Bradford-White Corp BWCV SECTION Gas Supply and Piping, Internet Version for Reference Only

Page 12
SECTION 3.

Internet Version for Reference Only

Page 12

Bradford White

 

 

 

 

 

Outdoor Vent

Outdoor

Model (Size)

Terminal

Combustion

 

 

Air Terminal

500

20254701

D2007900

750

20254703

D2007900

1000

20254705

D2008000

1250

D2007700

D2008000

1500

D2007700

D2008000

1750

D2007800

D2008000

2000

D2007800

D2008200

 

 

 

Table 6. Vent Terminals for Outdoor Units.

SECTION 3.

Gas Supply and Piping

3.1Gas Supply and Piping

Gas piping should be supported by suitable

hangers or floor stands, not by the appliance.

The Copper Brute II gas train allows the user to pipe the gas from either the right side or the left side of the unit. As shipped, the right side of the gas train is capped off, and there is a manual valve on the left side. If desired, the manual valve on the left side of the gas train may be moved to the right side, and the cap on the right side may be moved to the left.

Review the following instructions before proceeding with the installation.

1.Verify that the appliance is fitted for the proper type of gas by checking the rating plate. Copper Brute II heaters are equipped to operate at elevations up to 10000 feet (3050m). Copper Brute II heaters may be adjusted to operate properly at altitudes above 2500 feet (see Section 6.4.2) and the input will be reduced if the heating value of the gas supply is below sea level values.

2.The maximum inlet gas pressure must not exceed 13" W.C (3.2kPa). The minimum inlet gas pressure is 5" W.C. (1.2kPa).

3.Refer to Table 7, size supply.

4.Run gas supply line in accordance with all applicable codes.

5.Locate and install manual shutoff valves in accordance with state and local requirements.

6.A sediment trap must be provided upstream of the gas controls.

7.All threaded joints should be coated with piping compound resistant to action of liquefied petroleum gas.

8.The appliance and its individual shutoff valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 PSIG (3.45kpa).

9.The unit must be isolated from the gas supply system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.45kpa).

10.The appliance and its gas connection must be leak tested before placing it in operation.

11.Purge all air from gas lines.

 

 

Distance from Gas Meter

 

 

Model and

 

or Last Stage Regulator

 

 

 

0-31m

 

31-61m

 

61-91m

Gas Type

0-100'

100-200'

200-300'

500 natural

1-1/2"

3.8cm

2"

5.1cm

2"

5.1cm

500 propane

1"

2.5cm

1-1/2"

3.8cm

1-1/2"

3.8cm

750 natural

2"

5.1cm

2"

5.1cm

2-1/2"

6.4cm

750 propane

1-1/2"

3.8cm

1-1/2"

3.8cm

2"

5.1cm

1000 natural

2"

5.1cm

2-1/2"

6.4cm

3"

7.6cm

1000 propane

1-1/2"

3.8cm

2"

5.1cm

2-1/2"

6.4cm

1250 natural

2-1/2"

6.4cm

2-1/2"

6.4cm

3"

7.6cm

1250 propane

2"

5.1cm

2"

5.1cm

2-1/2"

6.4cm

1500 natural

2-1/2"

6.4cm

3"

7.6cm

3"

7.6cm

1500 propane

2"

5.1cm

2-1/2"

6.4cm

2-1/2"

6.4cm

1750 natural

2-1/2"

6.4cm

3"

7.6cm

3"

7.6cm

1750 propane

2"

5.1cm

2-1/2"

6.4cm

2-1/2"

6.4cm

2000 natural

3"

7.6cm

3"

7.6cm

3-1/2"

8.9cm

2000 propane

2-1/2"

6.4cm

2-1/2"

6.4cm

3"

7.6cm

Notes:

1.These figures are based on 1/2" (0.12kPa) water column pressure drop.

2.Check supply pressure and local code requirements before proceeding with work. 3.Pipe fittings must be considered when determining gas pipe sizing.

Table 7. Gas Piping Size.

Image 12
Contents Internet Version for Reference Only Installation and Operation Instructions forInstallation and Operation Instructions Copper BruteTABLE OF CONTENTS SECTION 7. MaintenanceSECTION 8. Trouble Shooting SECTION 9. Wiring DiagramsSECTION General Information 1.1 Introduction1.2 Model Identification 1.4 Dimensions 1.3 Warranty1.5 Locating the Appliance Figure 1. Dimensional Data SECTION Venting and Combustion Air 1.6 Locating Pump-Mounted Water Heater with Respect to Storage TanksFrom Outside Wall 2.1 Combustion Air2.1.2 Intake Combustion Air 2.2 Venting 2.2.1 Vent Categories2.2.2 Category I Vent 2.2.3 Common Venting SystemsFigure 3. Combustion Air and Vent Through Side Wall 2.3 Locating Vent & Combustion Air Terminals Important Note Massachusetts Code Requirement2.3.1 Side Wall Vent Terminal 2.3.2 Side Wall Combustion Air Terminal2.4 Common Vent Test 2.5 Vent Terminals for Outdoor Units2.3.3 Vertical Vent Terminal 2.3.4 Vertical Combustion Air TerminalSECTION Gas Supply and Piping 3.1 Gas Supply and PipingSECTION Water Connections Copper Brute II Water Heater 4.1 Water System Piping Water Heater4.2 Hot Water Supply Piping - Water Heater 4.3 Water Flow Requirements - Water HeaterTable 8. Water Flow Requirements Figure 4. Water Heater Piping - One Heater, One TankFigure 5. Water Heater Piping - Multiple Heaters, One Tank Figure 6. Water Heater Piping - One Heater, Multiple Tanks Figure 7. Water Heater Piping - Multiple Heaters, Multiple Tanks 5.1 Main Power SECTION Electrical Connections4.4 Combined Water Heating potable and Space Heating - Water Heater 4.5 Freeze Protection - Water Heater5.3 External Staging Control Wiring AVERTISSEMENTSECTION Operating Instructions 6.1 Sequence of Operation6.2 Programming the Temperature Control 6.2.1 System Piping “Primary Secondary Piping” “Parallel Piping”6.2.2 Choosing the Mode 6.2.3 Programming6.3.3 for more information BOIL MAX Boiler Maximum Temperature Boiler Start BOIL START The BOIL 6.2.4 Choosing the Mode for your Application Mechanical aquastat in a domestic hot water storage tank6.3 Advanced Topics Mode 5 Primary secondary piping with outdoor reset6.3.1 Differential 6.3.2 Staging Mode6.3.3 Boiler Minimum BOIL MIN 6.3.4 Boiler Maximum BOIL MAX 6.3.5 Boiler Target Temperature6.3.6 Pump Operation 6.3.7 Set point Operation6.3.9 Outdoor Reset Operation Outdoor Design OUTDR DSGN - The6.3.10 External Heater Operation 6.4 Operating the Burner and Set Up 6.4.1 Set Up for 0 to 2500 Feet Altitude6.3.11 Limit Controls 6.3.12 Advanced Programming ModeSECTION Maintenance 7.1 System Maintenance6.5 Shutting Down the Copper Brute 6.6 To Restart the Copper Brute7.2 Appliance Maintenance and Component Description 7.2.4 Manual Reset High Limit Control 7.2.5 Automatic Reset High Limit Control7.2.1 Burners 7.2.2 Filter7.2.12 Flow Switch 7.2.9 Ignition Sensors7.2.10 Transformer 7.2.11 BlowersSECTION Trouble Shooting 8.1 Resolving Lockouts8.2 Delayed Ignition - Possible Causes 8.3 Short CyclingERROR DISPLAYED DESCRIPTION OF ERROR8.6 Troubleshooting Copper Brute II Controls SECTION Wiring Diagrams Figure 18. Copper Brute II 500 - 750 Ladder DiagramFigure 19. Copper Brute II 1000 Ladder Diagram Figure 20. Copper Brute II 1250 - 2000 Ladder Diagram Figure 21. Copper Brute II 500 - 1000 Wiring Schematic Figure 22. Copper Brute II 1250 - 2000 Wiring Schematic Note Positions of field wiring terminals may vary, but Figure 23. Field Wiringterminal designations are as indicated Reference Only Wiring for Modes 1Figure 24. Field MODEVersion for Reference Only 25. Field Wiring for ModeInternet Copper Brute II 1250, 1500, 1750 & 2000 4-Stage Heater
Related manuals
Manual 64 pages 39.09 Kb