Honeywell STR12D warranty ±0.10 + Or ±0.10 +

Page 9

34-ST-03-64 Page 9

Performance Under Rated Conditions * - Model STR17G (0-100 to 0-3000 psig)

Parameter

Upper Range Limit **

psig

 

bar

 

 

Minimum Span

psig

 

bar

 

 

Turndown Ratio

 

Zero Elevation and Suppression

Accuracy (Reference – Includes combined effects of linearity, hysteresis, and repeatability)

Accuracy includes residual error after averaging successive readings.

For FOUNDATION Fieldbus use Digital Mode specifications. For HART use Analog Mode specifications.

Description

3000

210

100

7

30 to 1

No limit except minimum span from absolute zero to 100% of URL. Specifications valid over this range.

In Analog Mode: ±0.15% of calibrated span or upper range value (URV), whichever is greater.

For URV below reference point (300 psi), accuracy equals:

 

300 psi

 

21 bar

±0.10 + 0.05 (

 

) or ±0.10 + 0.05

(

 

) in % of span

span psi

span bar

In Digital Mode: ±0.125% of calibrated span or upper range value (URV), whichever is greater.

For URV below reference point (300 psi), accuracy equals:

 

300 psi

 

21 bar

±0.075 + 0.05 (

 

) or

±0.075 + 0.05 (

 

) in % of span

span psi

span bar

*Performance specifications are based on reference conditions of 25°C (77°F), zero (0) static pressure, 10 to 55% RH, and 316L Stainless Steel barrier diaphragm.

**Transmitter URL limit or maximum seal pressure rating, whichever is lower.

Image 9
Contents Introduction Guide34-ST-03-64 Description of Diaphragm SealsStainless Steel Nipples are available Description FeaturesSpecifications Operating Conditions All Models Parameter Description Parameter Bar Minimum Span Psig Turndown Ratio Upper Range Limit Psig±0.10 + Or ±0.10 + Performance Under Rated Conditions General for all Models Physical and Approval Bodies 34-ST-03-64 Parameter Description 34-ST-03-64 Supply voltage/loop resistance chart Transmitter above datum Transmitter at datumTransmitter below datum Density, direct acting instrument configuration Pipe Mount With HorizontalLGP/I Remote Seal DP/I Remote SealAP/I Remote Seal with Vertical Pipe Mount With Vertical Pipe MountLGP/I Remote Seal With Vertical PipeOptions Instructions Table II Seals Table II Seals Two 1/2 with plastic plugs Ansi Class 150/300/600 GFA Two 1/4 with plastic plugs MD0 Table II SealsNE0 PF0 QG0 Wetted MaterialTransmitter Mounting Brackets Options Table III Options Warranty OptionsCont’d See in Specification 21a Flush Flanged Seal Dimensions and DrawingsDimensions and Drawings, Dimensions and Drawings, Dimensions and Drawings, Dimensions and Drawings, This page Intentionally Blank