Carrier 50KQL-1PD manual Wshp sound control, Console units, Operating limits, Starting conditions

Page 24

Application data (cont)

OCTAVE BAND SOUND PRESSURE LEVEL (Lp)

ASSOCIATED WITH NC CURVES

NOISE

 

 

OCTAVE BAND SOUND PRESSURE LEVEL (Lp)

 

CRITERIA

 

 

 

 

Frequency (Hz)

 

 

 

CURVES

 

63

125

250

500

1000

 

2000

4000

8000

 

 

 

NC-15

49

36

26

17

17

 

14

12

11

NC-20

52

41

33

27

22

 

19

17

16

NC-25

54

45

38

31

27

 

24

22

21

NC-30

58

49

41

36

31

 

29

28

27

NC-35

61

53

45

40

36

 

34

33

32

NC-40

64

57

50

45

41

 

39

38

37

NC-45

67

61

54

49

46

 

44

43

42

NC-50

71

64

58

54

51

 

49

48

47

NC-55

74

68

63

58

56

 

54

53

52

NC-60

77

71

67

63

61

 

59

58

57

NC-65

80

75

71

68

66

 

64

63

62

WSHP sound control

Analyzing the projected sound level in the conditioned space caused by a WSHP unit is quite involved. The key is to have good sound power ratings (Lw) in dB on the equip- ment to determine the ductwork, ceiling and room sound attenuation effect.

Console units

With console units, the fan and compressor are located within the space, and only the casing design attenuates the transmission of sound sources into the space. The designer should carefully review the manufacturer’s acoustical data when selecting console units and use lower fan speeds to minimize space noise.

Operating limits

Environment

This equipment is designed for indoor installation ONLY.

Power supply

A voltage variation of ± 10% of nameplate utilization volt- age is acceptable.

Starting conditions

The 50KQL unit will start and operate in an ambient tem- perature of 50 F, with entering air temperature at 50 F, with entering water temperature at 60 F, with both air and water at the flow rates used in the ARI/ISO Standard 13256-1 rating test, for initial start-up in winter.

NOTE: These are not normal or continuous operating conditions. Such a start-up should be used to bring the building space up to occupancy temperature.

AIR LIMITS

 

 

50KQL

 

Cooling

 

Heating

Min. Ambient Air

50 F

 

50 F

Rated Ambient Air

80 F

 

66 F

Max. Ambient Air

100 F

 

86 F

Min. Entering Air

50 F

 

50 F

Rated Entering Air, db/wb

80/66 F

 

68 F

Max. Entering Air, db/wb

100/82 F

 

80 F

WATER LIMITS

 

 

 

 

50KQL

 

 

 

Cooling

 

Heating

Min. Entering Water

30 F*

 

21 F*

Normal Entering Water

86 F

 

70 F

Max. Entering Water

110 F

 

90 F

LEGEND

 

 

 

db

Dry Bulb

 

 

 

wb

Wet Bulb

 

 

 

*Requires optional extended range insulation package when operating below the dew point.

NOTES:

1.Minimum Air and Water conditions can only be used at ARI/ISO 13256-1 flow rates.

2.The 50KQL units may have up two values at maximum or minimum with all other param- eters at normal conditions.

Solenoid valves

In applications using variable flow pumping, solenoid valves can be factory installed and operated from the con- trol board in the Aquazone™ WSHP unit.

Freeze protection

Applications where systems are exposed to outdoor temperatures below freezing (32 F) must be protected from freezing. The most common method of protecting water systems from freezing is adding glycol concentrations into the water. Use design care when selecting both the type and concentrations of glycol due to the following:

Equipment and performance may suffer with high con- centrations of glycol and other antifreeze solutions

Loss of piping pressure may increase greatly, resulting in higher pumping costs

Higher mixture viscosity may cause excess corrosion and wear on the entire system

The water’s acidity may be greatly increased, promoting corrosion

Glycol promotes galvanic corrosion in systems of dissimilar metals. The result is corrosion of one metal by the other, causing leaks.

Electrical data

50KQL

 

VOLTS-PHASE

VOLTAGE

COMPRESSOR

FAN MOTOR

TOTAL UNIT

MIN CIRCUIT

MAX FUSE/

 

 

(60 Hz)

Min

Max

RLA

LRA

FLA

FLA

AMP

HACR

 

 

115-1

104

127

7.1

46.5

0.50

7.6

9.3

15

07

 

208/230-1

187

253

3.7

19.0

0.33

4.0

5.0

15

 

 

265-1

239

291

2.8

16.0

0.35

3.1

3.8

15

 

 

115-1

104

127

9.0

46.5

1.30

10.3

12.5

20

09

 

208/230-1

187

253

4.7

23.0

0.50

5.2

6.3

15

 

 

265-1

239

291

3.8

16.0

0.50

4.3

5.3

15

 

 

115-1

104

127

10.6

63.0

1.30

11.9

14.6

25

12

 

208/230-1

187

253

6.1

29.0

0.50

6.6

8.1

15

 

 

265-1

239

291

4.8

21.6

0.50

5.3

6.5

15

15

 

208/230-1

187

253

7.0

33.2

1.10

8.1

9.8

15

 

265-1

239

291

5.4

29.0

1.00

6.4

7.8

15

 

 

19

 

208/230-1

187

253

7.7

38.0

1.10

8.8

10.7

15

 

265-1

239

291

5.8

29.0

1.00

6.8

8.2

15

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

FLA — Full Load Amps

 

 

 

 

 

 

 

 

HACR — Heating, Air Conditioning and Refrigeration

 

 

 

 

 

 

 

LRA — Locked Rotor Amps

 

 

 

 

 

 

 

 

RLA —

Rated Load Amps

 

 

 

 

 

 

 

 

24

Image 24
Contents Features/Benefits Operating efficiencyTable of contents Features/Benefits Model number nomenclature Q L 0 7 S a E C 1 0 1 a aARI/ISO 13256-1 capacity ratings Physical dataOptions and accessories Factory-installed optionsField-installed accessories 50KQL Control Options TableCarrier Aquazone Thermostats Premierlink Communicating ControlDimensions 50KQL Bottom Return Cabinet Dimensions Right Hand Piping50KQL Bottom Return Cabinet Dimensions Left Hand Piping Rear View Access Damper OP Ening50KQL Front Return Cabinet Dimensions Right Hand Piping Rear Access50KQL Front Return Cabinet Dimensions Left Hand Piping Rear Access Rear View50KQL Chassis Dimensions Size 07, 09, 12, 15 Selection procedure with 50KQL12 example Page Performance data 50KQL07 Nominal Airflow 240 CFM50KQL09 Nominal Airflow 300 CFM 12.212.3 11050KQL12 Nominal Airflow 350 CFM 50KQL15 Nominal Airflow 400 CFM 17.6 13.813.9 10.4 17.6 50KQL19 Nominal Airflow 460 CFM 15.116.7 11.5 21.1 Correction Factors Entering AIR Correction Factors AirflowApplication data Water loop systemGround water systems Ground loop systemsCondensate drainage Water conditioningAcoustical design Water Quality GuidelinesWshp sound control Console unitsOperating limits Starting conditionsTypical wiring schematics Manual Changeover with Complete C ControllerManual Changeover with Deluxe D Controller CB* NoteAutomatic Changeover with Complete C Controller High FANAutomatic Changeover with Deluxe D Controller UMTTransformer Water Valve Field Line Voltage Wiring REMOTE-MOUNTED Thermostat with Complete C ControllerREMOTE-MOUNTED Thermostat with Deluxe D Controller Supply Air Temperature Sensor Space Temperature SensorPremierlink Controller Applications with Complete C Control Premierlink Controller Applications with Deluxe D ControlTypical piping 50KQL Piping DetailGuide specifications Console Water Source Heat PumpsGuide specifications Page Carrier Corporation Syracuse, New York