Bradford-White Corp BWCV Internet Version for Reference Only, Ignition Sensors, Transformer

Page 33
7.2.9 Ignition Sensors

Internet Version for Reference Only

Copper Brute II

Page 33

 

 

 

 

ignitor out. Install in reverse order, always using a new ignitor gasket with the replacement ignitor.

7.2.10 TransformerCaution

Ignitor gets hot.

7.2.9 Ignition Sensors

The ignition sensors ensure that the main flame is ignited, so that raw gas is not allowed to fill the combustion chamber. Copper Brute II models 500 and 750 have one sensor. Models 1000 to 2000 have two sensors (one for each ignition control). The ignitors are the ignition sensors on the heater. There are no separate ignition sensors.

7.2.10 Transformer

The Copper Brute II’s transformer is not capable of supplying control voltage for external devices such as zone valves, which must have their own separate power supply. Should a transformer need replacing, shut off the 120-volt power. Unplug the transformer wires, remove the mounting screws and remove the transformer. Replace transformer in the reverse order.

7.2.11 Blowers

The combustion air blowers bring the combustion air for the heater from the upper chamber to the lower chamber. Mixing of the gas and air occurs in the burners. Models 500, 750 and 1000 each have one blower, and models 1250 to 2000 each have two blowers (one blower for stages 1 and 2, and one for stages 3 and 4). If a blower change is required, turn off the 120-volt power and gas supply to the unit. Remove the front panel. Disconnect the blower's wire harness. Remove the screws at the blower flange, and pull the blower out. Replace blower in reverse order, ensuring that all joints are made correctly. After replacement, ensure that the unit operates properly, by following the set-up procedure in this manual.

7.2.12 Flow Switch

The heater uses a paddle-type flow switch to ensure that the unit has water flow before ignition is allowed.

7.2.13 Heat Exchanger Coil

7.2.11 BlowersWARNING

Black carbon soot buildup on a dirty heat exchanger can be ignited by a random spark or flame, thereby creating a risk of fire or explosion.. To prevent this from happening, dampen the soot deposits with a wet brush or fine water spray before servicing the heat exchanger.

The heater has a pre-mixed burner system. These systems provide the burners with sufficient air for complete combustion, and black carbon sooting is seldom experienced. If sooting is suspected, view ports for inspection of the heat exchanger are provided on both sides of the heater. They are located below the headers, and are accessed by opening the small round cover that is attached by one screw. In the unlikely event that there is a buildup of black carbon soot

or other debris on the heat exchanger, clean per the following:

1.Disconnect the electrical supply to the unit.

2.Turn off the gas supply by closing the manual gas valve on the heater.

3.Disconnect and remove the wires, conduit and sensors from all components that are attached to the inlet/outlet header.

4.Isolate the heat exchanger from the water supply.

5.Disconnect the header flanges from the inlet and outlet.

6.Allow the heat exchanger to drain. Remove the front cover(s) by removing the rubber access strip(s) and the retaining screws. Remove the venting and remove the top, by removing the screws that attach the top to the side panels. Remove the side panels. Remove the front lower panels sealing the combustion area. To remove the gas train, disconnect the unions located below the intermediate pan and the field installed union located outside the cabinet, and pull up, bringing the union end connectors through the grommets in the intermediate pan. To remove the intermediate pan, remove the slide out control assembly and blower(s) to reveal the screws. Remove the screws holding the intermediate pan, and lift up to remove it. The heat exchanger has integral metal sections attached, which connect to the frame of the heater. Locate and remove the screws along the front, rear and bottom of the integral metal sections, and remove the heat exchanger and metal sections by lifting up. On the larger appliances, a center heat exchanger support must be unbolted before it can be removed.

7.Remove the heat exchanger from the unit. NOTE: The heat exchangers are heavy and may require two people to remove to avoid personal injury.

8.Clean the heat exchanger: A light accumulation of soot or corrosion on the outside of the heat exchanger can be easily removed. Use a wire brush to remove loose soot and scale from the heat exchanger. Do not use water or compressed air for cleaning.

9.NOTE: While the heat exchanger is out of the unit, inspect the firewall refractory insulation. Replace if necessary.

Image 33
Contents Installation and Operation Instructions for Internet Version for Reference OnlyInstallation and Operation Instructions Copper BruteSECTION 7. Maintenance TABLE OF CONTENTSSECTION 8. Trouble Shooting SECTION 9. Wiring DiagramsSECTION General Information 1.1 Introduction1.2 Model Identification 1.4 Dimensions 1.3 Warranty1.5 Locating the Appliance Figure 1. Dimensional Data 1.6 Locating Pump-Mounted Water Heater with Respect to Storage Tanks SECTION Venting and Combustion AirFrom Outside Wall 2.1 Combustion Air2.1.2 Intake Combustion Air 2.2.1 Vent Categories 2.2 Venting2.2.2 Category I Vent 2.2.3 Common Venting SystemsFigure 3. Combustion Air and Vent Through Side Wall Important Note Massachusetts Code Requirement 2.3 Locating Vent & Combustion Air Terminals2.3.1 Side Wall Vent Terminal 2.3.2 Side Wall Combustion Air Terminal2.5 Vent Terminals for Outdoor Units 2.4 Common Vent Test2.3.3 Vertical Vent Terminal 2.3.4 Vertical Combustion Air Terminal3.1 Gas Supply and Piping SECTION Gas Supply and Piping4.1 Water System Piping Water Heater SECTION Water Connections Copper Brute II Water Heater4.2 Hot Water Supply Piping - Water Heater 4.3 Water Flow Requirements - Water HeaterFigure 4. Water Heater Piping - One Heater, One Tank Table 8. Water Flow RequirementsFigure 5. Water Heater Piping - Multiple Heaters, One Tank Figure 6. Water Heater Piping - One Heater, Multiple Tanks Figure 7. Water Heater Piping - Multiple Heaters, Multiple Tanks SECTION Electrical Connections 5.1 Main Power4.4 Combined Water Heating potable and Space Heating - Water Heater 4.5 Freeze Protection - Water HeaterAVERTISSEMENT 5.3 External Staging Control WiringSECTION Operating Instructions 6.1 Sequence of Operation6.2 Programming the Temperature Control “Parallel Piping” 6.2.1 System Piping “Primary Secondary Piping”6.2.2 Choosing the Mode 6.2.3 Programming6.3.3 for more information BOIL MAX Boiler Maximum Temperature Boiler Start BOIL START The BOIL Mechanical aquastat in a domestic hot water storage tank 6.2.4 Choosing the Mode for your ApplicationMode 5 Primary secondary piping with outdoor reset 6.3 Advanced Topics6.3.1 Differential 6.3.2 Staging Mode6.3.3 Boiler Minimum BOIL MIN 6.3.5 Boiler Target Temperature 6.3.4 Boiler Maximum BOIL MAX6.3.6 Pump Operation 6.3.7 Set point Operation6.3.9 Outdoor Reset Operation Outdoor Design OUTDR DSGN - The6.3.10 External Heater Operation 6.4.1 Set Up for 0 to 2500 Feet Altitude 6.4 Operating the Burner and Set Up6.3.11 Limit Controls 6.3.12 Advanced Programming Mode7.1 System Maintenance SECTION Maintenance6.5 Shutting Down the Copper Brute 6.6 To Restart the Copper Brute7.2 Appliance Maintenance and Component Description 7.2.5 Automatic Reset High Limit Control 7.2.4 Manual Reset High Limit Control7.2.1 Burners 7.2.2 Filter7.2.9 Ignition Sensors 7.2.12 Flow Switch7.2.10 Transformer 7.2.11 Blowers8.1 Resolving Lockouts SECTION Trouble Shooting8.2 Delayed Ignition - Possible Causes 8.3 Short CyclingDESCRIPTION OF ERROR ERROR DISPLAYED8.6 Troubleshooting Copper Brute II Controls Figure 18. Copper Brute II 500 - 750 Ladder Diagram SECTION Wiring DiagramsFigure 19. Copper Brute II 1000 Ladder Diagram Figure 20. Copper Brute II 1250 - 2000 Ladder Diagram Figure 21. Copper Brute II 500 - 1000 Wiring Schematic Figure 22. Copper Brute II 1250 - 2000 Wiring Schematic Note Positions of field wiring terminals may vary, but Figure 23. Field Wiringterminal designations are as indicated Wiring for Modes 1 Reference OnlyFigure 24. Field MODE25. Field Wiring for Mode Version for Reference OnlyInternet Copper Brute II 1250, 1500, 1750 & 2000 4-Stage Heater
Related manuals
Manual 64 pages 39.09 Kb