gas, set the low gas pressure switch to 3" w.c. For propane, set the low gas pressure switch to 5" w.c. For natural and propane, set the high gas pressure switch to 14".
11.2.10 Gas Conversion
Brute Elite units can be converted from natural to propane gas or from propane to natural gas easily in the field. Some units require the addition of a gas orifice along with proper gas valve adjustment. Other units require no additional parts, only proper gas valve adjustment. Please contact the Bradford White factory for specific information regarding the gas conversion of an appliance. If a gas conversion is performed, the unit must be identified with the appropriate gas labels and a conversion sticker to allow technicians performing maintenance in the future to properly identify the gas type of the appliance.
SIZE (MBTU) | KIT NUMBER |
80 | CA006201 |
|
|
105 | CA006202 |
150 | CA006203 |
199 | CA006204 |
|
|
210 | CA006204 |
285 | CA006205 |
399 | CA006207 |
|
|
500 | CA006207 |
600 | CA006207 |
750 | CA006207 |
|
|
850 | CA006207 |
Table 17. Propane Gas Conversion Kits.
SECTION 12.
Trouble Shooting
12.1 Sequence of Operation
Brute Elite is a cold start appliance that should start only on a call for heat from a tank aquastat, room thermostat, zone valve end switch or other space temperature control device.
1.Upon a call for heat: (a) the internal pump and system pump will start; (b) the blower will begin a 30 second
2.Following the prepurge cycle the direct spark ignition will spark and will begin a 4 second trial for ignition. The unit is allowed one or three ignition retries.
3.The gas valve will then be energized and a reduced rate ignition will occur. The unit will remain in a reduced rate
4.After the reduced rate start time is over, the unit will be in normal operation. Firing rate will modulate based on the heating load via the temperature controller settings and readings.
5.When the call for heat is complete, or the unit reaches its setpoint temperature, the gas valve will close, and the fan will continue to run for its 20 second post- purge. If a pump delay time is used, the pump will continue to run for the specified amount of time (adjustable from 0.1 to 10 minutes).
12.2 Short Cycling
Because Brute Elite is a modulating boiler, and its input will decrease when there is a reduction in heating load, short cycling is greatly reduced. If the heating load drops below the minimum input of the boiler for an extended period, the boiler will have a tendency to short cycle. This can be a symptom of improper control strategy or setpoints, or a load distribution problem. Brute Elite has a