50KQL09 — NOMINAL AIRFLOW 300 CFM
EWT |
| WATER PRESSURE DROP (ft wg) | COOLING — EAT 80 F DB/67 F WB |
| HEATING — EAT 70 F |
| |||||||||
GPM | Without Motorized | With Cv = 2.9 |
|
|
| Input |
|
|
|
| Input |
|
| ||
(F) | TC | SC | SHR |
| THR | TC |
|
| THA | ||||||
| Valve | MOPD = 125 psi | Power |
|
| Power |
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
| 1.3 | 2.2 | 2.4 |
|
|
|
|
|
| Operation not recommended | ||||
20 |
| 1.9 | 3.9 | 4.4 |
| Operation not recommended |
| ||||||||
|
|
|
|
|
|
|
| ||||||||
|
| 2.5 | 6.2 | 7.0 |
|
|
|
|
|
| 7.2 |
| 0.63 |
| 5.1 |
|
| 1.3 | 1.8 | 2.0 | 11.3 | 7.6 | 0.67 | 0.48 |
| 13.0 | 7.5 |
| 0.66 |
| 5.2 |
30 |
| 1.9 | 3.2 | 3.6 | 11.7 | 7.7 | 0.66 | 0.44 |
| 13.2 | 7.6 |
| 0.67 |
| 5.4 |
|
| 2.5 | 5.0 | 5.8 | 11.9 | 7.8 | 0.66 | 0.42 |
| 13.3 | 7.7 |
| 0.67 |
| 5.4 |
|
| 1.3 | 1.3 | 1.5 | 10.9 | 7.4 | 0.68 | 0.54 |
| 12.8 | 8.1 |
| 0.69 |
| 5.8 |
40 |
| 1.9 | 2.6 | 3.0 | 11.2 | 7.5 | 0.67 | 0.49 |
| 12.9 | 8.4 |
| 0.70 |
| 6.0 |
|
| 2.5 | 4.0 | 4.7 | 11.3 | 7.6 | 0.67 | 0.47 |
| 13.0 | 8.6 |
| 0.71 |
| 6.2 |
|
| 1.3 | 1.3 | 1.5 | 10.6 | 7.2 | 0.68 | 0.60 |
| 12.6 | 9.1 |
| 0.72 |
| 6.6 |
50 |
| 1.9 | 2.5 | 2.9 | 10.8 | 7.3 | 0.68 | 0.56 |
| 12.7 | 9.4 |
| 0.73 |
| 6.9 |
|
| 2.5 | 3.9 | 4.6 | 10.9 | 7.4 | 0.67 | 0.53 |
| 12.8 | 9.7 |
| 0.74 |
| 7.1 |
|
| 1.3 | 1.2 | 1.4 | 10.2 | 7.1 | 0.69 | 0.67 |
| 12.5 | 10.1 |
| 0.75 |
| 7.6 |
60 |
| 1.9 | 2.4 | 2.8 | 10.4 | 7.2 | 0.69 | 0.62 |
| 12.6 | 10.6 |
| 0.77 |
| 8.0 |
|
| 2.5 | 3.7 | 4.4 | 10.6 | 7.2 | 0.68 | 0.60 |
| 12.6 | 10.9 |
| 0.77 |
| 8.2 |
|
| 1.3 | 1.2 | 1.3 | 9.8 | 6.9 | 0.71 | 0.75 |
| 12.4 | 11.3 |
| 0.79 |
| 8.6 |
70 |
| 1.9 | 2.2 | 2.7 | 10.1 | 7.0 | 0.70 | 0.70 |
| 12.5 | 11.9 |
| 0.80 |
| 9.1 |
|
| 2.5 | 3.5 | 4.2 | 10.2 | 7.1 | 0.69 | 0.67 |
| 12.5 | 12.2 |
| 0.81 |
| 9.4 |
|
| 1.3 | 1.1 | 1.3 | 9.3 | 6.8 | 0.73 | 0.83 |
| 12.1 | 12.5 |
| 0.82 |
| 9.7 |
80 |
| 1.9 | 2.1 | 2.5 | 9.6 | 6.9 | 0.71 | 0.78 |
| 12.3 | 13.1 |
| 0.83 |
| 10.3 |
|
| 2.5 | 3.2 | 4.0 | 9.8 | 6.9 | 0.71 | 0.75 |
| 12.4 | 13.5 |
| 0.84 |
| 10.6 |
|
| 1.3 | 1.1 | 1.2 | 9.0 | 6.7 | 0.74 | 0.87 |
| 12.0 | 13.1 |
| 0.83 |
| 10.2 |
85 |
| 1.9 | 2.0 | 2.4 | 9.4 | 6.8 | 0.72 | 0.82 |
| 12.2 | 13.7 |
| 0.85 |
| 10.8 |
|
| 2.5 | 3.1 | 3.9 | 9.6 | 6.9 | 0.72 | 0.79 |
| 12.3 | 14.1 |
| 0.86 |
| 11.2 |
|
| 1.3 | 1.0 | 1.2 | 8.7 | 6.5 | 0.75 | 0.92 |
| 11.8 | 13.7 |
| 0.85 |
| 10.8 |
90 |
| 1.9 | 2.0 | 2.4 | 9.1 | 6.7 | 0.74 | 0.86 |
| 12.0 | 14.3 |
| 0.87 |
| 11.4 |
|
| 2.5 | 3.0 | 3.8 | 9.3 | 6.8 | 0.73 | 0.83 |
| 12.1 | 14.7 |
| 0.88 |
| 11.7 |
|
| 1.3 | 1.0 | 1.2 | 7.9 | 6.2 | 0.79 | 1.01 |
| 11.3 |
|
|
|
|
|
100 |
| 1.9 | 1.9 | 2.3 | 8.4 | 6.4 | 0.77 | 0.95 |
| 11.6 |
|
|
|
|
|
|
| 2.5 | 3.0 | 3.7 | 8.6 | 6.5 | 0.76 | 0.92 |
| 11.8 | Operation Not Recommended | ||||
|
| 1.3 | 1.0 | 1.2 | 6.9 | 5.7 | 0.83 | 1.10 |
| 10.7 | |||||
|
|
|
|
|
|
|
| ||||||||
110 |
| 1.9 | 2.0 | 2.4 | 7.5 | 6.0 | 0.80 | 1.04 |
| 11.1 |
|
|
|
|
|
|
| 2.5 | 3.1 | 3.8 | 7.8 | 6.2 | 0.79 | 1.02 |
| 11.3 |
|
|
|
|
|
| LEGEND |
DB | — Dry Bulb |
EAT | — Entering Air Temperature (F) |
EWT | — Entering Water Temperature (F) |
GPM | — Gallons per Minute |
MBtuh — Btuh in Thousands | |
SC | — Sensible Capacity (MBtuh) |
SHR | — Sensible Heat Ratio |
TC | — Total Capacity |
THA | — Total Heat of Absorption (MBtuh) |
THR | — Total Heat of Rejection (MBtuh) |
WB | — Wet Bulb |
WLHP | — Water Loop Heat Pump |
*ARI 320 points (bold printing) are shown for comparison purposes only. These are not certified data points.
NOTES:
1.MOPD = Maximum Operating Pressure Differential (water pres- sure differential at unit cannot exceed MOPD or water valve can- not close)
2.Interpolation is permissible, extrapolation is not.
3.All entering air conditions are 80 F db and 67 F wb in cooling and 70 F db in heating.
4.All performance data is based upon the lower voltage of dual volt- age rated units. See Performance Correction Tables on page 21 for operating conditions other than those listed above.
5.ARI/ISO
17