| is | |
|
|
|
|
| |
Code + Description | Cause | Solution | Remark |
| |
|
|
|
|
|
|
F10 (lock out error) | Pressure switch not | 1. | Check the running speed of the fan (12.5 "Display the selected | If the error cannot be resolved or is persistent, contact your |
|
Restriction on the | closing |
| appliance") | installation engineer |
|
| 2. | Check that the hoses on the pressure switch and the air supply | To replace the necessary parts, you must contact your installation |
| |
number of ignition |
|
| hose between fan and burner are correctly fitted. Refit them if | engineer |
|
attempts based on |
|
|
|
| |
|
| necessary |
|
| |
pressure switch state |
|
|
|
| |
changes. |
| 3. | Check for cracks in the hoses on the pressure switch and in the |
|
|
|
|
| air supply hose between fan and burner. If necessary, replace |
|
|
|
|
| the hoses. |
|
|
|
| 4. | Check that the flue gas outlet is compliant (3.9 "Air supply and |
|
|
|
|
| flue"). |
|
|
|
| 5. | Check for blockage in the flue gas discharge. Remove any |
|
|
|
|
| blockage that may be present |
|
|
|
| 6. | Check for blockage in the condensation water discharge. |
|
|
|
|
| Remove any blockage that may be present. |
|
|
|
| 7. | Measure the pressure differential across the pressure switch. |
|
|
|
|
| See the table in Preparation for |
|
|
|
|
| maintenance (15.2 "Preparation for maintenance"). If there is |
|
|
|
|
| insufficient pressure differential, clean the heat exchanger. If the |
|
|
|
|
| pressure differential is acceptable, check that the pressure |
|
|
|
|
| switch is closing, using a multimeter. |
|
|
|
|
|
|
| |
F11 (blocking error) | Defective gas valves | See F07. |
|
| |
Flame detection with |
|
|
|
|
|
closed gas valve. |
|
|
|
|
|
|
|
|
|
|
|
F17 (blocking error) | No power supply at | 1. | Check that there is power to the solar heating system controller | See the SGE electrical diagram (17 "Appendices") |
|
Communication error | solar controller | 2. | The measured voltage must be 230VAC | If the error persists, consult your installation engineer |
|
|
|
| |||
|
|
|
|
| |
|
|
|
|
|
|
| No cable or damaged | 1. | Check the wiring (communication cable) between the main | See the SGE electrical diagram (17 "Appendices") |
|
| cable |
| controller and the solar heating system controller | For replacement of the cable, contact your installation engineer |
|
|
| 2. | If cable missing, connect the cable |
|
|
|
| 3. | If cable damaged, replace the cable |
|
|
|
|
|
|
|
|
Instruction manual SGE | 87 |