Thermal Well Testing

Thermal Well Testing

CAUTION

Do not use standard multi-meter probes for this testing. Doing so will damage the connector. Use special pin type electronic probes or small diameter wire pins inserted into connector.

Follow the procedure, below, if the water heater gas control has gone into a ECO lock- out (4 flash, 3 second pause). Reset the gas control by rotating the setpoint knob to the minimum setting for at least 6 seconds before returning to the desired water tem- perature setting.

Step 1. Unplug the thermal well connector from the gas control.

Thermal well connector

Step 2. With a multi-meter set to the ohms setting, meas- ure the resistance between the middle and right side wires.

Step 3. With a multi-meter set to the ohms setting, meas- ure the resistance between the middle and left side wires.

Page 34

34

Image 34
Contents Service Manual Table of Contents Page Page Bradford White ECO-DEFENDER Safety System IntroductionHow to Use this Manual How the Safety System WorksTools Required for Service Tools RequiredSpecifications Vent Tables GallonSpecifications Wiring Diagram Control TimingsSequence of Operation Power Up SequenceNormal Heating Sequence Normal Heating Sequence cont’d Abnormal OperationAbnormal Operation cont’d Sequence of Operation Sequence of Operation Troubleshooting LED Status Control Status Probable Cause Service ProcedureTroubleshooting Troubleshooting Burner Cleaning Procedure Burner MaintenanceBurner Inspection Burner Cleaning Procedure cont’d Pilot Maintenance Pilot Inspection, Testing and ReplacementPilot Inspection, Testing and Replacement cont’d Page Pressure Switch Testing Pressure Switch TestingPressure Switch Testing cont’d Pressure Switch Replacement Pressure Switch ReplacementBlower Testing Blower TestingPage Blower Installation Blower ReplacementBlower Removal Blower Installation cont’d Blower Temperature Switch TestingBlower Temperature Switch Testing Blower Temperature Switch Testing cont’d Switch SettingBlower Temperature Switch Replacement Blower Temperature Switch ReplacementThermal Well Testing Thermal Well TestingThermal Well Testing cont’d Determine Tank TemperatureDetermine Water Temperature Inside Tank Sensor Resistance at Various Temperatures Component DisassemblyGas Control & Thermal Well Removal From Water Heater Gas Control Removal Gas Control Assembly to the Thermal Well Gas Control AssemblyGas Control Removal From Thermal Well cont’d Gas Control Assembly to the Thermal Well cont’d Flammable Vapor Sensor Testing Flammable Vapor Sensor TestingVAC Circuit Trace Safety Circuit Voltage Trace Safety Circuit Voltage TraceRemove the Blower to Gain Access to the Flue Baffle Blower RemovalDip Tube Inspection and Replacement Remove the Blower to Gain Access to the Flue Baffle cont’dDip Tube Inspection Anode Inspection and Replacement Anode InspectionInner Door Removal Procedure Inner Door RemovalInner Door Removal Procedure cont’d Inner Door Gasket ReplacementInner Door Gasket Replacement Procedure Inner Door Installation Inner Door Installation with GasketArrestor Cleaning ScreenLok Flame Arrestor Cleaning ProcedureCommon Terms Common TermsParts List Part Name and DescriptionParts@bradfordwhite.com Techserv@bradfordwhite.com