Code + Description | Cause | Solution | Remark |
| |
|
|
|
|
|
|
F03 (lock out error) | Damaged wiring/Open | 1. | Check the wiring between the pressure switch and the | If the error cannot be resolved or is persistent, contact your |
|
The pressure switch | circuit |
| controller | installation engineer |
|
| 2. | If necessary, replace the wiring | To replace the necessary parts, you must contact your installation |
| |
fails to work correctly |
| engineer |
| ||
|
|
|
| ||
| Pressure switch not | 1. | Check the running speed of the fan (12.5 "Display the selected |
|
|
| closing |
| appliance") |
|
|
|
| 2. | Check that the hoses on the pressure switch and the air supply |
|
|
|
|
| hose between fan and burner are correctly fitted. Refit them if |
|
|
|
|
| necessary |
|
|
|
| 3. | Check for cracks in the hoses on the pressure switch and in the |
|
|
|
|
| air supply hose between fan and burner. If necessary, replace |
|
|
|
|
| the hoses. |
|
|
|
| 4. | Check that the flue gas outlet is compliant (3.9 "Air supply and |
|
|
|
|
| flue"). |
|
|
|
| 5. | Check for blockage in the flue gas discharge. Remove any |
|
|
|
|
| blockage that may be present |
|
|
|
| 6. | Check for blockage in the condensation water discharge. |
|
|
|
|
| Remove any blockage that may be present. |
|
|
|
| 7. | Measure the pressure differential across the pressure switch. |
|
|
|
|
| See the table in Preparation for |
|
|
|
|
| maintenance (15.2 "Preparation for maintenance"). If there is |
|
|
|
|
| insufficient pressure differential, clean the heat exchanger. If the |
|
|
|
|
| pressure differential is acceptable, check that the pressure |
|
|
|
|
| switch is closing, using a multimeter. |
|
|
|
|
|
|
|
|
Instruction manual SGE | 84 |