Bradford-White Corp BWCV warranty Common Vent Test, Vent Terminals for Outdoor Units

Page 11

Internet Version for Reference Only

Copper Brute II

Page 11

 

 

 

 

2.Locate the terminal so that it will not be subject to damage by accident or vandalism.

3.Locate the combustion air terminal so that it cannot be blocked by snow. The National Fuel Gas Code requires that it be at least 12 inches (30 cm) above grade, but the installer may determine it should be higher, depending upon local conditions.

4.If the Copper Brute II is side-wall vented to the same wall, locate the vent terminal at least 3 feet (0.9m) horizontally from the combustion air terminal, and locate the vent terminal at least 1 foot (0.3m) above the combustion air terminal (see Figure 3).

2.3.3 Vertical Vent Terminal

When the unit is vented through the roof, the vent must extend at least 3 feet (0.9m) above the point at which it penetrates the roof. It must extend at least 2 feet (0.6m) higher than any portion of a building within a horizontal distance of 10 feet (3.0m), and high enough above the roof line to prevent blockage from snow. When the combustion air is taken from the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal (see Figure 2).

2.3.4Vertical Combustion Air Terminal

When combustion air is taken from the roof, a

field-supplied rain cap or an elbow arrangement must be used to prevent entry of rain water (see Figure 2). The opening on the end of the terminal must be at least 12" (30cm) above the point at which it penetrates the roof, and high enough above the roof line to prevent blockage from snow. When the vent terminates on the roof, the combustion air must terminate at least 12" (30cm) below the vent terminal.

2.4Common Vent Test

When an existing heater is removed from a

common venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it.

At the time of removal of an existing heater, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.

1.Seal any unused openings in the common venting system.

2.Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.

3.Insofar as it is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.

4.Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.

5.Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.

6.After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.

7.Any improper operation of the common venting system should be corrected so that the installation conforms to the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Installation Codes. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part II of the National Fuel Gas Code, ANSI Z223.1/ NFPA 54 and/or CSA B149.1, Installation Codes.

2.5Vent Terminals for Outdoor Units

For outdoor applications, the vent and

combustion air openings must be covered with proper terminals to prevent rain, snow and other objects from falling into the heater.

If local codes allow, outdoor installations may use 1' of appropriately sized galvanized single wall or B-Vent and a rain cap for exhaust vent termination in the default configuration (venting out of the top). An appropriately sized galvanized 90° ell, positioned with the opening facing down, may be used on the combustion air inlet in the default configuration on the back of the unit. Note that some local codes may require a higher vertical vent height, extending above any perimeter fencing, etc. In installations where the appearance of the vent is objectionable, the low profile vent terminals in Table 6 may be used.

Part numbers for the low profile terminals to cover the vent and combustion air openings are shown in Table 6.

Image 11
Contents Copper Brute Internet Version for Reference OnlyInstallation and Operation Instructions for Installation and Operation InstructionsSECTION 9. Wiring Diagrams TABLE OF CONTENTSSECTION 7. Maintenance SECTION 8. Trouble Shooting1.2 Model Identification SECTION General Information1.1 Introduction 1.5 Locating the Appliance 1.4 Dimensions1.3 Warranty Figure 1. Dimensional Data 2.1 Combustion Air SECTION Venting and Combustion Air1.6 Locating Pump-Mounted Water Heater with Respect to Storage Tanks From Outside Wall2.1.2 Intake Combustion Air 2.2.3 Common Venting Systems 2.2 Venting2.2.1 Vent Categories 2.2.2 Category I VentFigure 3. Combustion Air and Vent Through Side Wall 2.3.2 Side Wall Combustion Air Terminal 2.3 Locating Vent & Combustion Air TerminalsImportant Note Massachusetts Code Requirement 2.3.1 Side Wall Vent Terminal2.3.4 Vertical Combustion Air Terminal 2.4 Common Vent Test2.5 Vent Terminals for Outdoor Units 2.3.3 Vertical Vent Terminal3.1 Gas Supply and Piping SECTION Gas Supply and Piping4.3 Water Flow Requirements - Water Heater SECTION Water Connections Copper Brute II Water Heater4.1 Water System Piping Water Heater 4.2 Hot Water Supply Piping - Water HeaterFigure 4. Water Heater Piping - One Heater, One Tank Table 8. Water Flow RequirementsFigure 5. Water Heater Piping - Multiple Heaters, One Tank Figure 6. Water Heater Piping - One Heater, Multiple Tanks Figure 7. Water Heater Piping - Multiple Heaters, Multiple Tanks 4.5 Freeze Protection - Water Heater 5.1 Main PowerSECTION Electrical Connections 4.4 Combined Water Heating potable and Space Heating - Water HeaterAVERTISSEMENT 5.3 External Staging Control Wiring6.2 Programming the Temperature Control SECTION Operating Instructions6.1 Sequence of Operation 6.2.3 Programming 6.2.1 System Piping “Primary Secondary Piping”“Parallel Piping” 6.2.2 Choosing the Mode6.3.3 for more information BOIL MAX Boiler Maximum Temperature Boiler Start BOIL START The BOIL Mechanical aquastat in a domestic hot water storage tank 6.2.4 Choosing the Mode for your ApplicationMode 5 Primary secondary piping with outdoor reset 6.3 Advanced Topics6.3.3 Boiler Minimum BOIL MIN 6.3.1 Differential6.3.2 Staging Mode 6.3.7 Set point Operation 6.3.4 Boiler Maximum BOIL MAX6.3.5 Boiler Target Temperature 6.3.6 Pump Operation6.3.10 External Heater Operation 6.3.9 Outdoor Reset OperationOutdoor Design OUTDR DSGN - The 6.3.12 Advanced Programming Mode 6.4 Operating the Burner and Set Up6.4.1 Set Up for 0 to 2500 Feet Altitude 6.3.11 Limit Controls6.6 To Restart the Copper Brute SECTION Maintenance7.1 System Maintenance 6.5 Shutting Down the Copper Brute7.2 Appliance Maintenance and Component Description 7.2.2 Filter 7.2.4 Manual Reset High Limit Control7.2.5 Automatic Reset High Limit Control 7.2.1 Burners7.2.11 Blowers 7.2.12 Flow Switch7.2.9 Ignition Sensors 7.2.10 Transformer8.3 Short Cycling SECTION Trouble Shooting8.1 Resolving Lockouts 8.2 Delayed Ignition - Possible CausesDESCRIPTION OF ERROR ERROR DISPLAYED8.6 Troubleshooting Copper Brute II Controls Figure 18. Copper Brute II 500 - 750 Ladder Diagram SECTION Wiring DiagramsFigure 19. Copper Brute II 1000 Ladder Diagram Figure 20. Copper Brute II 1250 - 2000 Ladder Diagram Figure 21. Copper Brute II 500 - 1000 Wiring Schematic Figure 22. Copper Brute II 1250 - 2000 Wiring Schematic terminal designations are as indicated Note Positions of field wiring terminals may vary, butFigure 23. Field Wiring MODE Reference OnlyWiring for Modes 1 Figure 24. FieldCopper Brute II 1250, 1500, 1750 & 2000 4-Stage Heater Version for Reference Only25. Field Wiring for Mode Internet
Related manuals
Manual 64 pages 39.09 Kb