Bradford-White Corp BWCV Locating Vent & Combustion Air Terminals, Side Wall Vent Terminal

Page 10
2.3Locating Vent & Combustion Air Terminals

Internet Version for Reference Only

Page 10

Bradford White

 

 

 

 

the vent pipe. Horizontal runs must slope downwards not less than 1⁄4 inch per foot (2 cm/m) from the unit to the vent terminal. Reference Table 1 for the size of the Category III vent system. Up to three elbows can be used with 50 linear feet (15.2m) of pipe. Subtract 10 allowable linear feet (3.0m) for every additional elbow used.

Term

Description

Pipe

Must comply with UL Standard 1738

 

such as Type 29-4C Stainless Steel

 

(either insulated or non-insulated).

Joint

Follow vent manufacturer’s instructions

Sealing

 

Table 5. Required Horizontal Venting Material.

2.3.1 Side Wall Vent TerminalWARNING

The outdoor vent terminal gets hot. Unit must be installed in such a way as to reduce the risk of burns from contact with the vent terminal.

2.3Locating Vent & Combustion Air Terminals

2.3.1 Side Wall Vent Terminal

The appropriate Bradford White side wall vent hood must be used, and is listed in the installation and operation manual. The terminal provides a means of installing the vent piping through the building wall, and must be located in accordance with ANSI Z223.1/ NFPA 54 and applicable local codes. In Canada, the installation must be in accordance with CSA B149.1 or

.2 and local applicable codes. Consider the following when installing the terminal:

1.Figure 3 shows the requirements for mechanical vent terminal clearances for the U.S. and Canada.

2.Vent terminals for condensing appliances or appliances with condensing vents are not permitted to terminate above a public walkway, or over an area where condensate or vapor could create a nuisance or hazard.

3.Locate the vent terminal so that vent gases cannot be drawn into air conditioning system inlets.

4.Locate the vent terminal so that vent gases cannot enter the building through doors, windows, gravity inlets or other openings. Whenever possible, locations under windows or near doors should be avoided.

5.Locate the vent terminal so that it cannot be blocked by snow. The installer may determine that a vent terminal must be higher than the minimum shown in codes, depending upon local conditions.

6.Locate the terminal so the vent exhaust does not settle on building surfaces or other nearby objects. Vent products may damage such surfaces or objects.

7.If the water heater uses ducted combustion air from an intake terminal located on the same wall, locate the vent terminal at least 3 feet (0.9m) horizontally from the combustion air terminal, and locate the vent terminal at least 1 foot (0.3m) above the combustion air terminal.

Important Note:

Massachusetts Code Requirement.

For Sidewall Vented Appliances with Vent Ter- minals Located Less Than 7 Feet above grade:

1.Massachusetts Code requires that a CO Detector and Alarm, listed by an approved third party inspection agency to ANSI/UL 2034 and complying with NFPA720 (2005 Edition) be installed on each floor level in which there are bedroom(s), if there is not one already present. The location shall be in the living space outside the bedroom(s).

2.An additional CO Detector and Alarm, as indicated above, shall be located in the room that houses the appliance and shall be powered by the same electrical supply as the appliance such that one service switch serves both the appliance and the CO detector. The CO detector shall have a battery backup.

3.The vent terminal, and if applicable the air intake terminal, shall be the approved Laars terminals. A copy of this manual shall remain with the appliance at the completion of the installation.

4.A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

For Sidewall Vented Appliances with Vent Ter- minal Located More Than 7 Feet above grade:

Items 1, 2 and 3 above shall apply. Follow the Installation Instructions provided with the CO Detectors when installing them. For issues with the CO Detectors, contact the installing contractor.

2.3.2Side Wall Combustion Air Terminal

The Bradford White side wall combustion air

terminal (listed in Table 1) must be used when the unit takes its combustion air through a duct from a side wall. Consider the following when installing the terminal:

1.Do not locate the air inlet terminal near a source of corrosive chemical fumes (e.g., cleaning fluid, chlorinated compounds, etc.)

Image 10
Contents Installation and Operation Instructions Internet Version for Reference OnlyInstallation and Operation Instructions for Copper BruteSECTION 8. Trouble Shooting TABLE OF CONTENTSSECTION 7. Maintenance SECTION 9. Wiring Diagrams1.1 Introduction SECTION General Information1.2 Model Identification 1.3 Warranty 1.4 Dimensions1.5 Locating the Appliance Figure 1. Dimensional Data From Outside Wall SECTION Venting and Combustion Air1.6 Locating Pump-Mounted Water Heater with Respect to Storage Tanks 2.1 Combustion Air2.1.2 Intake Combustion Air 2.2.2 Category I Vent 2.2 Venting2.2.1 Vent Categories 2.2.3 Common Venting SystemsFigure 3. Combustion Air and Vent Through Side Wall 2.3.1 Side Wall Vent Terminal 2.3 Locating Vent & Combustion Air TerminalsImportant Note Massachusetts Code Requirement 2.3.2 Side Wall Combustion Air Terminal2.3.3 Vertical Vent Terminal 2.4 Common Vent Test2.5 Vent Terminals for Outdoor Units 2.3.4 Vertical Combustion Air TerminalSECTION Gas Supply and Piping 3.1 Gas Supply and Piping4.2 Hot Water Supply Piping - Water Heater SECTION Water Connections Copper Brute II Water Heater4.1 Water System Piping Water Heater 4.3 Water Flow Requirements - Water HeaterTable 8. Water Flow Requirements Figure 4. Water Heater Piping - One Heater, One TankFigure 5. Water Heater Piping - Multiple Heaters, One Tank Figure 6. Water Heater Piping - One Heater, Multiple Tanks Figure 7. Water Heater Piping - Multiple Heaters, Multiple Tanks 4.4 Combined Water Heating potable and Space Heating - Water Heater 5.1 Main PowerSECTION Electrical Connections 4.5 Freeze Protection - Water Heater5.3 External Staging Control Wiring AVERTISSEMENT6.1 Sequence of Operation SECTION Operating Instructions6.2 Programming the Temperature Control 6.2.2 Choosing the Mode 6.2.1 System Piping “Primary Secondary Piping”“Parallel Piping” 6.2.3 Programming6.3.3 for more information BOIL MAX Boiler Maximum Temperature Boiler Start BOIL START The BOIL 6.2.4 Choosing the Mode for your Application Mechanical aquastat in a domestic hot water storage tank6.3 Advanced Topics Mode 5 Primary secondary piping with outdoor reset6.3.2 Staging Mode 6.3.1 Differential6.3.3 Boiler Minimum BOIL MIN 6.3.6 Pump Operation 6.3.4 Boiler Maximum BOIL MAX6.3.5 Boiler Target Temperature 6.3.7 Set point OperationOutdoor Design OUTDR DSGN - The 6.3.9 Outdoor Reset Operation6.3.10 External Heater Operation 6.3.11 Limit Controls 6.4 Operating the Burner and Set Up6.4.1 Set Up for 0 to 2500 Feet Altitude 6.3.12 Advanced Programming Mode6.5 Shutting Down the Copper Brute SECTION Maintenance7.1 System Maintenance 6.6 To Restart the Copper Brute7.2 Appliance Maintenance and Component Description 7.2.1 Burners 7.2.4 Manual Reset High Limit Control7.2.5 Automatic Reset High Limit Control 7.2.2 Filter7.2.10 Transformer 7.2.12 Flow Switch7.2.9 Ignition Sensors 7.2.11 Blowers8.2 Delayed Ignition - Possible Causes SECTION Trouble Shooting8.1 Resolving Lockouts 8.3 Short CyclingERROR DISPLAYED DESCRIPTION OF ERROR8.6 Troubleshooting Copper Brute II Controls SECTION Wiring Diagrams Figure 18. Copper Brute II 500 - 750 Ladder DiagramFigure 19. Copper Brute II 1000 Ladder Diagram Figure 20. Copper Brute II 1250 - 2000 Ladder Diagram Figure 21. Copper Brute II 500 - 1000 Wiring Schematic Figure 22. Copper Brute II 1250 - 2000 Wiring Schematic Figure 23. Field Wiring Note Positions of field wiring terminals may vary, butterminal designations are as indicated Figure 24. Field Reference OnlyWiring for Modes 1 MODEInternet Version for Reference Only25. Field Wiring for Mode Copper Brute II 1250, 1500, 1750 & 2000 4-Stage Heater
Related manuals
Manual 64 pages 39.09 Kb