12-3. Troubleshooting check table

Note . LED indicates "00" in the normal status.

7-segment LED display

Error mode

00

Normal

If there is defect in the following parts(electronic control P.C. board, relay P.C. board, high pressure switches(63H1,63H2),indoor /outdoor fan motor , or indoor coil thermistor), the compressor may stop even with the display remained at “ 00 “.In any case, reset the breaker and check the above-stated parts.

Symptom

 

Outdoor unit does not operate.

 

 

 

 

 

Display

Detecting method

Detecting method

Check points

 

 

 

 

a4

Outdoor power system abnor-

When the compressor operation has been interrupted by overcurrent

• Inverter output

(A4)

mality

protection continuously three times within 1 minute after start-up, the

• Compressor

 

compressor stops operation.

 

 

 

 

 

a3

Outdoor electronic control P.C.

When the nonvolatile memory data cannot be read properly on the out-

• Outdoor electronic control P.C. board

(A3)

board abnormality

door controller board

 

p1

Indoor unit and LEV abnor-

When the drain abnormality is detected in the indoor unit and the indoor

• Check the abnormality indication on the

main coil temperature is too low, or when any abnormality is detected in

indoor unit.

(P1)

mality

the components of indoor unit

• LEV

 

 

 

 

 

 

 

 

 

Symptom

 

Outdoor unit stops and restarts every 3 minutes.

 

 

 

 

 

Display

Detecting method

Detecting method

Check points

 

 

 

 

 

 

 

• Check the characteristic of the evapora-

e9

Evaporation temperature ther-

The compressor stops when a short or open circuit occurs in the evap-

tion temperature thermistor. Refer to F

(E9)

mistor abnormality

oration temperature thermistor during compressor running.

on page 32.

• Check the contact of P. C. board con-

 

 

 

 

 

nectors.

 

 

 

 

 

 

 

• Check the characteristic of the discharge

e6

Discharge temperature ther-

The compressor stops when a short or open circuit occurs in the dis-

temperature thermistor. Refer to F on

(E6)

mistor abnormality

charge temperature thermistor during compressor running.

page 32.

• Check the contact of P. C. board con-

 

 

 

 

 

nectors.

 

 

 

 

f8

 

 

• Check the characteristic of the fin temper-

Fin temperature thermistor

The compressor stops when a short or open circuit occurs in the fin tem-

ature thermistor. Refer to F on page 32.

(F8)

abnormality

perature thermistor during compressor running.

• Check the contact of P.C. board connec-

 

 

tors.

 

 

 

 

 

 

 

 

 

 

• Check the inverter and compressor.

 

 

 

Refer to E on page 31.

a8

Overcurrent protection

When over current is applied to the power module, the compressor

• Check the amount of gas.

(A8)

stops and restarts in 3 minutes.

• Check the indoor/outdoor air flow for

 

short cycle.

 

 

 

 

 

• Check the indoor unit air filter for

 

 

 

clogging.

 

 

 

 

d6

Discharge temperature over-

When the discharge temperature thermistor detects 116˚C or above, the

• Check the amount of gas and the refriger-

compressor stops and restarts operation in 3 minutes.

ant cycle.

(d6)

heat protection

(Protection will be released at 100; or below.)

• Check the outdoor unit air passage.

 

 

 

 

 

d4

 

 

• Check the outdoor unit air passage.

Fin temperature overheat pro-

When the fin temperature thermistor detects 89˚C or above, the com-

• Check the power module.

(d4)

tection

pressor stops and restarts operation in 3 minutes.

• Check the outdoor fan motor. Refer to G

 

 

on page 32.

 

 

 

 

 

 

 

d7

High pressure protection

When the compressor starts, primary current or output voltage stops the

• Amount of gas

(d7)

compressor and restarts in 3 minutes.

• Outdoor unit air passage.

 

• Check the ball valve.

 

 

 

 

 

 

f5

Room-A gas pipe temperature

When a short or open circuit occurs in the Room-A gas pipe

• Room A gas pipe temperature thermistor

characteristic.

(F5)

thermistor abnormality

temperature thermistor.

• Contact of P.C. board connectors.

 

 

 

 

 

 

f6

Room-B gas pipe temperature

When a short or open circuit occurs in the Room-B gas pipe

• Room B gas pipe temperature thermistor

characteristic.

(F6)

thermistor abnormality

temperature thermistor.

• Contact of P.C. board connectors.

 

 

 

 

 

 

f7

Room-C gas pipe temperature

When a short or open circuit occurs in the Room-C gas pipe

• Room C gas pipe temperature thermistor

characteristic.

(F7)

thermistor abnormality

temperature thermistor.

• Contact of P.C. board connectors.

 

 

 

 

 

 

p9

Room-D gas pipe temperature

When a short or open circuit occurs in the Room-D gas pipe

• Room D gas pipe temperature thermistor

characteristic.

(P9)

thermistor abnormality

temperature thermistor.

• Contact of P.C. board connectors.

 

 

 

 

 

 

26

Image 26
Contents Contents MXZ-32SV E1 MXZ-32SV E2Outdoor Unit Technical ChangesPart Names and Functions Indoor / Outdoor Correspondence Table Outdoor UnitIndoor Units Combination MXZ-32SV E1 , MXZ-32SV E209+09+12 15.05 13.80 9.0 07+09 10.35 09+09+12 14.04 12.87 Specification MXZ-32SV E1 , MXZ-32SV E2Heating DB Test conditionsCooling DB35 WB24 0dB =Outlines and Dimensions Unit mmWiring Diagram Models MXZ-32SV- E1Refrigerant System Diagram UnitmmCDB Capacity and the Input CurvesCWB Capacity and input correction by inverter output frequency Outdoor UNITMXZ-32SVOutdoor low pressure and outdoor unit current Heat operationCurrent 10 15 20 10 15 20 SSR61 Microprocessor ControlInverter Multi System Control LEV control Cool DRY Heat Operational frequency range DRY CoolHigh or low pressure protection Discharge temperature protection controlHeat defrosting control Relation between main sensor and actuator Refrigerant recovery control on heatingOutdoor fan control Before troubleshooting, check the following TroubleshootingInstruction of troubleshooting Lead wiring Housing point Troubleshooting procedureTroubleshooting check table LEVCheck the contact of LEV board connec Trouble criterion of main parts Outdoor unit does not operate. LED display display OFF Outdoor unit does not operate. LED displayWhen heating operation does not work. Start When cooling operation does not work. StartCheck of LEV Check of thermistor Check of HPS Test Point Diagram and Voltage MXZ-32SV E1 , MXZ-32SV E2 Electronic control P.C.boardMXZ-32SV E2 Noise filter P.C.board MXZ-32SV E1Outdoor FAN 220V-240V AC Reversing Valve 220V-240V AC Outdoor FAN 230V AC Reversing Valve 230V ACM P.C.board MXZ-32SV E1 MXZ-32SV E2 Relay P.C.board MXZ-32SV E1 MXZ-32SV E2MXZ-32SV Disassembly InstructionsOutdoor Unit Operating Procedure Photos Removing the compressor PhotoRemoving the linear expansion valve Photo Removing the fan motorRemoving the 4-way valve Photo Operating Procedure Photos Removing the reactorParts List Outdoor Unit Functional Parts MXZ-32SV E1Outdoor Unit Structural Parts MXZ-32SV E117 16 15 MXZ-32SV E2Accessory Parts MXZ-32SV E1 MXZ-32SV E2 Symbol Qty / unit Parts No Parts Name Wiring RemarksDifferent-diameter pipe Outlet guide