Copper Brute II | Page 35 |
|
|
|
|
ERROR DISPLAYED
VIEW
DESCRIPTION OF ERROR
The control was unable to read a piece of information from its EEPROM. The control will stop operation until all settings in the Adjust menu have been checked by the user or installer.
VIEW
BOIL OUT
VIEW
BOIL OUT
VIEW
BOIL IN
VIEW
BOIL IN
VIEW
BOILSUP
VIEW
BOILSUP
OUTDR VIEW
OUTDR VIEW
VIEW
TANK
VIEW
TANK
The control is no longer able to read the heater outlet sensor due to a short circuit. In this case, if the heater inlet sensor is present and operational, the control will operate using the heater inlet sensor. Otherwise, the control will not operate the heater stages.
The control is no longer able to read the heater outlet sensor due to an open circuit. In this case, if the heater inlet sensor is present and operational, the control will operate using the heater inlet sensor. Otherwise, the control will not operate the heater stages.
The control is no longer able to read the heater inlet sensor due to a short circuit. In this case, the control will continue operation.
The control is no longer able to read the heater inlet sensor due to an open circuit. In this case, the control will continue operation.
The control is no longer able to read the heater supply sensor due to a short circuit. In this case, if the heater outlet sensor is present and operational, the control will operate based on the heater outlet sensor. If the heater outlet sensor is not available and the heater inlet sensor is present and operational, the control will operate using the heater inlet sensor.
Otherwise, the control will not operate the heater stages.
The control is no longer able to read the heater supply sensor due to an open circuit. In this case, if the heater outlet sensor is present and operational, the control will operate based on the heater outlet sensor. If the heater outlet sensor is not available and the heate inlet sensor is present and operational, the control will operate using the heater inlet sensor Otherwise, the control will not operate the heater stages.
The control is no longer able to read the outdoor sensor due to a short circuit. In this case, the control assumes an outdoor temperature of 32°F and continues operation.
The control is no longer able to read the outdoor sensor due to an open circuit. In this case, the control assumes an outdoor temperature of 32°F and continues operation.
The control is no longer able to read the tank sensor due to a short circuit. In this case the control will not operate the heater stages.
The control is no longer able to read the tank sensor due to an open circuit. In this case the control will not operate the heater stages.