NOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system). The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/f • G)
(1) COOL operation
①Both indoor and outdoor units are under the same temperature/humidity condition.
Relative humidity(%) | |
20 | 50 |
25 | 60 |
30 | 70 |
➁Air flow speed : HI
➂Inverter output frequency : 33Hz
<How to work
1.Set emergency switch to COOL or HEAT.The switch is locat- ed on indoor unit.
2.Press emergency run ON/OFF button. 3.Compressor starts running at rated frequency. 4.Indoor fan runs at HI speed.
5.To cancel this operation,press emergency run ON/OFF button or any button on remote controller.
(kgf/F•Gauge) (MPa•Gauge)
Outdoor low pressure
8
7
6
5
4
3
2
0.8 |
|
|
|
0.7 |
| 33Hz |
|
|
|
| |
0.6 |
|
|
|
0.5 |
|
|
|
0.4 |
|
|
|
0.3 |
|
|
|
0.2 |
| 35 | (;) |
15 | 25 | ||
20 | 30 | (%) |
Ambient temperature(:)/ Ambient humidity(%)
Outdoor unit current (A)
9 |
|
|
|
8 |
|
|
|
7 |
|
|
|
6 |
|
|
|
5 |
| 33Hz |
|
|
|
| |
4 |
|
|
|
3 |
|
| (;) |
15 20 | 25 | 30 35 | |
|
|
| (%) |
Ambient temperature(:)/ Ambient humidity(%)
(2)HEAT operation
① Indoor DB(°C) 20.0
WB(°C) 14.5
Outdoor DB(°C) | 2 | 7 | 15 | 20.0 |
WB(°C) | 1 | 6 | 12 | 14.5 |
➁Set air flow to Hi speed.
➂Inverter output frequency is 45Hz.
Outdoor unit current (A)
10
9
8
7
6
5
4
45Hz
0 5 10 15 20 25
Ambient temperature(:)
18