Honeywell STR12D warranty Options

Page 19

Options

34-ST-03-64 Page 19

Ordering Information

Mounting Bracket

The angle mounting bracket is available in either zinc-plated carbon steel or stainless steel and is suitable for horizontal or vertical mounting on a two inch (50 millimeter) pipe, as well as wall mounting. An optional flat mounting bracket is also available in carbon steel for two inch (50 millimeter) pipe mounting.

Indicating Meter

(Options ME and SM)

Two integral meter options are available. An analog meter (option ME) is available with a 0 to 100% linear scale. The Smart Meter (option SM) provides an LCD display for both analog and digital output and can be configured to display pressure in pre-selected engineering units.

HART® Protocol Compatibility (Options HC and H6)

Optional electronics modules for the ST 3000 provides HART Protocol compatibility in either HART 5.x or 6.x formats. Transmitters with a HART Option are compatible with any HART enabled system that provides 5.x or 6.x format support.

FOUNDATION Fieldbus

(Option FF)

Equips transmitter with FF protocol for use in 31.25 kbit/s FF networks. See document 34-ST- 03-72 for additional information on ST 3000 Fieldbus transmitters.

SIL2/SIL3 Certification (Option SL)

This ST 3000 product is available for use with safety systems. With the SL option, we are fully certified to SIL 2 capability for single transmitters and SIL 3 capability for multiple transmitter use through TÜV Nord Sys Tec GmbH & Co. KG. We are in compliance with the following SIL standards:

IEC 61508-1: 1998;

IEC 61508-2: 2000;

IEC 61508-3: 1998

NAMUR NE43 Compliance (Option NE)

This option provides software the meets the NAMUR NE43 requirements for failsafe software. Transmitter failure information is generated when the measuring information is no longer valid. Transmitter failure values are:

3.6 mA and ≥ 21.0 mA. The normal ST 3000 ranges are ≤ 3.8 mA and ≥ 20.5 mA.

Lightning Protection

(Option LP)

A terminal block with circuitry that protects the transmitter from transient surges induced by nearby lightning strikes is available.

Indicator Configuration (Option CI)

Provides custom configuration of Smart Meters

Tagging (Option TG)

Up to 30 characters can be added on the stainless steel nameplate mounted on the transmitter’s electronics housing at no extra cost. Note that a separate nameplate on the meter body contains the serial number and body-related data. A stainless steel wired on tag with additional data of up to 4 lines of 28 characters is also available. The number of characters for tagging includes spaces.

Transmitter Configuration (Option TC)

The factory can configure the transmitter linear/square root extraction, damping time, LRV, URV and mode (analog/digital) and enter an ID tag of up to eight characters and scratchpad information as specified.

Custom Calibration and ID in Memory (Option CC)

The factory can calibrate any range within the scope of the transmitter’s range and enter an ID tag of up to eight characters in the transmitter’s memory.

Contact your nearest Honeywell sales office, or

In the U.S.:

Honeywell

Industrial Automation & Control

16404 North Black Canyon Hwy.

Phoenix, AZ 85053

1-800-288-7491

In Canada:

The Honeywell Centre

155 Gordon Baker Rd.

North York, Ontario M2H 3N7

1-800-461-0013

In Latin America:

Honeywell Inc.

480 Sawgrass Corporate Parkway,

Suite 200

Sunrise, FL 33325

(954) 845-2600

In Europe and Africa: Honeywell S. A.

Avenue du Bourget 1

1140 Brussels, Belgium

In Eastern Europe: Honeywell Praha, s.r.o. Budejovicka 1 140 21 Prague 4,

Czech Republic

In the Middle East:

Honeywell Middle East Ltd.

Khalifa Street,

Sheikh Faisal Building

Abu Dhabi, U. A. E.

In Asia:

Honeywell Asia Pacific Inc.

Honeywell Building,

17 Changi Business Park Central 1

Singapore 486073

Republic of Singapore

In the Pacific:

Honeywell Pty Ltd.

5 Thomas Holt Drive

North Ryde NSW Australia 2113

(61 2) 9353 7000

In Japan:

Honeywell K.K.

14-6 Shibaura 1-chrome

Minato-ku, Tokyo, Japan 105-0023

Or, visit Honeywell on the World Wide Web at: http://www.honeywell.com

Specifications are subject to change

without notice

Image 19
Contents Introduction Guide34-ST-03-64 Description of Diaphragm SealsStainless Steel Nipples are available Description FeaturesSpecifications Operating Conditions All Models Parameter Description Parameter Bar Minimum Span Psig Turndown Ratio Upper Range Limit Psig±0.10 + Or ±0.10 + Performance Under Rated Conditions General for all Models Physical and Approval Bodies 34-ST-03-64 Parameter Description 34-ST-03-64 Supply voltage/loop resistance chart Transmitter at datum Transmitter above datumTransmitter below datum Density, direct acting instrument configuration DP/I Remote Seal With HorizontalPipe Mount LGP/I Remote SealWith Vertical Pipe With Vertical Pipe MountAP/I Remote Seal with Vertical Pipe Mount LGP/I Remote SealOptions Instructions Table II Seals Table II Seals Two 1/2 with plastic plugs Ansi Class 150/300/600 GFA Two 1/4 with plastic plugs PF0 QG0 Wetted Material Table II SealsMD0 NE0Transmitter Mounting Brackets Options Table III Options Warranty OptionsCont’d See in Specification 21a Flush Flanged Seal Dimensions and DrawingsDimensions and Drawings, Dimensions and Drawings, Dimensions and Drawings, Dimensions and Drawings, This page Intentionally Blank