11-6.Refrigerant recovery control on heating

<Control status>

The control performs when the following status are satisfied everything;

When there is 1 unit or more not operating indoor unit on heat operation. (Excluding thermo OFF)

When discharge temperature becomes 107; or more.

When it passed 60 minutes or more since the operation has started or the last refrigerant recovery has controlled.

<Control details>

LEV opening, which adjusts to not operating indoor unit, is considered to be 80 pulse.

<Control finish status>

The control finishes either as follows. However, the LEV opening is considered to be 59 pulse.

When it passed 60 seconds since the control has started.

When the discharge temperature is 90; or less.

11-7.Outdoor fan control

Fan speed is switched according to a number of operating indoor unit and the compressor frequency.

Note

When operation, fan speed of Hi/ Low mode changes to VHi/ Hi mode by promoting those fan speeds respectively by 1 step after defrosting is operated. This control is cleared, when the compressor off.

When overheat protection of P.C. board temperature or fin temperature operates, the outdoor fan speed is fixed to VHi mode regardless of compressor frequency. Also, when the overheat protection is cleared, the fan speed is

back to normal

When the indoor coil thermistor is 57; or more on HEAT operation, fan speed is fixed to Low notch . Or, the indoor coil thermistor is 45; or less on HEAT operation, fan speed is back to normal.

11-8.Relation between main sensor and actuator

Relation between main sensor and actuator.

24

Image 24
Contents Contents MXZ-32SV E1 MXZ-32SV E2Technical Changes Part Names and FunctionsOutdoor Unit Indoor / Outdoor Correspondence Table Outdoor UnitIndoor Units Combination MXZ-32SV E1 , MXZ-32SV E209+09+12 15.05 13.80 9.0 07+09 10.35 09+09+12 14.04 12.87 Specification MXZ-32SV E1 , MXZ-32SV E2Test conditions Cooling DB35 WB24Heating DB 0dB =Outlines and Dimensions Unit mmWiring Diagram Models MXZ-32SV- E1Refrigerant System Diagram UnitmmCapacity and the Input Curves CWBCDB Capacity and input correction by inverter output frequency Outdoor UNITMXZ-32SVOutdoor low pressure and outdoor unit current Heat operationCurrent 10 15 20 10 15 20 Microprocessor Control Inverter Multi System ControlSSR61 LEV control Cool DRY Heat Operational frequency range DRY CoolDischarge temperature protection control Heat defrosting controlHigh or low pressure protection Refrigerant recovery control on heating Outdoor fan controlRelation between main sensor and actuator Troubleshooting Instruction of troubleshootingBefore troubleshooting, check the following Lead wiring Housing point Troubleshooting procedureTroubleshooting check table LEVCheck the contact of LEV board connec Trouble criterion of main parts Outdoor unit does not operate. LED display display OFF Outdoor unit does not operate. LED displayWhen heating operation does not work. Start When cooling operation does not work. StartCheck of LEV Check of thermistor Check of HPS Test Point Diagram and Voltage MXZ-32SV E1 , MXZ-32SV E2 Electronic control P.C.boardNoise filter P.C.board MXZ-32SV E1 Outdoor FAN 220V-240V AC Reversing Valve 220V-240V ACMXZ-32SV E2 Outdoor FAN 230V AC Reversing Valve 230V ACM P.C.board MXZ-32SV E1 MXZ-32SV E2 Relay P.C.board MXZ-32SV E1 MXZ-32SV E2Disassembly Instructions Outdoor Unit Operating Procedure PhotosMXZ-32SV Removing the compressor PhotoRemoving the fan motor Removing the 4-way valve PhotoRemoving the linear expansion valve Photo Operating Procedure Photos Removing the reactorParts List Outdoor Unit Functional Parts MXZ-32SV E1Outdoor Unit Structural Parts MXZ-32SV E117 16 15 MXZ-32SV E2Accessory Parts MXZ-32SV E1 MXZ-32SV E2 Symbol Qty / unit Parts No Parts Name Wiring RemarksDifferent-diameter pipe Outlet guide