Venting methods
Vertical venting | Horizontal venting |
This canopy range hood is factory set for vertical venting. For rear vent applications, the blower must be turned inside the range hood so that the blower vents to the rear as indicated. The blower is turned by removing two screws on each side of the blower, rotating the blower with the exhaust opening facing the rear and then replacing the screws. The exhaust cover(s) must be moved to block the unused opening(s). The blower must be converted before installing the range hood.
Vent system needed for installation is not included. The 36" (91.4 cm) and 42" (106.7 cm) models have one exhaust opening.
The 48" (121.9 cm) model has two
roof cap
(8.3 cm x 25 cm) |
vertical venting |
(roof or wall) |
(8.3 cm x 25 cm) horizontal venting
wall cap
used with Chimney Extension Kit No. 8284754.)
Vent system can terminate either through the roof or wall.
The vent system length should not exceed the lengths shown in the chart.
Vent size | Maximum length |
35 ft. (10.7 m) | |
7" (17.8 cm) round | 40 ft. (12.2 m) |
8" (20.3 cm) round | 50 ft. (15.2 m) |
9" (22.9 cm) round | 60 ft. (18.3 m) |
10" (25.4 cm) round | 60 ft. (18.3 m) |
Calculating the vent system length
To calculate the length of the system you need, add the equivalent feet (meters) for each vent piece used in the system.
Vent Piece | 7" (17.8 cm), 8" (20.3 cm), | |
| Rectangular | 9" (22.9 cm), 10" (25.4 cm) |
|
| Round |
45° elbow | 7.0 feet | 2.5 feet |
| (2.1 m) | (0.8 m) |
90° elbow | 5.0 feet | 5.0 feet |
| (1.5 m) | (1.5 m) |
90° flat elbow | 12.0 feet |
|
| (3.7 m) |
|
transition to round | 5.0 feet |
|
| (1.5 m) |
|
wall cap | 0.0 feet |
|
| (0.0 m) |
|
Example for
(8.3 cm x 25 cm) vent system
wall | |
(8.3 cm x 25 cm) | cap |
elbow | 6 ft. (1.8 m) |
|
2ft.
(0.6 m)
Maximum length | = 35 ft. (10.7 m) | ||
1 — 90° elbow | = | 5 ft. | (1.5 m) |
8 ft. (2.4 m) straight | = | 8 ft. | (2.4 m) |
1 — wall cap | = | 0 ft. | (0 m) |
Length of |
|
|
|
|
|
| |
(8.3 cm x 25 cm) |
|
|
|
system | = 13 ft. | (4 m) |
Note: Flexible vent is Not recommended.
Flexible vent creates back pressure and air turbulence that greatly reduces performance.