| is | |
|
|
|
|
| |
Code + Description | Cause | Solution | Remark |
| |
|
|
|
|
| |
S18 (blocking error) | Short circuit in sensor | Replace sensor S1 | To replace the necessary parts, you must contact your installation |
| |
Short circuit in temp. | circuit |
|
| engineer |
|
sensor S1 in the |
|
|
|
|
|
collector |
|
|
|
|
|
|
|
|
|
| |
F01 (blocking error) | Live and neutral | Connect live and neutral correctly (3.11 "Electrical connection"); | See the SGE electrical diagram (17 "Appendices") |
| |
| connected wrong way | the appliance is |
|
| |
Defect in power supply | round |
|
|
|
|
circuit |
|
|
|
|
|
Condensation on the | 1. | Disconnect the lead at the flame probe | If errors persist, contact your installation engineer |
| |
|
| ||||
| flame probe | 2. | Ignite the appliance three times, with an interrupted ionisation |
|
|
|
|
|
| ||
|
|
| circuit |
|
|
|
| 3. | Reconnect the ionisation lead to the flame probe |
|
|
|
| 4. | Ignite the appliance again |
|
|
|
| 5. | The repeated ignition attempts will have caused the |
|
|
|
|
| condensation to evaporate |
|
|
|
|
|
|
| |
| Floating neutral | Install an isolating transformer (3.11.4 "Isolating transformer") | Contact your installation engineer to have an isolating transformer |
| |
|
|
|
| installed |
|
|
|
|
|
|
|
F02 (lock out error) | Defective motor and/or | 1. | Check the motor and rotor | See the SGE electrical diagram (17 "Appendices") |
|
Fan fails to run at | rotor. | 2. | Replace the fan if the motor or rotor is defective. |
|
|
| To have the wiring replaced and a new fan fitted, you must contact |
| |||
| 3. | Reset appliance controller |
| ||
correct speed. |
| your installation engineer |
| ||
|
|
|
|
|
|
| Damaged wiring | 1. | Check the wiring between the fan and the controller. |
|
|
|
| 2. | If any wires are damaged, the wiring harness must be replaced. |
|
|
|
| 3. | Reset appliance controller |
|
|
|
|
|
|
|
|
| Dirty or blocked fan | 1. | Check if the fan is dirty |
|
|
|
| 2. | Check that the rotor can rotate freely |
|
|
|
| 3. | Reset appliance controller |
|
|
|
|
|
|
|
|
| Because of a drop in | 1. | Check the supply voltage, this must be 230 VAC |
|
|
| the supply voltage, the | 2. | Reset appliance controller |
|
|
| fan is not running at the |
|
| ||
| correct speed. |
|
|
|
|
Instruction manual SGE | 83 |