Carrier 50KQL-1PD manual Options and accessories, Factory-installed options

Page 6

Options and accessories

Factory-installed options

Cupronickel heat exchangers are available for higher corrosion protection for applications such as open tower, geothermal, etc. Consult the water quality guidelines for proper application and selection of this option.

Thermostat options include a unit mounted Manual Changeover (MCO) or Auto Changeover (ACO) thermo- stat. The temperature set point knob and push button switches for fan speed and cool/heat mode (MCO) selec- tion are conveniently located on the top. The thermostat senses the return-air temperature. The thermostat sends the appropriate signal to the controller for cooling or heat- ing mode of operation.

Options R and S allow connection to a remote wall- mounted thermostat. The Complete C controller requires a heat pump thermostat. The Deluxe D controller can be configured for heat pump or heat/cool thermostat.

Extended range is provided to insulate the coaxial coil to prevent condensation, and therefore potential dripping problems, in applications where the entering water temperature is below the normal operating range (less than 60 F).

Cabinet options include a locking control panel for added security. Bottom or front return with left or right hand configurations are available for ease of installation. Available with 3 or 5 in. subbase, with or without motor- ized damper.

Motorized fresh air damper with the unit-mounted thermostat. Opens when LOW or HIGH fan speed selec- tions are made from the push button switches. When STOP or FAN ONLY selections are made the spring return on the damper motor closes the damper. With remote thermostat the motorized fresh air damper opens when the fan is running.

Piping connections can be provided on either the right or left hand side of the unit, for easy installation. Orienta- tion is determined by facing the unit from the front side.

Automatic flow regulators include internally mounted

2.25or 3.0 gpm/ton automatic flow regulating valves for easier installation.

Two-way motorized control valve can be provided with a copper or cupronickel heat exchanger for applications involving open type systems or variable speed pumping. This valve will slowly open and close in conjunction with the compressor operation to shut off or turn on water to the unit. Standard two-way valve performance includes Cv of

2.9and maximum operating pressure differential (MOPD) of 125 psi.

Mute package includes high density noise suppression material on front, right, and left sides of compressor compartment and 1/2-in. fiberglass insulation on all insulated surfaces, for extra-quiet operation in the most critical applications.

Deluxe D control system provides the same functions as the Complete C while incorporating additional flexibility and functions to include:

Thermostat input capabilities — Accommodate emergency shutdown mode and night setback with override (NSB) potential. Night setback from low temperature thermostat

with 2-hour override is initiated by a momentary signal from the thermostat.

Compressor relay staging — Used with dual stage units (units with 2 compressors and 2 Deluxe D controls) or in master/slave applications.

Boilerless electric heat control system — Allows automatic changeover to electric heat at low loop water temperature.

Intelligent reversing valve operation — Minimizes reversing valve operation for extended life and quiet operation.

Thermostat type select (Y, O or Y, W) — Provides ability to work and select heat pump or heat/cool thermostats (Y, W).

Reversing valve signal select (O or B) — Provides selection for heat pump O/B thermostats.

Dehumidistat input — Provides operation of fan control for dehumidification operation.

Multiple units on one thermostat/wall sensor — Provides for communication for up to three heat pumps on one thermostat.

Boilerless changeover temperature — Provides selection of boilerless changeover temperature set point.

Accessory relays — Allow configuration for multiple appli- cations including fan and compressor cycling, digital night setback (NSB), mechanical night setback, water valve oper- ation, and outside air damper operation.

Night low limit — If the unit operation is turned OFF from either the push button switches, remote thermostat or the energy management system, it is possible that the space temperature could drop uncontrollably. The Night Low Limit feature, with Deluxe D controller, helps maintain the space temperature at a level that is the best compromise between energy consumption and a safe space tempera- ture. A thermostat located near the return air filter activates the blower and compressor operation when the space temperature falls below 50 F. When return air tem- perature is raised above 55 F the compressor and blower stop.

Override function — An Override function is available for units operating in occupied/unoccupied mode under the control of an external timeclock or an energy management system. A contact closure from the timeclock or energy management system shorts the NSB and C terminal on the Deluxe D controller signaling an unoccupied mode.

For units with the unit-mounted thermostat, pressing override switch (located under control access door) will override the unoccupied mode and allow the occupied mode of operation to continue for a period of two hours.

The units with the remote wall-mounted thermostat require a digital thermostat with the override function. In unoccupied mode an accessory relay is energized on the Deluxe D controller. The NO/NC contacts of the relay can be used as appropriate input to the digital thermostat to signal occupied/unoccupied mode. The thermostat selects cooling/heating set points based on occupied/unoccupied mode.

PremierLink™ controller is compatible with the Carrier Comfort Network (CCN) and other building automation systems (BAS). This control is designed to allow users the access and ability to change factory-defined settings thus expanding the function of the standard unit.

6

Image 6
Contents Features/Benefits Operating efficiencyTable of contents Features/Benefits Model number nomenclature Q L 0 7 S a E C 1 0 1 a aARI/ISO 13256-1 capacity ratings Physical dataOptions and accessories Factory-installed optionsField-installed accessories 50KQL Control Options TableCarrier Aquazone Thermostats Premierlink Communicating ControlDimensions 50KQL Bottom Return Cabinet Dimensions Right Hand Piping50KQL Bottom Return Cabinet Dimensions Left Hand Piping Rear View Access Damper OP Ening50KQL Front Return Cabinet Dimensions Right Hand Piping Rear Access50KQL Front Return Cabinet Dimensions Left Hand Piping Rear Access Rear View50KQL Chassis Dimensions Size 07, 09, 12, 15 Selection procedure with 50KQL12 example Page Performance data 50KQL07 Nominal Airflow 240 CFM12.3 50KQL09 Nominal Airflow 300 CFM12.2 11050KQL12 Nominal Airflow 350 CFM 50KQL15 Nominal Airflow 400 CFM 17.6 13.813.9 10.4 17.6 50KQL19 Nominal Airflow 460 CFM 15.116.7 11.5 21.1 Correction Factors Entering AIR Correction Factors AirflowGround water systems Application dataWater loop system Ground loop systemsAcoustical design Condensate drainageWater conditioning Water Quality GuidelinesOperating limits Wshp sound controlConsole units Starting conditionsTypical wiring schematics Manual Changeover with Complete C ControllerManual Changeover with Deluxe D Controller CB* NoteAutomatic Changeover with Complete C Controller High FANAutomatic Changeover with Deluxe D Controller UMTTransformer Water Valve Field Line Voltage Wiring REMOTE-MOUNTED Thermostat with Complete C ControllerREMOTE-MOUNTED Thermostat with Deluxe D Controller Premierlink Controller Applications with Complete C Control Supply Air Temperature SensorSpace Temperature Sensor Premierlink Controller Applications with Deluxe D ControlTypical piping 50KQL Piping DetailGuide specifications Console Water Source Heat PumpsGuide specifications Page Carrier Corporation Syracuse, New York