•When cooling, heat exchanger of
•When heating,
(LED display: 00, p1)

D Check of LEV
Start
Turn on power supply to the outdoor unit after checking LEV coil is mounted to the LEV body securely.
Is "click - click" sound heard?
Or, do you feel vibration of the LEV coil with a hand?
No
Disconnect the connector
(CN791: unit A, CN792: unit B, CN793: unit C,
CN794: unit D), and measure the resistance of LEV coil to check the integrity.
No
Replace the LEV coil.
Yes
Nomal
Yes Replace the electronic control P. C. board
•When heating, room does not get warm.
•When cooling, room does not get cool. (LED display: 00, a8)

E Check of inverter/ compressor
Start
Disconnect the lead wire to the compressor at terminals, and turn on power supply to the indoor and outdoor unit. Three minutes later, EMERGENCY OPERATION starts.
|
|
| W1 • After the outdoor fan starts running, wait for 1 minutes or more before | ||||||||||||||
|
|
| |||||||||||||||
Measure the voltage between |
| measuring the voltage. |
|
|
|
| |||||||||||
each leading to the compressor. | • The output voltage values in the above table have the tolerance of i20%. | ||||||||||||||||
U (BLK) - V (WHT) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
V (WHT) - W (RED) |
| No | LED indicator the inverter | No |
| 1. Turn off power supply of the indoor | |||||||||||
W (RED) - U (BLK) |
|
|
|
| stops due to over current? |
|
| and outdoor unit, and disconnect | |||||||||
Output voltage |
|
|
|
|
|
|
|
|
|
|
|
|
|
| the connector CN 551 in the relay | ||
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
COOL: 100V(58Hz) HEAT: 100V(58Hz) |
|
|
|
|
|
|
|
| Yes |
|
| P. C. board | |||||
Is voltage output? W1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2. Turn on power supply to the outdoor | ||
|
|
|
|
| Replace the electronic |
|
|
| |||||||||
| Yes |
|
|
|
|
|
|
|
|
| unit, and after 1 minutes or more | ||||||
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
| control P. C. board |
|
|
|
| |||||||
Is output balanced? | No |
|
|
|
|
|
|
|
| passed, check the resistance | |||||||
|
|
|
| with the I.P.M P. C. board. |
|
|
|
| |||||||||
|
|
|
|
|
|
|
| between the connector | |||||||||
|
|
|
|
|
|
|
|
| |||||||||
| Yes |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| CN551 pin 1 and pin 2. | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Turn off power supply of indoor and outdoor unit, |
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||
and measure the compressor winding resistance |
| No |
|
|
| 0" |
| Check the resistance | |||||||||
between the compressor terminals. |
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| between each terminal | ||||
Is there resistance of 0.27" to 0.34" between |
|
|
|
|
|
|
|
|
|
| |||||||
the each terminals? |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Infinite | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| Replace the |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| |||||||
| Yes |
|
|
|
|
|
|
| compressor. |
|
|
| After 1 minutes has passed since the | ||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Return the lead wire of compressor to former, and |
|
|
|
|
|
|
|
|
|
| power supply of outdoor unit was | ||||||
|
|
|
|
|
|
|
|
|
| turned off, disconnect the connector | |||||||
turn on power supply to indoor and outdoor unit. |
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
| CN 553 in the noise filter P. C. board. | |||||||
Three minutes later EMERGENCY OPERATION starts. |
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Clarify the causes by counting time until the inverter stops. 0 to 10 seconds: compressor rare short
10 to 60 seconds: compressor lock
60 seconds to 5minutes: refrigerant circuit defective
5 minutes or more: normal
0"
Replace the relay P. C. board.
Check the resistance HPS (63H2).
Infinite
Replace the
HPS (63H2).
31