Mitsubishi Electronics MXZ-32SV Disassembly Instructions, Outdoor Unit Operating Procedure Photos

Page 37

13

 

DISASSEMBLY INSTRUCTIONS

 

 

 

 

 

 

 

 

 

 

 

13-1 MXZ-32SV -

 

, MXZ-32SV -

 

 

 

 

 

 

E1

E2

 

 

 

 

 

OUTDOOR UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPERATING PROCEDURE

PHOTOS

 

 

 

 

 

 

 

 

 

1.Removing the compressor

Photo 1

(1)Remove the screws fo the service panel, and remove it.

 

 

 

 

Release refrigerant gas.

 

 

 

 

(2)Remove the screws of the top panel, and remove it.

 

 

Top panel

(3)Remove the screws of the front panel, and remove it.

 

 

 

 

 

 

(4)Disconnect the compressor lead wire. (TAB64,TAB65,TAB66)

 

 

 

 

(5)Disconnect the ourdoor electronic control P.C. board

 

 

 

 

connectors CN791, CN792, CN793, CN794, CN662,

 

 

 

 

CN722, and CN661. Disconnect the noise filter P.C. board

 

 

 

 

connectors CN913.

 

 

 

 

(6)Remove the four screws of the electrical parts, and remove

 

 

 

 

them.

 

 

Service panel

(7)Remove the propeller.

Front

(8)Remove the screws of the separator, and remove it.

panel

(9)Detach the brazed joints of the compressor suction and dis-

 

 

 

 

charge pipes. (See Photo 3.)

 

 

 

 

(10)Remove the three compressor nuts and remove the com-

Photo 2

pressor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control P.C.board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electrical parts

Sepatator

Terminal

Photo 3

Discharge pipe brazed part

Suction pipe braxed part

37

Image 37
Contents MXZ-32SV E1 MXZ-32SV E2 ContentsPart Names and Functions Technical ChangesOutdoor Unit Outdoor Unit Indoor / Outdoor Correspondence TableMXZ-32SV E1 , MXZ-32SV E2 Indoor Units Combination09+09+12 15.05 13.80 9.0 07+09 10.35 09+09+12 14.04 12.87 MXZ-32SV E1 , MXZ-32SV E2 SpecificationCooling DB35 WB24 Test conditionsHeating DB 0dB =Unit mm Outlines and DimensionsModels MXZ-32SV- E1 Wiring DiagramUnitmm Refrigerant System DiagramCWB Capacity and the Input CurvesCDB Outdoor UNITMXZ-32SV Capacity and input correction by inverter output frequencyHeat operation Outdoor low pressure and outdoor unit currentCurrent 10 15 20 10 15 20 Inverter Multi System Control Microprocessor ControlSSR61 LEV control Cool DRY Heat DRY Cool Operational frequency rangeHeat defrosting control Discharge temperature protection controlHigh or low pressure protection Outdoor fan control Refrigerant recovery control on heatingRelation between main sensor and actuator Instruction of troubleshooting TroubleshootingBefore troubleshooting, check the following Lead wiring Housing point Troubleshooting procedureLEV Troubleshooting check tableCheck the contact of LEV board connec Trouble criterion of main parts Outdoor unit does not operate. LED display Outdoor unit does not operate. LED display display OFFWhen cooling operation does not work. Start When heating operation does not work. StartCheck of LEV Check of thermistor Check of HPS Electronic control P.C.board Test Point Diagram and Voltage MXZ-32SV E1 , MXZ-32SV E2Outdoor FAN 220V-240V AC Reversing Valve 220V-240V AC Noise filter P.C.board MXZ-32SV E1MXZ-32SV E2 Outdoor FAN 230V AC Reversing Valve 230V ACRelay P.C.board MXZ-32SV E1 MXZ-32SV E2 M P.C.board MXZ-32SV E1 MXZ-32SV E2Outdoor Unit Operating Procedure Photos Disassembly InstructionsMXZ-32SV Removing the compressor PhotoRemoving the 4-way valve Photo Removing the fan motorRemoving the linear expansion valve Photo Removing the reactor Operating Procedure PhotosOutdoor Unit Functional Parts MXZ-32SV E1 Parts ListMXZ-32SV E117 16 15 MXZ-32SV E2 Outdoor Unit Structural PartsSymbol Qty / unit Parts No Parts Name Wiring Remarks Accessory Parts MXZ-32SV E1 MXZ-32SV E2Outlet guide Different-diameter pipe