Internet Version for Reference Only
Copper Brute II | Page 29 |
|
|
|
|
signal to these terminals. The control energizes the heater pump (if equipped), energizes the
6.3.11 Limit Controls
In addition to the temperature control, Copper Brute II appliances are fitted with a manual reset high limit and an automatic reset high limit. These are located near the rear of the cabinet on the right side, behind the slide out drawer (see Figure 17). Both controls should be set at least 25°F higher than the target temperature to avoid short cycling. To set these controls, remove the control panel cover and pull the control panel out to gain access. Appliances with reversed heat exchangers have the limit controls relocated to the left side of the appliance. The left access door must be removed to gain access to the limit controls on these appliances.
6.3.12Advanced Programming Mode
Advanced programming mode allows the
installer to set the temperature control for proportional staging. In advanced programming mode, the interstage differential, interstage delay, interstage on and off delay, and minimum time on and off are all set manually.
NOTE: Advanced programming mode is rarely required. It is intended for advanced installers, and only when the application demands such programming.
To enter advanced programming mode, remove the bezel on the temperature control by pulling out at the bottom. Remove the small Phillips head screw to access the dip switch. The dip switch is mounted on a circuit board.
Locate the letter “A” on the circuit board and slide the corresponding dip switch toward the letter “A”. The default setting of this dip switch is toward the “OFF” lettering on the circuit board.
6.4Operating the Burner and Set Up
6.4.1 Set Up for 0 to 2500 Feet Altitude
The Copper Brute II appliance utilizes a modular design to achieve its
1.Using this manual, make sure the installation is complete and fully in compliance with the instructions.
2.Determine that the appliance and system are filled with water and all air has been bled from both. Open all valves.
3.Observe all warnings on the Operating Instructions label and turn on gas and electrical power to appliance.
4.Switch on the heater power switch located on the right side of the unit.
5.The heater will enter the start sequence, as long as the unit is being called for heat. The blower and pump come on for
6.When the unit is running, the supply gas pressure must be checked. Inlet gas pressure must not exceed 13" W.C. (3.2kPa). The minimum inlet gas pressure is 5" W.C. (1.2kPa).
7.Once the inlet gas pressure is verified, the outlet gas pressure from each valve (manifold gas pressure) must be checked, and adjusted, if necessary. The manifold gas pressure must be 2.5" W.C. (0.62kPa).
8.Complete the setup by checking the CO2 at the outlet of the unit. The CO2 should be 8% for natural gas, or 9.2% for propane.
9.After placing the heater in operation, the Burner Safety Shutoff Device must be tested. To test:
(a)Close gas shutoff valve with burner operating.
(b)The flame will go out and blower will continue to run for the post purge cycle. One additional attempt to light will follow. Ignition will not occur as the gas is off. The ignition control will lockout, and will have to be reset before the unit will operate.
(c)Open gas shutoff valve. Restart the appliance. The ignition sequence will start again and the burner will start. The appliance will return to its previous mode of operation.
NOTE: Models 1000 - 2000 have two ignition controls and two ignitors, which work independently of one another. If the ignition control for stages 1 and 2 fails to properly light the main burners for those stages, the second ignition control will still be active, and will be able to energize stages 3 and 4. This, of course, will only occur if all other safety devices confirm that the unit will run in a safe condition.