Bradford-White Corp BNTH, BNTV, Modulating Boiler warranty SECTION Gas Supply and Piping

Page 18
SECTION 4.

Page 18

BRADFORD WHITE CORP.

 

 

 

 

3.Insofar as it is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.

4.Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so the appliance will operate continuously.

5.Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.

6.After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.

7.Any improper operation of the common venting system should be corrected so that the installation conforms to the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Installation Codes. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as deter- mined using the appropriate tables and guidelines in the National Fuel Gas Code, ANSI Z223.1 NFPA 54 and/or CSA B149.1, Installation Codes.

SECTION 4.

Gas Supply and Piping

4.1 Gas Supply and Piping

Gas piping should be supported by suitable hangers or floor stands, not the appliance.

Review the following instructions before proceeding with the installation.

1.Verify that the appliance is fitted for the proper type of gas by checking the rating plate. Brute Elite will function properly without the use of high altitude modification at elevations up to 10,000 feet (3050 m).

2.The maximum inlet gas pressure must not exceed 13" W.C. (3.2kPa). The minimum inlet gas pressure is 4" W.C. (1.0kPa).

3.Refer to Tables 6A, 6B, 6C and 6D to size piping.

4.Run gas supply line in accordance with all applicable codes.

5.Locate and install manual shutoff valves in accordance with state and local requirements.

6.A sediment trap must be provided upstream of the gas controls.

7.All threaded joints should be coated with piping compound resistant to action of liquefied petroleum gas.

8.The appliance and its individual shutoff valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 PSIG (3.45kPa).

9.The unit must be isolated from the gas supply system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.45kPa).

10.The appliance and its gas connection must be leak tested before placing it in operation.

11.Purge all air from gas lines.

4.1 Gas Supply and Piping WARNING:

Open flame can cause gas to ignite and result in property damage, severe injury, or loss of life.

NOTE: The Brute Elite appliance and all other gas appliances sharing the gas supply line must be firing at maximum capacity to properly measure the inlet supply pressure. The pressure can be measured at the supply pressure port on the gas valve. Low gas pressure could be an indication of an undersized gas meter, undersized gas supply lines and/or an obstructed gas supply line. Some Brute Elite units are equipped with low and high gas pressure switches that are integrally vent limited. These types of devices do not require venting to atmosphere.

Image 18
Contents Installation and Operation Instructions for Installation and Operation InstructionsDocument BRUTE ELITESECTION TABLE OF CONTENTSBrute Elite Control Setup and Operation General InformationReplacement Parts SECTION MaintenanceTrouble Shooting SECTION Modes of Operation1.2 Model Identification SECTION General Information1.1 Introduction Model NomenclatureFigure 1. Location of Components, Sizes Figure 2. Location of Components, SizesFigure 3. Location of Components, Size Figure 4. Location of Components, SizeFigure 5. Location of Components, Size Figure 6. Location of Components, SizeFigure 7. Location of Components, Sizes 750 and 1.3 Appliance Overview 1.4 Warranty1.6 Dimensions 1.5 UnpackingFigure 9. Dimensional Drawing, Sizes Dimensions are nominal and are shown in inches, cmBrute Elite is for indoor installations only SECTION Locating the Appliance2.1 Locating the Appliance 3.1.1 Combustion Air From Room SECTION Venting and Combustion Air3.1 Combustion Air 3.1.2 Ducted Combustion Air3.2 Venting Figure 10. Combustion Air and Vent Through RoofTable 5. Required Exhaust Vent Material A. exhaust vent terminal not included 3.3 Locating Vent & Combustion Air Terminals3.2.1 Venting Requirements Unique to Canada E. CPVC exhaust pipe section 80-500 not incl5. For concentric vent, follow instructions included with vent kit 3.3.5 Installations in the Commonwealth of Massachusetts3.3.2 Side Wall Combustion Air Terminal 3.3.3 Vertical Vent TerminalFigure 12. Combustion Air and Vent Through Side Wall 3. Signage 3.4 Common Vent Test2. Approved Carbon Monoxide Detectors 4. InspectionSECTION Gas Supply and Piping 4.1 Gas Supply and Piping3. Refer to Tables 6A, 6B, 6C and 6D to size piping 5.2 Brute Elite Water Heater Flow and Head Requirements see Table SECTION Pump Requirements5.1 Brute Elite Boiler Flow and Head Requirements see Table Table 6ASECTION 6A Water Connections - BNTH Boiler 6A.1 BNTH System Piping Hot Supply Connections6A.2 BNTH Cold Water Make-Up 6A.5 Recognized Chemicals 6A.4 BNTH Suggested Piping Schematics6A.3 Freeze Protection 1. Sentinel Performance Solutions Group 2. Hercules Chemical CompanyFigure 15. Hydronic Piping - Single Boiler zoning with circulators Brute Elite Figure 17. Hydronic Piping - Multiple Boilers zoning with circulators Brute Elite PagePage Brute Elite PagePage 6B.2 Piping Requirements SECTION 6B6B.1 BNTV Water Quality Water Connections - BNTV Water Heater6B.4 Freeze Protection 6B.5 BNTV Suggested Piping Schematics6B.3 Cold Water Make-Up 6B.6 BNTV Suggested PumpsCaution Pump sizing must be based opon Figure 25. DHW Piping, Two Heaters, One Vertical TankFigure 26. DHW Piping, Two Heaters, Two Vertical Tanks water hardness at job site7.1 Main Power SECTION Electrical Connections7.3 24Vac Transformer with Integral Circuit Breaker 7.10 Lead Lag/ Cascading Wiring Connections7.2 Pump Connections 7.4 Hydronic Call for HeatFigure 28. Lead-Lag / Cascading Wiring Connections 7.11 Wiring Diagrams see Figures 29 and Figure 29. Ladder DiagramFigure 30. Wiring Diagram all sizes SECTION Brute Elite Control Setup and Operation 8.1 Display Navigation8.2 Ignition Control- Sequence of Events 8.5 High Limit 8.3 Modulation Control8.5 Anti-Short Cycle ASC 8.7 Outlet Water Temperature8.12.1 Lead Lag Setpoint 8.12.5 Lead Lag Base Load Setting8.13 Boiler Pump Interrupt 8.12.2 Lead Lag Master/Slave SelectionSECTION Modes of Operation 9.2 Hydronic Heating with Outdoor Reset9.4 Hydronic Heating Using External Modulation Control 9.1 Hydronic Heating Demand9.8 Domestic Hot Water Demand BNTV only 9.5 Hydronic Heating Using Local Lead- Lag/Cascading Feature9.7 Warm Weather Shutdown Let’s consider the following example9.9 Domestic Hot Water Heating Using External Modulation Control 10.1 Filling the Boiler System 10.2 Operating the Burner and Set UpSECTION Operating Instructions 10.2.1 Burner Operation10.4 To Restart Brute Elite 10.2.2 Boiler Setup and Adjustment10.3 Shutting Down Brute Elite 3. WAIT FIVE 5 MINUTES80-285 Figure 33A. Brute Elite Gas Valves 285, 399 andFigure 33B. Brute Elite Gas Valves 600, 750 and 11.2 Appliance Maintenance and Component Description SECTION Maintenance11.1 System Maintenance yearly, unless otherwise noted11.2.4 Ignitor Assembly 11.2.5 Flame SensorIgniters and sensors get hot and can cause burns or injury 11.2.6 Transformer with Integral Circuit Breaker 11.2.7 Blower11.2.8 Heat Exchanger Coils 11.2.9 Gas Pressure Switches optional SECTION Trouble Shooting12.3 Error Codes - See Table 12.1 Sequence of Operationcontinued next page PROBLEMSOLUTION CODE#Table 18. Error Codes see Section13.1 General Information SECTION Replacement Parts13.2 Parts List Jacket Components - See FigureGas Train Components - See Figure Heat Exchanger Components - See Figure Contact Customer Service at 800 900-9275 Electrical Components - See FigureFigure 35. Jacket Components Figure 36A. Internal Components, Sizes Figure 36B. Internal Components, SizesFigure 36C. Internal Components, Sizes Figure 37A. Gas Train Components, Sizes Figure 37B. Gas Train Components, Sizes Figure 38. Heat Exchanger Components Figure 39. Electrical Components Brute Elite Warranty Service 800 Tech. Service 800Service Parts 800 Ambler, PA