Troubleshooting
| LED Status | Control Status |
| Probable Cause | Service Procedure |
|
|
|
|
| 1. Unstable pilot |
|
|
| Six flashes, |
| 2. Pilot tube block or restricted | 1. See Burner Inspection |
| |
| one flash, | Failed to light pilot, |
| 3. Oxidation | on page 20 |
|
| three second | system resets after |
| electrode |
| |
| pause (Soft | (5) minutes |
| 4. Wire damage to pilot | Testing and Replacement |
|
| Lockout) |
| assembly or bad connection at | on page 22 |
| |
|
|
|
| gas valve |
|
|
|
|
|
|
|
|
|
|
|
| 1. | Vent blockage or improper |
|
|
|
|
| vent configuration | 1. Check vent or vent |
| |
|
|
| 2. | Pressure switch tubing kinked | tables |
|
|
| Pressure switch or | or blocked |
| ||
| Six flashes, | blower temperature | 3. | Faulty pressure switch | Testing on page 25 |
|
| two flashes, | switch opened | 4. | Vent termination being | 4. Refer to venting section |
|
| three second | during burner | affected by wind | of installation manual |
| |
| pause (Soft | operation. System | 5. | Blower not spinning up to | 5. See Blower Testing on |
|
| Lockout) | resets after (5) | speed | page 28 |
| |
|
| minutes | 6. | Blower temperature or |
| |
|
|
| exhaust temperature too high | Temperature Switch |
| |
|
|
| 7. | Faulty blower temperature | Testing on page 31 |
|
|
|
| switch |
|
| |
|
|
| 1. | Unstable pilot |
|
|
| Six flashes, |
| 2. | Pilot tube block or restricted | 1. See Burner Inspection |
|
|
| 3. | Oxidation | on page 20 |
| |
| three | Pilot flame |
| |||
| electrode |
| ||||
| flashes, | extinguished, |
| |||
| 4. | Wire damage to pilot | Testing and Replacement |
| ||
| three second | system auto resets |
| |||
| pause (Soft | after (5) minutes | assembly or bad connection at | on page 22 |
| |
| gas control | 5. Refer to Installation & |
| |||
| Lockout) |
|
| |||
|
| 5. | Insufficient combustion air | Operation Manual |
| |
|
|
|
| |||
|
|
| 6. | Insufficient gas pressure |
|
|
| Six flashes, | Undesired false |
|
|
|
|
| four flashes, |
|
|
|
| |
| pilot flame sensed, | Pilot valve stuck in open position | Replace gas control |
| ||
| three second |
| ||||
| pause | system auto resets |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| 1. | Flammable vapor present |
|
|
|
| Flammable vapor | 2. | Flammable vapor sensor |
|
|
| Seven | sensor or | exposed to excessive moisture |
|
| |
| flashes, | resettable thermal | 3. | Flammable vapor sensor | See Flammable Vapor |
|
| three second | switch fault | exposed to extreme ambient | Sensor Testing on page 40 |
| |
| pause | detected, see | temperature |
|
| |
|
| warning label | 4. | Resettable thermal switch |
|
|
|
|
| open |
|
| |
|
|
| 1. | Flammable vapor sensor out |
|
|
| Eight | Flammable vapor | of specification; verify Flammable |
|
| |
| flashes, one | Vapor Sensor (FVS) resistance is |
|
| ||
| sensor out of | See Flammable Vapor |
| |||
| flash, three | specification, | not below 25 k. | Sensor Testing on page 40 |
| |
| second | 2. | Possible short in flammable |
| ||
| possible short |
|
| |||
| pause | vapor sensor or resettable |
|
| ||
|
|
|
| |||
|
|
| thermal switch wiring |
|
| |
|
|
|
|
|
|
|
Page 18