Bradford-White Corp BNTH, BNTV SECTION Venting and Combustion Air, Combustion Air From Room

Page 12
SECTION 3.

Page 12

BRADFORD WHITE CORP.

 

 

 

 

SECTION 3.

Venting and Combustion Air

3.1 Combustion Air

Brute Elite boilers and water heaters must have provisions for combustion and ventilation air in accordance with the applicable requirements for Combustion Air Supply and Ventilation in the National Fuel Gas Code, ANSI Z223 1; or in Canada, the Natural Gas and Propane Installation Code, CSA B149.1. All applicable provisions of local building codes must also be adhered to.

A Brute Elite unit can take combustion air from the space in which it is installed, or the combustion air can be ducted directly to the unit. Ventilation air must be provided in either case.

3.1.1Combustion Air From Room

In the United States, the most common

requirements specify that the space shall communicate with the outdoors in accordance with method 1 or 2, which follow. Where ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect.

HORIZONTAL INTAKE AND EXHAUST PVC VENT TERMINAL KITS

SIZE

2" PVC

3" PVC

4" PVC

6" PVC

Standard

Concentric

Standard

Concentric

Standard

Standard

 

 

CA006000

CA005900 239-44069-01

 

 

80

included

optional

optional

optional

n/a

n/a

 

 

 

 

 

 

 

105

included

optional

optional

optional

n/a

n/a

150

n/a

n/a

included

optional

n/a

n/a

 

 

 

 

 

 

 

199/210

n/a

n/a

included

optional

n/a

n/a

 

 

 

 

 

 

 

285

n/a

n/a

optional

optional

included

n/a

399

n/a

n/a

n/a

n/a

included

n/a

 

 

 

 

 

 

 

500

n/a

n/a

n/a

n/a

included

n/a

 

 

 

 

 

 

 

600

n/a

n/a

n/a

n/a

included

optional

750

n/a

n/a

n/a

n/a

n/a

included

 

 

 

 

 

 

 

850

n/a

n/a

n/a

n/a

n/a

included

 

 

 

 

 

 

 

Concentric vent terminal = 10 ft. pipe length.

Method 1: Two permanent openings, one

commencing within 12" (300mm) of the top and one commencing within 12" (300mm) of the bottom, of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors. When directly communicating with the outdoors, or when communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4000 Btu/hr (550 square mm/kW) of total input rating of all equipment in the enclosure. When communicating to the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than 1 square inch per 2000 Btu/hr (1100 square mm/kW) of total input rating of all equipment in the enclosure.

Method 2: One permanent opening, commencing within 12" (300mm) of the top of the enclosure, shall be permitted. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that directly communicate with the outdoors and shall have a minimum free area of 1 square inch per 3000 Btu/hr (734 square mm/kW) of the total input rating of all equipment located in the enclosure. This opening must not be less than the sum of the areas of all vent connectors in the confined space.

Other methods of introducing combustion and ventilation air are acceptable, providing they conform to the requirements in the applicable codes listed above.

In Canada, consult local building and safety codes or, in absence of such requirements, follow CAN/CGA B149.

3.1.2 Ducted Combustion Air

The combustion air can be taken through the wall, or through the roof. When taken from the wall, it must be taken from out-of-doors by means of the horizontal wall terminal, shown in Table(s) 3. See Table 2 to select the appropriate diameter air pipe. When taken from the roof, a field-supplied rain cap or an elbow arrangement must be used to prevent entry of rain water (see Figure10).

Use ABS, PVC, CPVC or galvanized pipe for the

Table 3a. PVC Vent Terminal Kits.

SIZE

PRO TECH (FasNSeal)

 

HEAT FAB (Saf-T-Vent)

 

 

Z FLEX (Z-Vent)

 

 

Boiler

 

Flue

Intake Air

Boiler

Intermediate

Flue

Intake Air

Boiler

Flue

Intake Air

 

 

Adapter

Termination

Termination

Adapter

Adapter

Termination

Termination

Adapter

Termination

Termination

399-600

F303759

 

FSBS4

FSAIH04

KB285600

9454BUREZ-1*

9492

9414TERM

2SVSLA04

2SVSTP04

2SVSTEX0490

 

 

FSRC4(R.C)

303888

 

 

5400CI

 

 

2SVSRCX04

 

 

750-850

F303759

 

FSBS6

FSAIH04

Table 3b. Approved Stainless Steel Terminations and Adapters.

(intake only)

 

303888

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTALLATION STANDARDS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MATERIAL

 

 

UNITED STATES

 

 

 

CANADA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ABS

 

 

ANSI/ASTM D1527

 

 

 

 

 

 

 

PVC, sch 40

 

ANSI/ASTM D1785 or D2665

 

Air pipe material must be chosen

 

 

CPVC, sch 40

 

 

ANSI/ASTM F441

 

based upon the intended application of the boiler.

Single wall galv. steel

 

 

26 gauge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 4. Required Combustion Air Pipe Material.

Image 12
Contents Installation and Operation Instructions DocumentInstallation and Operation Instructions for BRUTE ELITETABLE OF CONTENTS Brute Elite Control Setup and OperationSECTION General InformationSECTION Maintenance Trouble ShootingReplacement Parts SECTION Modes of OperationSECTION General Information 1.1 Introduction1.2 Model Identification Model NomenclatureFigure 1. Location of Components, Sizes Figure 2. Location of Components, SizesFigure 3. Location of Components, Size Figure 4. Location of Components, SizeFigure 5. Location of Components, Size Figure 6. Location of Components, SizeFigure 7. Location of Components, Sizes 750 and 1.4 Warranty 1.6 Dimensions1.3 Appliance Overview 1.5 UnpackingFigure 9. Dimensional Drawing, Sizes Dimensions are nominal and are shown in inches, cmBrute Elite is for indoor installations only SECTION Locating the Appliance2.1 Locating the Appliance SECTION Venting and Combustion Air 3.1 Combustion Air3.1.1 Combustion Air From Room 3.1.2 Ducted Combustion Air3.2 Venting Figure 10. Combustion Air and Vent Through RoofTable 5. Required Exhaust Vent Material 3.3 Locating Vent & Combustion Air Terminals 3.2.1 Venting Requirements Unique to CanadaA. exhaust vent terminal not included E. CPVC exhaust pipe section 80-500 not incl3.3.5 Installations in the Commonwealth of Massachusetts 3.3.2 Side Wall Combustion Air Terminal5. For concentric vent, follow instructions included with vent kit 3.3.3 Vertical Vent TerminalFigure 12. Combustion Air and Vent Through Side Wall 3.4 Common Vent Test 2. Approved Carbon Monoxide Detectors3. Signage 4. InspectionSECTION Gas Supply and Piping 4.1 Gas Supply and Piping3. Refer to Tables 6A, 6B, 6C and 6D to size piping SECTION Pump Requirements 5.1 Brute Elite Boiler Flow and Head Requirements see Table5.2 Brute Elite Water Heater Flow and Head Requirements see Table Table 6ASECTION 6A Water Connections - BNTH Boiler 6A.1 BNTH System Piping Hot Supply Connections6A.2 BNTH Cold Water Make-Up 6A.4 BNTH Suggested Piping Schematics 6A.3 Freeze Protection6A.5 Recognized Chemicals 1. Sentinel Performance Solutions Group 2. Hercules Chemical CompanyFigure 15. Hydronic Piping - Single Boiler zoning with circulators Brute Elite Figure 17. Hydronic Piping - Multiple Boilers zoning with circulators Brute Elite PagePage Brute Elite PagePage SECTION 6B 6B.1 BNTV Water Quality6B.2 Piping Requirements Water Connections - BNTV Water Heater6B.5 BNTV Suggested Piping Schematics 6B.3 Cold Water Make-Up6B.4 Freeze Protection 6B.6 BNTV Suggested PumpsFigure 25. DHW Piping, Two Heaters, One Vertical Tank Figure 26. DHW Piping, Two Heaters, Two Vertical TanksCaution Pump sizing must be based opon water hardness at job site7.1 Main Power SECTION Electrical Connections7.10 Lead Lag/ Cascading Wiring Connections 7.2 Pump Connections7.3 24Vac Transformer with Integral Circuit Breaker 7.4 Hydronic Call for HeatFigure 28. Lead-Lag / Cascading Wiring Connections 7.11 Wiring Diagrams see Figures 29 and Figure 29. Ladder DiagramFigure 30. Wiring Diagram all sizes SECTION Brute Elite Control Setup and Operation 8.1 Display Navigation8.2 Ignition Control- Sequence of Events 8.3 Modulation Control 8.5 Anti-Short Cycle ASC8.5 High Limit 8.7 Outlet Water Temperature8.12.5 Lead Lag Base Load Setting 8.13 Boiler Pump Interrupt8.12.1 Lead Lag Setpoint 8.12.2 Lead Lag Master/Slave Selection9.2 Hydronic Heating with Outdoor Reset 9.4 Hydronic Heating Using External Modulation ControlSECTION Modes of Operation 9.1 Hydronic Heating Demand9.5 Hydronic Heating Using Local Lead- Lag/Cascading Feature 9.7 Warm Weather Shutdown9.8 Domestic Hot Water Demand BNTV only Let’s consider the following example9.9 Domestic Hot Water Heating Using External Modulation Control 10.2 Operating the Burner and Set Up SECTION Operating Instructions10.1 Filling the Boiler System 10.2.1 Burner Operation10.2.2 Boiler Setup and Adjustment 10.3 Shutting Down Brute Elite10.4 To Restart Brute Elite 3. WAIT FIVE 5 MINUTES80-285 Figure 33A. Brute Elite Gas Valves 285, 399 andFigure 33B. Brute Elite Gas Valves 600, 750 and SECTION Maintenance 11.1 System Maintenance11.2 Appliance Maintenance and Component Description yearly, unless otherwise noted11.2.4 Ignitor Assembly 11.2.5 Flame SensorIgniters and sensors get hot and can cause burns or injury 11.2.6 Transformer with Integral Circuit Breaker 11.2.7 Blower11.2.8 Heat Exchanger Coils SECTION Trouble Shooting 12.3 Error Codes - See Table11.2.9 Gas Pressure Switches optional 12.1 Sequence of OperationPROBLEM SOLUTIONcontinued next page CODE#Table 18. Error Codes see SectionSECTION Replacement Parts 13.2 Parts List13.1 General Information Jacket Components - See FigureGas Train Components - See Figure Heat Exchanger Components - See Figure Contact Customer Service at 800 900-9275 Electrical Components - See FigureFigure 35. Jacket Components Figure 36A. Internal Components, Sizes Figure 36B. Internal Components, SizesFigure 36C. Internal Components, Sizes Figure 37A. Gas Train Components, Sizes Figure 37B. Gas Train Components, Sizes Figure 38. Heat Exchanger Components Figure 39. Electrical Components Brute Elite Tech. Service 800 Service Parts 800Warranty Service 800 Ambler, PA