CORRECTION FACTORS — ENTERING AIR
| HEATING |
|
|
|
|
|
| COOLING |
|
|
|
|
| ||
EAT |
| Input |
| EAT |
|
| Sensible Capacity Entering Dry Bulb (F) |
| Power |
| |||||
DB | TC | THA | WB | TC |
|
|
|
|
|
|
|
| THR | ||
Power | 70 | 75 | 80 | 80.6 |
| 85 | 90 | 95 | Input | ||||||
(F) |
|
| (F) |
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
60 | 1.011 | 0.989 | 1.007 | 60 | 0.893 | 0.889 | 1.087 | * | * |
| * | * | * | 0.964 | 0.902 |
65 | 1.004 | 0.994 | 1.004 | 65 | 0.964 | 0.692 | 0.884 | 1.085 | 1.108 |
| * | * | * | 0.988 | 0.967 |
68 | 1.002 | 0.997 | 1.002 | 66.2 | 0.983 | 0.645 | 0.838 | 1.036 | 1.059 |
| 1.231 | * | * | 0.995 | 0.985 |
70 | 1.000 | 1.000 | 1.000 | 67 | 1.000 | 0.613 | 0.806 | 1.000 | 1.027 |
| 1.199 | * | * | 1.000 | 1.000 |
75 | 0.996 | 1.007 | 0.995 | 70 | 1.049 | — | 0.683 | 0.879 | 0.902 |
| 1.077 | 1.274 | 1.415 | 1.016 | 1.046 |
80 | 0.991 | 1.018 | 0.990 | 75 | 1.118 | — | — | 0.676 | 0.698 |
| 0.866 | 1.068 | 1.266 | 1.037 | 1.106 |
*Sensible Capacity equals total capacity.
CORRECTION FACTORS — AIRFLOW
| % OF |
| COOLING CORRECTIONS |
| HEATING CORRECTIONS | |||||
NOMINAL | TC |
| SC | Input |
| THR | TC | Input | THA | |
AIRFLOW |
| Power |
| Power | ||||||
|
|
|
|
|
|
| ||||
| 75% | 0.951 |
| 0.860 | 0.963 |
| 0.952 | 0.990 | 1.054 | 0.966 |
| 81% | 0.964 |
| 0.894 | 0.973 |
| 0.965 | 0.993 | 1.035 | 0.977 |
| 88% | 0.979 |
| 0.936 | 0.984 |
| 0.979 | 0.996 | 1.019 | 0.987 |
| 94% | 0.990 |
| 0.969 | 0.992 |
| 0.990 | 0.998 | 1.008 | 0.994 |
| 100% | 1.000 |
| 1.000 | 1.000 |
| 1.000 | 1.000 | 1.000 | 1.000 |
| 106% | 1.010 |
| 1.033 | 1.008 |
| 1.010 | 1.002 | 0.994 | 1.005 |
| 113% | 1.019 |
| 1.069 | 1.016 |
| 1.019 | 1.003 | 0.988 | 1.011 |
|
| LEGEND |
|
|
|
|
|
| ||
DB | — Dry Bulb |
|
|
|
|
|
|
|
| |
EAT — Entering Air Temperature (F) |
|
|
|
|
|
| ||||
SC | — Sensible Capacity |
|
|
|
|
|
| |||
TC | — Total Capacity |
|
|
|
|
|
|
|
|
THA — Total Heat of Absorption
THR — Total Heat of Rejection
50KQL CONSOLE BLOWER PERFORMANCE 60 Hz
| RATED | AIRFLOW (cfm) | |
50KQL | AIRFLOW | Low Speed | High Speed |
| (cfm) | ||
|
|
| |
07 | 240 | 190 | 240 |
09 | 300 | 240 | 300 |
12 | 350 | 300 | 350 |
15 | 400 | 340 | 400 |
19 | 460 | 400 | 460 |
NOTES:
1.Fan speed is field adjustable.
2.All airflow is rated at lowest voltage if unit is dual voltage rated, i.e., 208 v for
3.All units are ARI/ISO
4.All units are designed and rated for zero external static pressure
21