Mitsubishi Electronics MXZ-32SV service manual Cool DRY Heat

Page 21

<Correction>

COOL

DRY

HEAT

1Suction super heat

(MIN gas pipe temperature thermistor - Evaporation temperature thermistor)

2 Each correction w 1

-

 

 

 

(Each gas pipe temperature thermistor - Evaporation temperature thermistor)

(Main pipe temperature thermistor - sub pipe temperature thermistor)

3 Discharge temperature

w 2 w 2

w1 Perform this, when number of operation units is 2units or more

w2 When the correction opening of suction super heat is 0, correct the LEV opening by dischaege temperature.

(1)LEV opening correction by suction super heat (COOL, DRY)

(Suction super heat) = (Minimum gas pipe temperature) - (Evaporation temperature) When COOL and DRY , correct the LEV openings corrected from the table below

(2) Separate correction (COOL,DRY)

(When number of operation unit is 2 units or more)

(a)Correction by the separate super heat

Correct the LEV separately by temperature difference between each gas pipe temperature thermistor and evaporator temperature thermistor.

1Calculate each super heat of the unit from the expression below;

(Super heat) = (Gas pipe temperature thermistor) - (Evaporation temperature thermistor)

2Select a minimum super heat from among them.

3Correct an each LEV is corrected opening is corrected by difference between each super heat and minimum super heat.

21

Image 21
Contents MXZ-32SV E1 MXZ-32SV E2 ContentsTechnical Changes Part Names and FunctionsOutdoor Unit Outdoor Unit Indoor / Outdoor Correspondence TableMXZ-32SV E1 , MXZ-32SV E2 Indoor Units Combination09+09+12 15.05 13.80 9.0 07+09 10.35 09+09+12 14.04 12.87 MXZ-32SV E1 , MXZ-32SV E2 SpecificationCooling DB35 WB24 Test conditionsHeating DB 0dB =Unit mm Outlines and DimensionsModels MXZ-32SV- E1 Wiring DiagramUnitmm Refrigerant System DiagramCapacity and the Input Curves CWBCDB Outdoor UNITMXZ-32SV Capacity and input correction by inverter output frequencyHeat operation Outdoor low pressure and outdoor unit currentCurrent 10 15 20 10 15 20 Microprocessor Control Inverter Multi System ControlSSR61 LEV control Cool DRY Heat DRY Cool Operational frequency rangeDischarge temperature protection control Heat defrosting controlHigh or low pressure protection Refrigerant recovery control on heating Outdoor fan controlRelation between main sensor and actuator Instruction of troubleshooting TroubleshootingBefore troubleshooting, check the following Lead wiring Housing point Troubleshooting procedureLEV Troubleshooting check tableCheck the contact of LEV board connec Trouble criterion of main parts Outdoor unit does not operate. LED display Outdoor unit does not operate. LED display display OFFWhen cooling operation does not work. Start When heating operation does not work. StartCheck of LEV Check of thermistor Check of HPS Electronic control P.C.board Test Point Diagram and Voltage MXZ-32SV E1 , MXZ-32SV E2Outdoor FAN 220V-240V AC Reversing Valve 220V-240V AC Noise filter P.C.board MXZ-32SV E1MXZ-32SV E2 Outdoor FAN 230V AC Reversing Valve 230V ACRelay P.C.board MXZ-32SV E1 MXZ-32SV E2 M P.C.board MXZ-32SV E1 MXZ-32SV E2Outdoor Unit Operating Procedure Photos Disassembly InstructionsMXZ-32SV Removing the compressor PhotoRemoving the fan motor Removing the 4-way valve PhotoRemoving the linear expansion valve Photo Removing the reactor Operating Procedure PhotosOutdoor Unit Functional Parts MXZ-32SV E1 Parts ListMXZ-32SV E117 16 15 MXZ-32SV E2 Outdoor Unit Structural PartsSymbol Qty / unit Parts No Parts Name Wiring Remarks Accessory Parts MXZ-32SV E1 MXZ-32SV E2Outlet guide Different-diameter pipe