Performance Under Rated Conditions * - Model STR12D (0-10 to 0-400 inH2O)

Parameter

 

 

 

 

 

 

 

 

 

Description

 

 

Upper Range Limit **

inH2O

400 (39.2°F/4°C is standard reference temperature for inH2O range.)

 

mbar

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Span

inH2O

10 Note: Recommended minimum span in square root mode is 20 inH2O (50 mbar).

 

mbar

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turndown Ratio

 

40 to 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zero Elevation and Suppression

No limit except minimum span within ±100% URL.

 

 

 

 

 

 

Accuracy (Reference – Includes

In Analog Mode: ±0.2% of calibrated span or upper range value (URV), whichever is

combined effects of linearity,

greater, terminal based.

 

 

 

 

 

 

 

 

 

 

 

hysteresis, and repeatability)

For URV below reference point (50 inH2O), accuracy equals:

 

 

Accuracy includes residual error

±0.1 + 0.1

50 inH2O

or ±0.1 + 0.1

 

 

125 mbar

 

in % of span

after averaging successive

 

 

 

 

 

 

( span mbar)

readings.

 

span inH2O

 

 

 

 

 

For FOUNDATION Fieldbus use

In Digital Mode: ±0.175% of calibrated span or upper range value (URV), whichever is

Digital Mode specifications. For

greater, terminal based.

 

 

 

 

 

 

 

 

 

 

 

HART use Analog Mode

 

For URV below reference point (50 inH2O), accuracy equals:

specifications.

 

 

 

 

50 inH2O

 

 

 

 

 

 

125 mbar

 

 

 

 

 

 

 

 

 

 

 

 

 

±0.075 + 0.10

 

 

or ±0.075 + 0.10 (

 

) in % of span

 

 

span inH2O

span mbar

Combined Zero and Span

In Analog Mode: ±1.2% of span.

 

 

 

 

 

 

 

 

Temperature Effect per 28°C

For URV below reference point (200 inH2O), effect equals:

(50°F) ***

 

 

 

 

200 in H2O

 

 

 

500 mbar

 

 

±0.2 + 1.0

 

 

 

 

 

or ±0.2 + 1.0

 

 

 

In % span

 

 

 

span in H2O

 

span mbar

 

 

 

 

 

 

 

 

 

 

 

 

 

In Digital Mode: ±1.175% of span.

For URV below reference point (200 inH2O), effect equals:

 

200 in H2O

500 mbar

±0.175 + 1.0

 

or ±0.175 + 1.0

span mbar

In % span

span in H2O

 

 

 

 

 

*Performance specifications are based on reference conditions of 25°C (77°F), zero (0) static pressure, 10 to 55% RH, and 316L Stainless Steel barrier diaphragm.

**Transmitter URL limit or maximum seal pressure rating, whichever is lower.

***Specification applies to transmitters with 2 seals only. Apply 1.5 times factor to temperature effect for capillary lengths greater than 10 feet.

Image 6
Contents Guide IntroductionDescription of Diaphragm Seals 34-ST-03-64Stainless Steel Nipples are available Features DescriptionSpecifications Operating Conditions All Models Parameter Description Parameter Upper Range Limit Psig Bar Minimum Span Psig Turndown Ratio±0.10 + Or ±0.10 + Performance Under Rated Conditions General for all Models Physical and Approval Bodies 34-ST-03-64 Parameter Description 34-ST-03-64 Supply voltage/loop resistance chart Transmitter above datum Transmitter at datumTransmitter below datum Density, direct acting instrument configuration LGP/I Remote Seal With HorizontalPipe Mount DP/I Remote SealLGP/I Remote Seal With Vertical Pipe MountAP/I Remote Seal with Vertical Pipe Mount With Vertical PipeOptions Instructions Table II Seals Table II Seals Two 1/2 with plastic plugs Ansi Class 150/300/600 GFA Two 1/4 with plastic plugs NE0 Table II SealsMD0 PF0 QG0 Wetted MaterialTransmitter Mounting Brackets Options Warranty Options Table III OptionsCont’d See in Specification Dimensions and Drawings 21a Flush Flanged SealDimensions and Drawings, Dimensions and Drawings, Dimensions and Drawings, Dimensions and Drawings, This page Intentionally Blank