10-3-4.Outdoor low pressure and outdoor unit current

1. 07-class unit in single operation

NOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system). The converted score against the traditional unit system can be gotten according to the formula below.

1(MPa • G) =10.2(kgf/f • G)

(1) COOL operation

1Both indoor and outdoor units are under the same temperature/humidity condition.

Dry-bulb temperature(°C)

Relative humidity(%)

20

50

25

60

30

70

2Air flow speed : HI

3Inverter output frequency : 33Hz

<How to work fixed-frequency operation>

1.Set emergency switch to COOL or HEAT.The switch is locat- ed on indoor unit.

2.Press emergency run ON/OFF button. 3.Compressor starts running at rated frequency.

4.Indoor fan runs at HI speed and continues for 30 minutes. 5.To cancel this operation,press emergency run ON/OFF button

or any button on remote controller.

(kgf/F•Gauge) (MPa•Gauge)

Outdoor low pressure

8

7

6

5

4

3

2

0.8

 

 

 

0.7

 

 

 

0.6

 

33Hz

 

 

 

 

0.5

 

 

 

0.4

 

 

 

0.3

 

 

 

0.2

 

35

(;)

15

25

20

30

(%)

Ambient temperature(:)/ Ambient humidity(%)

Outdoor unit current (A)

9

 

 

 

8

 

 

 

7

 

 

 

6

 

 

 

 

 

33Hz

 

5

 

 

 

4

 

 

 

3

 

 

(;)

15 20

25

30 35

 

 

 

(%)

Ambient temperature(:)/ Ambient humidity(%)

(2)HEAT operation

Indoor DB(°C) 20.0

WB(°C) 14.5

Outdoor

DB(°C)

2

7

15

20.0

WB(°C)

1

6

12

14.5

Set air flow to Hi speed.

Inverter output frequency is 45Hz.

Outdoor unit current (A)

10

9

8

7

6

5

4

45Hz

0

5

10

15

20

25

Ambient temperature(:)

15

Image 15
Contents MXZ-32SV E1 MXZ-32SV E2 ContentsTechnical Changes Part Names and FunctionsOutdoor Unit Outdoor Unit Indoor / Outdoor Correspondence TableMXZ-32SV E1 , MXZ-32SV E2 Indoor Units Combination09+09+12 15.05 13.80 9.0 07+09 10.35 09+09+12 14.04 12.87 MXZ-32SV E1 , MXZ-32SV E2 Specification0dB = Test conditionsCooling DB35 WB24 Heating DBUnit mm Outlines and DimensionsModels MXZ-32SV- E1 Wiring DiagramUnitmm Refrigerant System DiagramCapacity and the Input Curves CWBCDB Outdoor UNITMXZ-32SV Capacity and input correction by inverter output frequencyHeat operation Outdoor low pressure and outdoor unit currentCurrent 10 15 20 10 15 20 Microprocessor Control Inverter Multi System ControlSSR61 LEV control Cool DRY Heat DRY Cool Operational frequency rangeDischarge temperature protection control Heat defrosting controlHigh or low pressure protection Refrigerant recovery control on heating Outdoor fan controlRelation between main sensor and actuator Lead wiring Housing point Troubleshooting procedure TroubleshootingInstruction of troubleshooting Before troubleshooting, check the followingLEV Troubleshooting check tableCheck the contact of LEV board connec Trouble criterion of main parts Outdoor unit does not operate. LED display Outdoor unit does not operate. LED display display OFFWhen cooling operation does not work. Start When heating operation does not work. StartCheck of LEV Check of thermistor Check of HPS Electronic control P.C.board Test Point Diagram and Voltage MXZ-32SV E1 , MXZ-32SV E2Outdoor FAN 230V AC Reversing Valve 230V AC Noise filter P.C.board MXZ-32SV E1Outdoor FAN 220V-240V AC Reversing Valve 220V-240V AC MXZ-32SV E2Relay P.C.board MXZ-32SV E1 MXZ-32SV E2 M P.C.board MXZ-32SV E1 MXZ-32SV E2Removing the compressor Photo Disassembly InstructionsOutdoor Unit Operating Procedure Photos MXZ-32SVRemoving the fan motor Removing the 4-way valve PhotoRemoving the linear expansion valve Photo Removing the reactor Operating Procedure PhotosOutdoor Unit Functional Parts MXZ-32SV E1 Parts ListMXZ-32SV E117 16 15 MXZ-32SV E2 Outdoor Unit Structural PartsSymbol Qty / unit Parts No Parts Name Wiring Remarks Accessory Parts MXZ-32SV E1 MXZ-32SV E2Outlet guide Different-diameter pipe