Mitsubishi Electronics MXZ-32SV Heat defrosting control, High or low pressure protection

Page 23

11-3.Heat defrosting control

(1) Conditions to enter defrosting mode

1. When temperature of defrosting thermistor is -3;or less.

2.When specified non-defrosting time, is counted in the control p.c.board is satisfied. (Total time of compressor operating)

Going to defrosting mode at both condition of 1 and 2.

(2) Defrosting operation

1. Compressor stops for 50 seconds, Indoor fan is off, Defrosting lamp lights

2.4-way valve reverses flow, Compressor operates by the frequency in heat defrosting control. 3. After compressor stops for 35 seconds, 4-way valve reverses flow, then defrosting finishes.

(3) Conditions to finish defrosting mode

1. When the defrosting thermistor temperature is 8; or more.

2. When it has spent 10 minutes for defrosting. Defrosting finishes at condition of 1 or 2.

11-4.High or low pressure protection

(1) High pressure protection control on heat mode

Temperature of the main pipe temp. thermistor in the indoor unit controls the operation frequency.

When temperature of the main pipe temp. thermistor is approx. 49;, the operation frequency is set at the current level. When temperature of the main pipe temp. thermistor is approx. 52; the protection control decreases the frequency at the speed of 3Hz a minutes.

When temperature of the main pipe temp. thermistor is approx. 57; the protection decreases the frequency at the speed of 4Hz a minute and changes the outdoor fan to Low.

Note: Temperature of the pipe temp. thermistor is different depending on the indoor unit. Temperature of the pipe temp. thermistor is 45; or less, the protection control is Released.

(2) High pressure protection control by high pressure switch (H.P.S) High-pressure switch controls the operation frequency and outdoor fan motor. <Control status>

When high-pressure switch is ON.

(When discharge pipe pressure is 2.75 MPa or more.) <Control details>

(a)When cooling or drying

The protection control decreases the compressor frequency at the speed of 10Hz a minute.

(The compressor operates continuously in min. frequency according to a command to decrease more than the min. level.)

(b)When heating

The protection control decreases the compressor frequency at the speed of 10Hz a minute.

The protection control changes the outdoor fan to Low. <Release status>

When high-pressure switch is OFF. (When discharge pipe pressure is 2.35 MPa or more.) Or, the compressor stops.

11-5.Discharge temperature protection control

This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge temp. thermistor.

(1) Compressor ON/OFF

When temperature of the discharge temp. thermistor exceeds 116;, the control stops the compressor. When temperature of the discharge temp. thermistor is 80; or less, the controls starts the compressor.

(2) Compressor operation frequency

When temperature of the discharge temp. thermistor is expected to be higher than 116;, the control decreases 12Hz from the current frequency.

When temperature of the discharge temp. thermistor is expected to be higher than 111; and less than 116;, the control decreases 6Hz from the current frequency.

When temperature of the discharge temp. thermistor is expected to be higher than 104; and less than 111;, the control is set at the current frequency.

23

Image 23
Contents MXZ-32SV E1 MXZ-32SV E2 ContentsOutdoor Unit Technical ChangesPart Names and Functions Outdoor Unit Indoor / Outdoor Correspondence TableMXZ-32SV E1 , MXZ-32SV E2 Indoor Units Combination09+09+12 15.05 13.80 9.0 07+09 10.35 09+09+12 14.04 12.87 MXZ-32SV E1 , MXZ-32SV E2 Specification0dB = Test conditionsCooling DB35 WB24 Heating DBUnit mm Outlines and DimensionsModels MXZ-32SV- E1 Wiring DiagramUnitmm Refrigerant System DiagramCDB Capacity and the Input CurvesCWB Outdoor UNITMXZ-32SV Capacity and input correction by inverter output frequencyHeat operation Outdoor low pressure and outdoor unit currentCurrent 10 15 20 10 15 20 SSR61 Microprocessor ControlInverter Multi System Control LEV control Cool DRY Heat DRY Cool Operational frequency rangeHigh or low pressure protection Discharge temperature protection controlHeat defrosting control Relation between main sensor and actuator Refrigerant recovery control on heatingOutdoor fan control Lead wiring Housing point Troubleshooting procedure TroubleshootingInstruction of troubleshooting Before troubleshooting, check the followingLEV Troubleshooting check tableCheck the contact of LEV board connec Trouble criterion of main parts Outdoor unit does not operate. LED display Outdoor unit does not operate. LED display display OFFWhen cooling operation does not work. Start When heating operation does not work. StartCheck of LEV Check of thermistor Check of HPS Electronic control P.C.board Test Point Diagram and Voltage MXZ-32SV E1 , MXZ-32SV E2Outdoor FAN 230V AC Reversing Valve 230V AC Noise filter P.C.board MXZ-32SV E1Outdoor FAN 220V-240V AC Reversing Valve 220V-240V AC MXZ-32SV E2Relay P.C.board MXZ-32SV E1 MXZ-32SV E2 M P.C.board MXZ-32SV E1 MXZ-32SV E2Removing the compressor Photo Disassembly InstructionsOutdoor Unit Operating Procedure Photos MXZ-32SVRemoving the linear expansion valve Photo Removing the fan motorRemoving the 4-way valve Photo Removing the reactor Operating Procedure PhotosOutdoor Unit Functional Parts MXZ-32SV E1 Parts ListMXZ-32SV E117 16 15 MXZ-32SV E2 Outdoor Unit Structural PartsSymbol Qty / unit Parts No Parts Name Wiring Remarks Accessory Parts MXZ-32SV E1 MXZ-32SV E2Outlet guide Different-diameter pipe