Code + Description | Cause | Solution | Remark |
| |
|
|
|
|
| |
F06 (lock out error) | Damaged cable in | Check the wiring of the flame probe. If necessary, replace the | If the error persists, contact your installation engineer. |
| |
| contact with metal | wiring. | To replace the necessary parts, you must contact your installation |
| |
Short circuit between | surface. |
|
| engineer |
|
flame probe and earth |
|
|
|
|
|
Ceramic part of the | 1. | Check that the ceramic part of the flame probe is still intact in |
|
| |
| flame probe is |
| the vicinity of the burner's air distribution plate. |
|
|
| broken/cracked. | 2. | If not, the flame probe must be replaced. |
|
|
|
|
|
| ||
|
|
|
|
|
|
F07 (lock out error) | Defective gas valves | 1. | Check whether there is still burner pressure present after the | If the error cannot be resolved or is persistent, contact your |
|
|
|
| gas valves have closed. | installation engineer |
|
A flame has been |
| 2. | Check whether a flame is still present after the gas valves have | To replace the necessary parts, you must contact your installation |
|
detected after the gas |
| engineer |
| ||
valve was closed. |
|
| closed. |
|
|
| 3. | If this is the case, the gas control must be replaced. |
|
| |
|
|
|
| ||
|
|
|
|
|
|
F08 (lock out error) | Flame detection before | 1. | Reset the electronic controller. | If the error cannot be resolved or is persistent, contact your |
|
| the gas valve opened. | 2. | If the error reappears, replace the electronic controller. | installation engineer |
|
Error message from |
| To replace the necessary parts, you must contact your installation |
| ||
|
|
|
| ||
safety relay |
|
|
| engineer |
|
|
|
|
|
|
|
F09 (lock out error) | The temperature at the | 1. | Check that the circulation pump (if present) is working | If the error cannot be resolved or is persistent, contact your |
|
Water temperature | top of the tank exceeds | 2. | Check the position of the temperature sensor T . | installation engineer |
|
93 oC. |
| 1 |
|
| |
safety. |
| 3. | Reset appliance controller |
|
|
|
|
|
|
|
|