Mitsubishi Electronics MXZ-32SV service manual Check of HPS

Page 33

• When the operation frequency does not go up from lowest frequency.

H Check of HPS

Start

1.Disconnect the connector CN722 in the electronic control P. C. board.

2.Check the resistance of HPS after 1 minutes have passed since the outdoor unit power supply was turnd off.

Check the resistance between

Infinity

each terminal?

Replace HPS (63H1).

 

0"

 

Return CN722 to former.

Turn on power supply to the indoor and outdoor unit. 3 minutes lator, EMERGENCY OPERATION starts.

Yes

Is HPS protection displayed

No

immediately after compressor Replace the electronic control P. C. board. starts.

Yes

Normal

I The other cases

In the case that the indoor fan and outdoor fan operate but the compressor does not operate, it causes that the high pressure switch can be operated once.

First of all, check the high pressure switch can be shorted, turn OFF the power and turn ON again 1 minute later. Indoor unit dose not operate. (difference modes)

When you try to run two indoor unit simultaneously, one for cooling and the other for heating, the unit which transmits signal to the outdoor units earlier decides the operation mode. The other unit indicates as shown in the figure below.

When the above situation occurs, set all the indoor units to the same mode, turn OFF the indoor units, and then turn them back ON.

Though the top of the indoor unit sometimes gets warm, this does not mean malfunction. The reason is that the refrigerant gas continuously flows into the indoor unit even while it is not operating.

OPERATION INDICATOR

Lighting

Flashing

33

Image 33
Contents MXZ-32SV E1 MXZ-32SV E2 ContentsTechnical Changes Part Names and FunctionsOutdoor Unit Outdoor Unit Indoor / Outdoor Correspondence TableMXZ-32SV E1 , MXZ-32SV E2 Indoor Units Combination09+09+12 15.05 13.80 9.0 07+09 10.35 09+09+12 14.04 12.87 MXZ-32SV E1 , MXZ-32SV E2 SpecificationCooling DB35 WB24 Test conditionsHeating DB 0dB =Unit mm Outlines and DimensionsModels MXZ-32SV- E1 Wiring DiagramUnitmm Refrigerant System DiagramCapacity and the Input Curves CWBCDB Outdoor UNITMXZ-32SV Capacity and input correction by inverter output frequencyHeat operation Outdoor low pressure and outdoor unit currentCurrent 10 15 20 10 15 20 Microprocessor Control Inverter Multi System ControlSSR61 LEV control Cool DRY Heat DRY Cool Operational frequency rangeDischarge temperature protection control Heat defrosting controlHigh or low pressure protection Refrigerant recovery control on heating Outdoor fan controlRelation between main sensor and actuator Instruction of troubleshooting TroubleshootingBefore troubleshooting, check the following Lead wiring Housing point Troubleshooting procedureLEV Troubleshooting check tableCheck the contact of LEV board connec Trouble criterion of main parts Outdoor unit does not operate. LED display Outdoor unit does not operate. LED display display OFFWhen cooling operation does not work. Start When heating operation does not work. StartCheck of LEV Check of thermistor Check of HPS Electronic control P.C.board Test Point Diagram and Voltage MXZ-32SV E1 , MXZ-32SV E2Outdoor FAN 220V-240V AC Reversing Valve 220V-240V AC Noise filter P.C.board MXZ-32SV E1MXZ-32SV E2 Outdoor FAN 230V AC Reversing Valve 230V ACRelay P.C.board MXZ-32SV E1 MXZ-32SV E2 M P.C.board MXZ-32SV E1 MXZ-32SV E2Outdoor Unit Operating Procedure Photos Disassembly InstructionsMXZ-32SV Removing the compressor PhotoRemoving the fan motor Removing the 4-way valve PhotoRemoving the linear expansion valve Photo Removing the reactor Operating Procedure PhotosOutdoor Unit Functional Parts MXZ-32SV E1 Parts ListMXZ-32SV E117 16 15 MXZ-32SV E2 Outdoor Unit Structural PartsSymbol Qty / unit Parts No Parts Name Wiring Remarks Accessory Parts MXZ-32SV E1 MXZ-32SV E2Outlet guide Different-diameter pipe