• When thermistor is abnormal. (When the LED display is a table below.)

F Check of thermistor
Start |
| |
| Abnormal | |
|
| |
Disconnect the connector in the electronic control P. C. board (see below table), and | ||
measure the resistance of thermistor to check whether the thermistor is normal or not. |
| |
| Normal |
|
|
|
Replace the thermistor
Reconnect the connector (CN661, CN662 and CN663) and disconnect the lead wire leading to the compressor. Turn on power supply to the indoor and outdoor unit. Three minutes later EMERGENCY OPERATION starts.
Does thermistor operate 10 minutes or more though the No thermistor abnormality is not displayed?
Yes
Normal
Replace the electronic control P. C. board.
Thermistor | Symbol | Connector, Pin No. |
Defrost thermistor | RT62 | Between CN661 pin1 and pin2 |
Discharge temperature thermistor | RT61 | Between CN661 pin3 and pin4 |
Evaporation temperature thermistor | RT63 | Between CN661 pin5 and pin6 |
Gas pipe temperature thermistor (Unit A) | RT66 | Between CN662 pin1 and pin2 |
Gas pipe temperature thermistor (Unit B) | RT67 | Between CN662 pin3 and pin4 |
Gas pipe temperature thermistor (Unit C) | RT68 | Between CN662 pin5 and pin6 |
Gas pipe temperature thermistor (Unit D) | RT69 | Between CN662 pin7 and pin8 |
Fin temperature thermistor | RT65 | Between CN663 pin1 and pin2 |
• Fan motor does not operate. Or, fan motor stops at once’ after fan motor operates.

G Check of fan motor
Start
Check the connection of connector (CN851, CN852) in the fan motor relay connector and electronic control P. C. board at the noise filter P. C. board and connector (CN901, CN902) in the noise filter board.
Disconnect the fan motor connector, and measure the resistance of the | Abnormal |
| |||
Replace the fan motor | |||||
fan motor winding to check the winding characteristic. |
|
| |||
|
|
| |||
| Normal |
|
|
| |
|
|
|
|
1.Disconnect the lead wire leading to the compressor. Turn on power supply to the indoor and outdoor unit. Three minutes later, EMERGENCY OPERATION starts.
2.Check the voltage between pin 2 and pin 3, pin 2 and pin 5, pin 2 and pin 6 at the fan motor connector.
Is there voltage of 220V AC - 240V AC? No
Yes
1. | Turn off power supply of the indoor and outdoor unit, and disconnect the connector |
|
|
| |
No | Replace the electronic | ||||
| (CN851, CN852). | ||||
|
|
| control P. C. board | ||
2. | Is the voltage 0V, when the voltage between CN852 pin1 (+) and CN851 pin1 |
|
| ||
|
|
|
pin2
| Yes |
| |
Is there voltage of 12V DC between CN852 pin1 (+) and pin3 | No | ||
turns on the indoor unit and EMERGENCY OPERATION starts in three minutes. |
| ||
| Yes |
| |
|
| ||
|
| ||
Replace the noise filter P. C. board |
|
|
32